 The compressor must only be used 

for its designed purpose(s) and within its 

scope of application (refer to «operating 

limits»). 

Consult Application guidelines and da-

tasheet available from cc.danfoss.com

 Under all circumstances, the 

EN378 (or  other applicable local 

safety regulation) requirements 

must be fulfilled.

The compressor is delivered under 

nitrogen gas pressure (between 0.3 

and 0.7 bar) and hence cannot be 

connected as is; refer to the «assem-

bly»

 

section for further details.

The compressor must be 

handled with caution in the 

vertical position (maximum 

offset from the vertical : 15°)

© Danfoss | DCS(CC) | 2016.04

FRCC.PI.036.A2.021 - 8510278P01B

Danfoss MLZ/MLM116 scroll compressors  compressors’

 

motors are protected by an external module protecting against phase loss/reversal, over heating 

and high current draw. 

Fuses ..........................................................................................F1

Compressor contactor .........................................................KM

Control relay ...........................................................................KA

Safety lock out relay .............................................................. KS

Optional short cycle timer (3 min)  ............................... 180 s

External overload protection ...............................................F2

Pump-down pressure switch ...............................................LP

High pressure safety switch.................................................HP

Control device .........................................................................TH

Liquid Line Solenoid valve ............................................... LLSV

Discharge gas thermostat ................................................DGT

Fused disconnect ...................................................................Q1

Motor safety thermostat ................................................... thM

Compressor motor ................................................................. M

Motor Protection Module ............................................... MPM

Thermistor chain.......................................................................S

Safety pressure switch ........................................................ LPS

A1

A3

A2

MPM

S

KS

Wiring diagram without pump-down cycle

LPS

A1

A3

A2

MPM

S

LPS

Wiring diagram with pump-down cycle

LP

Installation and servicing of the compressor by qualified personnel only. Follow 
these instructions and sound refrigeration engineering practice relating to 

installation, commissioning, maintenance and service.

A

D

B

C

E

F

A

:  Model number  

D

:  Supply voltage, Starting current & Maximum operating current

B

:   Serial  number 

E

:  Housing service pressure

C

:   Refrigerant   

F

:  Factory charged lubricant

R404A 

R22 

0

5

10

15

20

25

30

35

40

45

50

55

60

65

70

-35

-30

-25

-20

-15

-10

-5

0

5

10

15

SH = 10K

RGT = 20°C          

0

5

10

15

20

25

30

35

40

45

50

55

60

65

70

-35

-30

-25

-20

-15

-10

-5

0

5

10

15

SH = 10K

RGT = 20°C          

Danfoss scroll compressors

MLZ/MLM116

 

Instructions