Via monte Nero, 40/B – 21049 TRADATE (VA) ITALY
Phone: +39 (0)331841070 Fax:+39 (0)331841950 - e-mail:
datexel@datexel.it
-
www.datexel.it
Double output
power supply unit
DAT 411
DAT 411
GENERAL DESCRIPTION
The power supply unit DAT 411 is designed to provide two not regulated isolated outputs to power the DATEXEL devices like transmitters and
low current consumption converters.
In function of the version, the device can accept three input voltage values:24, 120 or 230 Vac.
The DAT 411 is in compliance with the Directive 2004/108/EC on the Electromagnetic Compatibility.
It is housed in a plastic enclosure of 28 mm thickness suitable for DIN rail mounting in compliance with EN-50022 and EN-50035 standards
.
FEATURES
- AC line input: 24, 120 or 230 Vac @ 50-60 Hz
- Two isolated outputs
- Power supply unit for transmitters
- EMC compliant – CE mark
- In compliance with the safety standard
- Suitable for DIN rail mounting in compliance with EN 50022 and EN-50035
USER INSTRUCTIONS
The DAT 411 must be connected as follows:
The input connections must be made as shown in the section "Input connections".
The input voltage ( AC line ) must be applied between the terminals G ( IN AC) and H ( IN AC ).
The output connections must be made as shown in the sections “Output 1 & 2 connections”
The output signal Out 1 is provided between the terminals F (+Vout1) and E (GND1), The output signal Out 2 is provided between the
terminals D (+Vout2) and C (GND2).
To install the transmitter refer to section “Installation Instructions”.
TECHNICAL SPECIFICATIONS (Typical at 25 °C and in nominal conditions)
Input
Input voltage 24 Vac ± 10 % @ 50-60 Hz.
120 Vac ± 10 % @ 50-60 Hz.
230 Vac ± 10 % @ 50-60 Hz.
Outputs
Output 1 (Out 1) 20 Vdc @ 25 mA not regulated for Rload = 250 ohm
Output 2 (Out 2) 20 Vdc @ 25 mA not regulated for Rload = 250 ohm
Load resistance (Rload) see section “Load characteristic”
Environmental data
Safety EN 61010-1
Electromagnetic Compatibility (EMC)
( for industrial environments ) Immunity: EN 61000-6-2; Emission : EN 61000-6-4.
Operating Temperature -20 ÷ 60 °C
Storage Temperature -40 ÷ 85 °C
Humidity (not condensed) 0 ÷ 90%
Weight about 130 g