background image

CAUTION

Install or remove modules from the shelf only when the power is off.

If you install a module in the shelf with the power on, the internal
circuitry may suffer damage and the product warranty will be void.

Remove and install circuit boards only in a static-safe environment

(use antistatic wrist straps, smocks, footwear, etc.).

Keep circuit boards in their antistatic bags when they are not in use.

Do not ship or store circuit boards near strong electrostatic, electromag-

netic, magnetic, or radioactive fields.

For more complete information on electrostatic discharge safety

precautions, refer to Bellcore

TM

 Technical Reference # TR-NWT-000870.

Copyright 1999 by Dantel, Inc. • Dantel is a registered trademark of Dantel, Inc. • ISO 9001 Registered

Printed in the U.S.A.

46112 

SynchMaster

D

ATA

 C

ONTROLLER

 M

ODULE

46113 

SynchMaster

D

ATA

 P

ORT

 M

ODULE

I

NSTALLATION

 & O

PERATION

 M

ANUAL

46112/113-0299 <90-00032>

About this Practice:

This practice has been reissued to:
• Update the 46113 strapping

options in the 

Installation section.

Issue date:  February 1999

Reissued Practices: Updated and
new content can be identified by a
banner in the right margin.

UPDATED

Table of Contents

Ordering Information ...........................................................................  2

General Description ..............................................................................  2

Circuit Description ...............................................................................  2

Application Information .......................................................................  6

Installation ..........................................................................................  11

Operation ............................................................................................  20

Technical Specifications .....................................................................  21

Warranty .............................................................................................  22

Summary of Contents for SynchMaster 46112

Page 1: ... discharge safety precautions refer to BellcoreTM Technical Reference TR NWT 000870 Copyright 1999 by Dantel Inc Dantel is a registered trademark of Dantel Inc ISO 9001 Registered Printed in the U S A 46112 SynchMaster DATA CONTROLLER MODULE 46113 SynchMaster DATA PORT MODULE INSTALLATION OPERATION MANUAL 46112 113 0299 90 00032 About this Practice This practice has been reissued to Update the 461...

Page 2: ...at fit into any 400 type or similar equipment housing CIRCUIT DESCRIPTION Figures 1 and 2 show the functional schematics for the 46112 SynchMaster Data Controller Module and the 46113 SynchMaster Data Port Module respectively FIG 1 FUNCTIONAL SCHEMATIC 46112 5 2 1 TXC INPUT RXC INPUT RXC INPUT 6 8 7 RESERVED RESERVED RESERVED FRAMING GENERATION MICRO PROCESSOR TX INSERT LED RS 422 DRIVERS AND RECE...

Page 3: ... sequences the data to and from the microprocessor Proper sequencing prevents the data from individual ports becoming intermixed Microprocessor The microprocessor is resident for completing asynchronous synchronous conversion of the data as well as multiplexing the data Status Indicating LEDs The 46112 SynchMaster module s green status indicating LEDs are designated as follows TX INSERT When data ...

Page 4: ...ALLEL DATA UART CONFIGURATION SWITCHES PARALLEL DATA UART CONFIGURATION SWITCHES DATA 5 VDC OUTPUT 5 VDC REGULATOR POWER SUPPLY TERMINATION RESISTORS XPORT R W TTL BUSS XRST XUART SW DATA BUS XD1 DATA BUS XD0 DATA BUS XD3 DATA BUS XD2 DATA BUS XD5 DATA BUS XD4 DATA BUS XD7 DATA BUS XD6 ADDRESS BUSS XA1 ADDRESS BUSS XA0 ADDRESS BUSS XA3 ADDRESS BUSS XA2 ADDRESS BUSS XA5 ADDRESS BUSS XA4 ADDRESS BUS...

Page 5: ...he 46112 SynchMaster module s microprocessor reads con figuration switches which programs the 46113 SynchMaster module s UARTs The switches determine the operating mode the number of data and stop bits the parity and the baud data transmission rate and set the channel number Status Indicating LEDs There are two sets of four green front panel LEDs The top four LEDs are labeled TXD ports A to D and ...

Page 6: ...the same as two terminal setups In this mode you can transmit and receive data from two different directions You can drop data received from the west direction of the 46112 SynchMaster Module to the 46113 SynchMaster Module You can also repeat transmit through the east direction line side through the other 46112 SynchMaster Module You can also transmit data from east to west Fig 6 shows a repeater...

Page 7: ...GE 7 FIG 3 TERMINAL MODE APPLICATION TO FACILITY DIGITAL TRANSMISSION EQUIPMENT TERMINAL MODE APPLICATION 1 2 8 29 30 31 32 5 6 7 8 1 2 3 4 A B C D A B C D A B C D 4 6 1 1 3 4 6 1 1 3 4 6 1 1 3 4 6 1 1 2 APPLICATION INFORMATION ...

Page 8: ...NS 41 55 EVEN NUMBERED PINS 42 56 PORT A CONNECTIONS PORT B CONNECTIONS PORT C CONNECTIONS PORT D CONNECTIONS RST R W UART SW PORT 36 38 39 40 36 38 39 40 36 38 39 40 36 38 39 40 ODD NUMBERED PINS 41 55 EVEN NUMBERED PINS 42 56 ODD NUMBERED PINS 41 55 EVEN NUMBERED PINS 42 56 PARALLEL CONNECTIONS TO ALL OTHERS 46113s 5 VDC 22 22 TRANSMIT CLOCKISINPUT RECEIVE 46112 8 7 TXC0 17 _ _ _ _ _ 9 10 5 6 3 ...

Page 9: ... REPEATER MODE APPLICATION APPLICATION INFORMATION EAST DIGITAL TRANSMISSION EQUIPMENT WEST DIGITAL TRANSMISSION EQUIPMENT REPEATER APPLICATION TO OTHER PORTS TO OTHER PORTS 1 2 3 4 1 2 3 4 A B C D A B C D 4 6 1 1 3 4 6 1 1 2 4 6 1 1 3 4 6 1 1 2 ...

Page 10: ...EATER TERMINAL MODE APPLICATION EAST DIGITAL TRANSMISSION EQUIPMENT WEST DIGITAL TRANSMISSION EQUIPMENT TERMINAL REPEATER APPLICATION TO OTHER PORTS TO OTHER PORTS 1 2 3 4 1 2 3 4 4 6 1 1 3 4 6 1 1 2 4 6 1 1 3 4 6 1 1 2 APPLICATION INFORMATION ...

Page 11: ...ints that allow terminating resistors for use on the receiver circuits The resistors are labeled TRMA TRMB TRMC and TRMD When placed in the T position the terminating resistor connects across the RS 422 differential inputs When placed in the O position the terminating resistors do not connect To prevent a misleading front panel indicator place in the G position for all applications except those us...

Page 12: ...BASSEMBLY STRAPPING OPTIONS POSITION STRAPS X1 X2 X3 and X4 G RS232 T RS422 O RS422 RS232 RS422 TERMINATED RS422 NON TERMINATED 1 2 RS 232 2 3 TERMINATED 2 4 RS 422 UNTERMINATED NOTE S5 OPEN 1 2 3 4 5 6 7 8 1 2 3 4 5 S1 S6 S2 OPEN 1 2 3 4 5 6 7 8 1 2 3 4 5 OPEN OPEN OPEN 1 2 3 4 5 6 7 8 1 2 3 4 5 S3 S8 S4 OPEN 1 2 3 4 5 6 7 8 1 2 3 4 5 OPEN OPEN S7 POWER SUPPLY X1 X2 X3 X4 1 2 3 1 2 3 4 1 2 3 1 2 ...

Page 13: ... 8 OFF ON OFF OFF OFF 9 OFF ON OFF OFF ON 10 OFF ON OFF ON OFF 11 OFF ON OFF ON ON 12 OFF ON ON OFF OFF 13 OFF ON ON OFF ON 14 OFF ON ON ON OFF 15 OFF ON ON ON ON 16 ON OFF OFF OFF OFF 17 ON OFF OFF OFF ON 18 ON OFF OFF ON OFF 19 ON OFF OFF ON ON 20 ON OFF ON OFF OFF 21 ON OFF ON OFF ON 22 ON OFF ON ON OFF 23 ON OFF ON ON ON 24 ON ON OFF OFF OFF 25 ON ON OFF OFF ON 26 ON ON OFF ON OFF 27 ON ON OFF...

Page 14: ... port baud address list as well as blank list forms follow the switch settings table below Assign port addresses to the highest baud rates first followed by progressively lower rates Each time an address is assigned note which addresses become unavailable then go on to assign the next port to be used to the next available address Allowable address switch settings for specific data rates are listed...

Page 15: ... 4800 3 11 19 27 OFF OFF OFF ON ON 4800 4 12 20 28 OFF OFF ON OFF OFF 4800 5 13 21 29 OFF OFF ON OFF ON 4800 6 14 22 30 OFF OFF ON ON OFF 4800 7 15 23 31 OFF OFF ON ON ON 2400 0 16 OFF OFF OFF OFF OFF 2400 1 17 OFF OFF OFF OFF ON 2400 2 18 OFF OFF OFF ON OFF 2400 3 19 OFF OFF OFF ON ON 2400 4 20 OFF OFF ON OFF OFF 2400 5 21 OFF OFF ON OFF ON 2400 6 22 OFF OFF ON ON OFF 2400 7 23 OFF OFF ON ON ON 2...

Page 16: ... 3 11 OFF ON OFF ON ON 2D Port 8 1200 Baud 12 OFF ON ON OFF OFF Port 1 13 OFF ON ON OFF ON 3A Port 9 1200 Baud 14 OFF ON ON ON OFF Not Used 15 OFF ON ON ON ON Not Used 16 ON OFF OFF OFF OFF Port 1 17 ON OFF OFF OFF ON Port 2 18 ON OFF OFF ON OFF Port 3 19 ON OFF OFF ON ON Port 4 20 ON OFF ON OFF OFF Port 1 21 ON OFF ON OFF ON Port 5 22 ON OFF ON ON OFF Port 6 23 ON OFF ON ON ON Not Used 24 ON ON O...

Page 17: ...99 90 00032 PAGE 17 SWITCH SETTINGS ADDRESS 1 2 3 4 5 PORT DESCRIPTION 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 INSTALLATION TABLE E BLANK PORT ADDRESS ALLOCATION TABLE ...

Page 18: ...DDRESS BUS TO 46113 46112 Card Edge Connector Pin Outs TXC OUTPUT XA6 XA5 XA4 XD0 XD1 XD2 XD3 XD7 XD6 XD5 XD4 EXTERNAL DATA BUS TO 46113 UART SW 5 VDC INPUT GROUND DC TX TX RESERVED RESERVED RESERVED RESERVED RESERVED RESERVED RESERVED RESERVED INSTALLATION 4 Wire the pin connector Wire the 46112 and 46113 SynchMaster Module connectors in the shelf Refer to Figs 9 and 10 5 Install the modules in t...

Page 19: ...13 12 11 10 9 8 7 6 5 4 3 2 1 CIRCUIT SIDE OF PC BOARD COMPONENT SIDE OF PC BOARD XA0 XA1 XA2 XA3 BATT 21 TO 56 VDC XR W XX XA7 XPORT ADDRESS BUS TO 46112 46113 Card Edge Connector Pin Outs XA6 XA5 XA4 XD0 XD1 XD2 XD3 XD7 XD6 XD5 XD4 DATA BUS TO 46112 XUART SW XRST PORT A TRANSMIT TX TX TD RS 232 RS 422 MPI RS 232 PORT B TRANSMIT TX TX TD RS 232 RS 422 MPI RS 232 PORT C TRANSMIT TX TX TD RS 232 RS...

Page 20: ...ed for the 46112 SynchMaster Module the TX INSERT LED will light TX REPEAT When lit the TX REPEAT LED indicates that data is not being transmitted at the site Either the TX REPEAT or the TX INSERT will be on alternatively 46113 Status indicating LEDs There are two sets of four green front panel LEDs The top four LEDs are labeled TXD ports A to D and light up when the port A B C or D drop side equi...

Page 21: ... Short Circuit Current Output Resistance Maximum Load Resistance 3 to 5 V 3 to 5 V 10 5 V Typical 9 0 Minimum w 3K Ohm Load 9 5 V Typical w No Load 8 V Minimum w 3 K Ohm Load 45 mA Maximum 300 Ohms Minimum 3 K Ohms RS422 Receivers Differential Input Threshold Voltage Common Mode Input Voltage Drivers Differential Output Voltage Short Circuit Current Maximum Load Resistance 0 2 V Referenced to Grou...

Page 22: ...tten instrument signed by a duly authorized officer of the Seller and accepted by the Buyer Warranty and remedies on products not manufactured by the Seller are in accordance with warranty of the respective manufacturer THE SELLER MAKES NO OTHER WARRANTY OF ANY KIND WHATSOEVER EXPRESSED OR IMPLIED AND ALL IMPLIED WARRANTY OF FITNESS FOR A PARTICULAR PUR POSE WHICH EXCEEDS THE AFORESAID OBLIGATIONS...