FRCC.EI.002.A1.02 © Danfoss Commercial Compressors 04/08

  The  compressor  must  only  be 

used for its designed purpose(s) and 

within its scope of application (refer 

to «operating limits»). 

Consult Application guidelines and da-

tasheet available from cc.danfoss.com

The compressor is delivered under 

nitrogen  gas  pressure  (between  0.3 

and 0.7 bar) and hence cannot be 

connected  as  is;  refer  to  the  «as-

sembly»

 

section for further details.

  Under  all  circumstances,  the 

EN378 (or other applicable local safety 

regulation)  requirements  must  be 

fulfilled.

The compressor must be handled 

with  caution  in  the  vertical  posi-

tion  (maximum  offset  from  the 

vertical : 15°)

 

Operating limits

MT

MTZ

MTZ

MTZ

NTZ

R22

R407C

R134a

R404A / R507A

High side pressure range

bar (g)

10,9 - 27,7

12,5 - 29,4

7,9 - 22,6

13,2 - 27,7

13,2 - 27,7

Low side pressure range

bar (g)

1,0 - 7,0

1,4 - 6,6

0,6 - 4,7

1,0 - 7,2

0,1 - 3,3

Discharge temperature must be kept lower than 130°C

Housing 

Service

 Pressure

Lubricant 

Supply Voltage 
Maximum current
 Starting current

Model 

Number

Serial 

Number

1" : 80 Nm

1"1/4 : 90 Nm

1"3/4 : 110 Nm

Installation and servicing of the compressor by qualified personnel only. Follow these instructions and sound refrigeration engineering 
practice relating to installation, commissioning, maintenance and service.

HM8-40

15 Nm

230 V

A + C

Thermostat

C

S

R

IOL

   

  PSC

    

 CSR

3

230 V 

Thermostat

BµF

Start Relay

5

2

1

15 kΩ -1 w

C

S

R

IOL

A + C

C

R

S

C

R

S

 

Never operate compressors without terminal cover fitted 

15 Nm

HM12-50

INSTRuCTIONS

MT / MTZ / NTZ COMPReSSORS 