background image

 

 U:\Manuals\EFC\EFC2V2TC 

-EN-.pdf 

1/15                                                           2008-11-13 

EFC2 V2 TC 

 

 

Service manual 

 

 

 

 

            

 

 

 

 

 

 

Summary of Contents for KONTROLLELEKTRONIK EFC2 V2 TC

Page 1: ...U Manuals EFC EFC2V2TC EN pdf 1 15 2008 11 13 EFC2 V2 TC Service manual...

Page 2: ...0 Spare parts list 11 Test Report TKS 3000 and ACUE 3000 12 Test Report ACUE CS1 14 Contact In the table below you can see how to contact the manufacturer and sales offices Office Sweden Norway Denmar...

Page 3: ...ltage Directive including 93 68 EEC where required 86 336 EEC EMC Directive including 92 31 EEC and 93 68 EEC 89 392 EEC Machine Directive The product is manufactured according to SS EN 604 39 1 The p...

Page 4: ...ons with frame WxHxD 720x720x656 720x720x656 Cabinet data Data and dimensions of the cabinet are shown in the following table Specification Designation Value Weight Estimated to max 45 kg Metal sheet...

Page 5: ...Controlling The table below show the components and types for controlling of the Free cooling unit Specification 48 VDC 48V DC 230V AC Control unit See separate manual ACUE CSI 3GS ACUE 3000 TKS 3000...

Page 6: ...ATURE SET MOTOR PROTECTOR SET COOLING UNITS 0 1 2 SET HIGH TEMP ALARM SET CONTROL MODE SET LOW TEMP ALARM OUTDOOR TEMPERATURE SET TEMP EL HEATER SET DIFF TEMP COOLING 1 SET DIFF TEMP COOLING 2 MODE SE...

Page 7: ...ption Flow The picture below schematically shows the air flow in a shelter In the same picture some accessories that can be connected to the controller are shown GT1 EFC2 V2 230 V RADIOBASE SHELTER GT...

Page 8: ...een Brown Blue Yellow green Brown White Indoor temp sensor RG TD5A Exhaust Air damper 230VAC LM230A 3 x 0 5 Brown Green White 2 Brown 3 White 1 Blue Junction box Brown Green White Filter Alarm Output...

Page 9: ...hite 3 5 4 Brown 1 2 Black Blue 5G 1 5 1 Black Blue Green yellow White Brown PB2 F12 Brown White Brown White SENSOR RG K81 PUSH BUTTON TIMER OPTION 2x0 5 OUTDOOR TEMP SENSOR SG K81 White Brown 3 2 Fno...

Page 10: ...valid if documented preventive maintenance has been carried out with an interval of maximum 1 year The documentation could be in form of a written log Leaving the site Before leaving the site make sur...

Page 11: ...4 Damper actuator LM230 889 331570 Damper actuator LM24 889 331562 Contact In the table below you can see how to contact the manufacturer and sales offices Office Sweden Norway Denmark Name Kontrollel...

Page 12: ...er activated if installed Check that the heater becomes warm 2 120 Air dampers to environment open if installed Check that the air damper opens 3 60 Fan signal speed up to max Check that the fan speed...

Page 13: ...ble shall be done Alarm Action Check Fire smoke alarm Activate the smoke detector Check that everything is stopped Fan Heater AC and that the dampers are closed The display shows Fire Alarm Sign the p...

Page 14: ...ime delay The test can be stopped whenever you wish by pressing the button approximately 5 seconds or until the display show any form of a two figure number The designations in the protocol refer to t...

Page 15: ...TEMP ALARM The sensor indicate very hot cut off or not connected To make the test of the sensors as reliable as possible please make no manual steps After the self test the Fire and smoke alarm if ap...

Reviews: