background image

Installation notes

DANLERS Limited, Vincients Road, CHIPPENHAM, Wiltshire, SN14 6NQ, UK.
Telephone: +44 (0)1249 443377   Fax: +44 (0)1249 443388   
E-mail: sales@danlers.co.uk    Web: 

www.danlers.co.uk

Company Registered Number 2570169   VAT Registration Number 543 5491 38

Products available from DANLERS

•  PIR occupancy switches • Daylight linked dimmers • Manual high frequency dimmers 

•  Photocells • Radio remote controls • Time lag switches • Outdoor security switches 

•  Dimmers • Heating, ventilation and air-conditioning controls • Bespoke / O.E.M. products

Please call for more information or a free catalogue, or visit our website.

This product conforms to BS EN 60669-2-1, BS EN 55015 and BS EN 60730.
Please ensure the most recent edition of the appropriate local wiring regulations are observed 

and suitable protection is provided (protected with the appropriate MCB) 1kV over voltage. 

Please ensure that this device is disconnected from the supply if an insulation test is made. 
This product is covered by a warranty which extends to 5 years from the date of manufacture.

Precautions and Warranty 

15/09/16

INS311 EZ CESR

Variants

DANLERS design and manufacture other EasyZAPP Ceiling Flush Mounted 

variants, coded by the following order codes: 

EZ CESR 10VDC 

  Suitable for 1-10VDC ballasts 

EZ CESR DALI 

  Suitable for DALI ballasts.

Troubleshooting

The load will not switch on:

 

• The LUX setting as specified by the EasyZAPP App is set too low and is inhibiting 

the switch. 

• The moving body is not emitting more IR than the background. 

    (Person wearing insulating clothing in a warm environment) 

• Person is too far from the PIR switch, see detection diagram. 

• Person is moving unusually slowly (perhaps when testing). 

• The control unit battery is not engaged (ON). 

    Switch RED dip switch next to the telejack connector on the EZ CESR  

    control unit towards the centre of the control (see diagram D).

The load switches on when nobody is present:

 

• Heater causing infra-red variations in a small cold room. 

    Resite the EZ CESR control away from heater. 

• Please contact DANLERS for further technical support.  

   

  EasyZAPP Ceiling flush mounted switches

  EZ CESR 

EasyZAPP ControlZAPP ceiling surface passive infra-red occupancy switches can 

be mounted directly onto solid ceilings or onto a range of different mounting boxes 

(diagram A). EasyZAPP devices incorporate a passive infra-red quad sensor to detect 

movement of a warm body within their detection zone (diagram B) and a photocell to 

monitor the ambient light level. 

Please Note: ALL adjustments  are made via a freely downloadable EasyZAPP 

App available from the DANLERS website. EasyZAPP products cannot be 

configured by DANLERS ControlZAPP or ScheduleZAPP apps.

Upon detecting movement, if the ambient light is dark enough, the EasyZAPP device 

will turn the load ON. The ambient threshold can be set to between approximately 

30 lux to 1000 lux and infinite lux (photocell inactive) via the ‘Brightness’ settings on 

the EasyZAPP App. If no more movement is detected within a pre-selected time as 

determined by the EasyZAPP App, then the EasyZAPP device will turn the load off. 

This ‘Timeout’ or time lag can be set via the EasyZAPP App adjuster between 10sec 

and 23hrs 59min 59sec. 

Loading

 

EZ CESR is suitable for mains switching or DALI switching only. 

EZ CESR can switch up to:
•  10 amps (3000W) of resistive loads 

•  6 amps (1500W) fluorescent lamps, high frequency or switch start,  

  incandescent or mains halogen lamps (recommended with integral safety fuse) 

•  3 amps (750W) of electronic or wire wound transformers.
•  2 amps (500W) of low energy lamps: CFL, LED, 2D etc.
•  1 amp (250W) of fans or most metal halide lamps.

Start-up mode and Default settings

When the EZ CESR is powered up, it will take 1 minute for the circuitry to stabilise 

(detection LED flashing) and ensure the output is off, the EasyZAPP device will then 

enter its Default Operating Mode. 

Please Note:

 When in the Default Operating Mode the EZ CESR is set up as 

an occupancy switch with a 20 minute turn OFF timeout (time lag) and photocell 

disabled.