Installation notes

DANLERS Limited, Vincients Road, CHIPPENHAM, Wiltshire, SN14 6NQ, UK.

Telephone: +44 (0)1249 443377   Fax: +44 (0)1249 443388   

E-mail: sales@danlers.co.uk    Web: 

www.danlers.co.uk

Company Registered Number 2570169   VAT Registration Number 543 5491 38

Products available from DANLERS

•  PIR occupancy switches • Daylight linked dimmers • Manual high frequency dimmers 

•  Photocells • Radio remote controls • Time lag switches • Outdoor security switches 

•  Dimmers • Heating, ventilation and air-conditioning controls • Bespoke / O.E.M. products

Please call for more information or a free catalogue, or visit our website.

This product conforms to BS EN 60669-2-1.
Please ensure the most recent edition of the appropriate local wiring regulations are observed 

and suitable protection is provided e.g. 13 amps over current, 1kV over voltage. Please ensure 

that this device is disconnected from the supply if an insulation test is made. 
This product is covered by a warranty which extends to 5 years from the date of manufacture.

Precautions and Warranty 

  Plated heater boost / multi-selector switches

  TLSW HB       

TLSW HB1246 

TLSW HB BP     

  TLSW HB BP1246  TLSW MS       

TLSW MS1246

DANLERS plated heater boost/multi-selector switch can be mounted 

onto a standard back box and needs a neutral connection. It can switch 

a  resistive  heating  load  up  to  3kW. The  plate  incorporates  four  red 

LEDs, each representing a different remaining time range. Each time 

the button is pressed the remaining time advances to the next value, 

giving a longer time lag. If the button is pressed when the fourth LED 

is lit the load is switched off. The switches can be wired in parallel with 

any other relay  output timers as a manual override.
The four time lags periods are as follows:
TLSW HB 

Marked ‘HEATINg BOOST’ plate with ¼, ½, 1 

 

   

and 2 hour periods

TLSW HB1246 

Marked ‘HEATINg BOOST’ plate with 1, 2, 4 

 

   

and 6 hour periods 

TLSW MS 

Marked plate with ¼, ½, 1 and 2 hour periods

 

TLSW MS1246 

Marked plate with 1, 2, 4 and 6 hour periods

 

TLSW HB BP 

Blank plate with ¼, ½, 1 and 2 hour periods

 

TLSW HB BP1246  Blank plate with 1, 2, 4 and 6 hour periods

These switches can only be connected to a 230V, 50Hz ac supply.

 

They can switch up to 13 amps (3000W) of resistive loads

 

or they can 

also switch up to 1 amp (250W) of fans

For larger loads they can be 

used to operate a contactor.

Installation procedure

1.  Please read these notes carefully before commencing work.

 

In case of doubt please consult a qualified electrician.

 

Make sure the power is isolated from the circuit.

 

Remove the top and bottom lugs if using a 4 lug metal back box.

2.  The TLSW HB / MS  switches have a  terminal block on the reverse, 

 

which should be connected as shown in wiring diagram overleaf:

  L  

Live input

 

SL  

Switched Line output

 

Neutral (two neutral terminals are available)

3.  Turn on the supply and test the function of the switch.

15/11/13

INS992 TLSWHB

Troubleshooting

The heater boost / multi-selector switch resets itself off: 

•  The supply to the heater boost / multi-selector switch must be 

 

  permanent, it should not be wired in series after another timer 

 

  device.

The main heating timer is not functioning: 

•  The heater boost / multi-selector switch can only be wired in 

parallel with relay output timer units, otherwise the output of the 

other timer may be damaged.

Loading

Wiring diagram

NEUTRAL  

Heater Boost / Multi-selector

LOAD

LIVE  

NEUTRAL   

~ 230 Vac

SL   

L   

N   