Delta UPS - Amplon Family

User Manual

The power behind competitiveness

GAIA Series, Single Phase

1/2/3 kVA

Summary of Contents for Amplon GAIA Series

Page 1: ...www deltapowersolutions com Delta UPS Amplon Family User Manual The power behind competitiveness GAIA Series Single Phase 1 2 3 kVA ...

Page 2: ... Any disposition duplication dissemination reproduction modification translation extraction or usage of this Manual in whole or in part is prohibited without the prior written permission of Delta Given that Delta will continuously improve and develop the product changes may be made to the information in this Manual at any time without obligation to notify any person of such revision or changes Delt...

Page 3: ...ECTING TO UTILITY POWER 18 3 6 TURNING ON THE UPS 18 3 7 COLD START WHEN UTILITY POWER IS NOT PRESENT 18 3 8 UPS SELF TEST 18 3 9 SILENCE FUNCTION 19 3 10 TURNING OFF THE UPS 19 3 11 IF CERTAIN ABNORMAL CONDITION OCCURS THE UPS WILL SEND THE FOLLOWING MESSAGES 19 3 12 DE RATING POWER 20 3 13 UPS INTERNAL FAULT 21 CHAPTER 4 COMMUNICATION INTERFACE 22 4 1 RS232 USB 23 4 2 DRY CONTACT 24 4 3 SNMP CAR...

Page 4: ...rent protection for the output AC circuit has to be provided by others All of our UPS have an electronic protection of AC output short circuit Servicing of batteries should be performed or supervised by personnel who are knowledgeable about batteries and the required precautions Keep unauthorized personnel away from batteries When replacing batteries replace with the same number of the LC R129 PAN...

Page 5: ... harmful interference in a residential installation This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions may cause harmful interference to radio communications However there is no guarantee that interference will not occur in a particular installation If this equipment does cause harmful interference to radio or tele...

Page 6: ...the limits for a Class A digital device pursuant to Part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions manual may cause harmful interference to ...

Page 7: ...into a DC voltage which is called DC BUS voltage then divides into two paths One path goes to charger which converts the DC BUS voltage into a proper DC voltage to charge the UPS battery The other path goes into DC AC half bridge inverter The other way works as a bypass path The bypass relay near the output will choose either the bypass path or inverter output In general the UPS will internally do...

Page 8: ...is so called ON BATTERY mode The auxiliary power circuit supplies the designated power to all the control circuits Because the DC AC inverter is always working the DC DC converter can work rapidly and replace the AC DC converter while the utility power fails Furthermore the bypass relay continuously keeps in the position of inverter output to supply the regulated power for the load There is no pow...

Page 9: ...With this function the investment in the capacity of circuit breakers can be reduced specially it will be highly regarded as an important feature in critical load applications Complete Protection On line double conversion design pure sine wave output and zero transfer time provide best protection With a built in surge spike and line noise protection the UPS prevents destructive hardware damage and...

Page 10: ...provides a variety of functions which meet users needs Users can instantly understand the status of the UPS via the informative LED display Audible alarms bar meters and status indicators such as battery replace indication UPS fault line condition overload etc are simple and easy for user to understand Moreover users can simply reset the circuit breaker instead of having to replace a fuse in the e...

Page 11: ... Follow Instructions Protective grounding terminal A terminal which must be connected to earth ground prior to making any other connection to the equipment This symbol indicates the word phase ON TEST This symbol indicates the principal on off switch is in the ON position OFF This symbol indicates the principal on off switch is in the STAND BY position ...

Page 12: ...10 CHAPTER 2 OPERATION 2 1 Operation Panel Figure 2 1 Operation Panel ...

Page 13: ... running in ON BATTERY mode backup mode the internal batteries will supply the power 5 Level LEDs The four LEDs indicate that the current battery capacity in ON BATTERY mode or the current load level of the UPS in ON LINE mode 6 Battery LED When this LED lights up Level LEDs will show the current battery capacity 7 Load LED When this LED lights up Level LEDs will show the load level of the UPS 8 B...

Page 14: ... 4 SNMP SLOT A SNMP adapter can be plugged in this port for managing the UPS on network Please refer to section four for more detailed information Optional 5 TVSS Transient Voltage Surge Suppressor RJ 45 RJ 11 SURGE PROTECTOR These connectors are used to prevent damages caused by surge noise and spike traveling from the telephone or network line 10 5 9 6 3 2 7 1 4 8 RS232 REPO IN OUT SURGE PROTECT...

Page 15: ...purpose 8 External Batteries Connector Used for connecting external battery Bank to extend back up time Remark UPS can support 3 packs of external battery box at most 9 USB USB connector can be plugged in this port The communication port is used to communicate PC and UPS 10 EPO RJ11 Emergency power OFF When UPS is connected to RJ11 connector It enables emergency Shutdown of UPS s inverter ...

Page 16: ... Please check if any items are missing If there is any damage or anything missing please immediately contact the dealer from whom you purchased the unit No Item Quantity 1 UPS 1 pc 2 User Manual 1 pc 3 RS232 Cable 1 pc 5 Power Cord 1 pc 6 Tower Stand 1 set 7 UPS Test Report 1 pc 8 Caution Letter 1 pc 9 Software CD UPSentry Smart 2000 1 pc 10 Series Number Label 3 pcs 11 Bracket Ear 1 set 3 1 Mount...

Page 17: ...bank 1 Before installation check the rating voltage of battery bank is suitable for the UPS 2 When UPS is running for the first time charge the UPS for at least 8 hours to ensure batteries inside are fully charged before operation 3 Utilize the battery connection cable be attached in battery bank package packed with the battery bank and UPS show as Figure 3 3 Vertical Bracket ʳ Figure 3 2 Vertical...

Page 18: ...mergently please plug in the power cord directly 9 Besides plugging in the battery power cord the battery power cord needs to be fixed with the screws 3 3 Connecting the RS 232 Dry contact Connect the interface signal cable between the RS 232 Dry contact port on the rear panel of UPS and COM1 or COM2 of computer if necessary Show as Figure 3 4 1 and 3 4 2 Refer to section four for more information...

Page 19: ...S 3 4 Connecting the load 1 Calculate power consumption of your loads to ensure that the overload condition will not happen 2 Plug the power cord of the equipment into the output receptacles on the rear panel of the UPS Caution Do not connect a laser printer to the UPS REPO INPUT INPUT BREAKER SURGE PROTECTOR OUT IN 3 1 SNMP SLOT 24V DC 40A RS232 2 LOAD 1 LO INPUT BREAKER INPUT 3 SURGE PROTECTOR O...

Page 20: ... running in ON LINE mode Shown as Figure 3 6 Note When you hear the beep sound please release the button 3 7 Cold start when utility power is not present Even when there is no utility power you can still turn on the UPS Just press the On Test button and hold for 3 seconds the UPS will start up after you hear a short beep The battery LED and on battery LED will light on and the UPS runs in ON BATTE...

Page 21: ...plug the power cord 3 11 If certain abnormal condition occurs the UPS will send the following messages ON BATTERY mode When the UPS is in ON BATTERY mode the on battery LED will light on buzzer beep half second every 2 seconds and then the UPS will start supplying power to load through batteries Shown as Figure 3 8 OVERLOAD If the load exceeds the UPS rating after a limited period the overload LED...

Page 22: ...1 SHORT CIRCUIT When the output of the UPS shorts in ON LINE mode or ON BATTERY mode the UPS will shut down without output voltage As soon as the short circuit is happened the fault LED will light on and the UPS alarm will sound continuously When remove short circuit the UPS output will recover If short circuit is happened in BYPASS mode the UPS will protect itself by tripping the input breaker an...

Page 23: ...will protect itself by thermal switches This status is so called O T P Show as Figure 3 13 When the UPS fan is failure It is show as Figure 3 14 9 When under or over voltage is happened in the UPS output This kind of fault will be detected by the microprocessor in the UPS and is so called U V P O V P Show as Figure 3 15 3 16 9 When under or over bus voltage is happened in the UPS and is so called ...

Page 24: ...onnector is defined as follows Figure 4 1 Pin Assignment Figure 4 2 Open Collector Circuit Maximum voltage and current on pin 1 8 is 30VDC 10mA ASSIGNMENT DESCRIPTION PIN RS 232 Dry Contact 1 Low battery Open collector 2 UPS TxD typical RS 232 level 3 UPS RxD typical RS 232 level Remote Shutdown 5 12V 4 Reserved for PNP 5 GND GND 6 Reserved for PNP Reserved 7 Reserved for PNP Reserved 8 Utility Fa...

Page 25: ...toring inverter status 4 Monitoring UPS status 5 Monitoring the utility power status 6 Providing the power switch function for computer to turn on off the utility power on schedule for power saving 7 Adjustable Transfer voltage HARDWARE BAUD RATE 2400 bps DATA LENGTH 8 bits STOP BIT 1 bit PARITY NONE CABLING Standard D sub 9 cable UPS side male PC side female ...

Page 26: ...5 are connected via photo coupler Cabling The users must use the special cable The connection is described as follows PC female UPS male Pin1 Pin1 battery Low Pin3 Pin5 GND Pin4 Pin3 Shutdown Pin7 Pin6 Pin7 Pin7 Pin8 Pin8 AC Fail The communication port on the rear panel of the UPS may be connected to a computer This port allows the computer to monitor the UPS and control the operation of the UPS i...

Page 27: ... Besides SNMP card supports Telnet and FTP for remote monitoring and firmware upgrading Specification Auto detecting 10 100MNetwork speed Supporting protocol TCP IP UDP HTTP ICMP ARP TELNET BOOTP DHCP FTP and SNMPv1 Remote firmware upgradeable and configurable Web server built in allow monitoring controlling UPS via browser VT100 terminal mode or Telnet to configure SNMP Function Schedule Shutdown...

Page 28: ...batteries and the required precautions Keep unauthorized personnel away from batteries 5 1 Battery Replacement See Figure 5 1 M Remove front panel N Unscrew four bolts of the battery Compartment O Unplug battery connectors P Unscrew two bolts Q Pull the battery set out and renew it R Assemble UPS by reverse procedure Figure 5 1 Battery Replacement ...

Page 29: ... personnel if above actions do not solve the problem Batteries inside the UPS are not fully charged Recharge the batteries for at least 8 hours UPS is overloaded Remove some unnecessary loads Batteries are weak Batteries weak faster when used often or operating at higher temperature If the battery is near the end of its life call for service personnel Replace the battery even if the Replace Batter...

Page 30: ...n in UPS operates on battery even though the line is in normal operating condition Very high low or distorted utility voltage Have qualified electrician check the input voltage The exhaust fans and ventilation grills may be obstructed Choose a well ventilated area to position your UPS to allow adequate dissipation of heat UPS over temperature The environment temperature exceeds 40o C 104o F Positi...

Page 31: ...operator described as below Show as Figure 6 1 Output temperature protect Fault LED light flash Output over voltage protect 50 LED light on Output under voltage protect 50 LED light flash Bus over voltage protect 25 LED light on Bus under voltage protect 25 LED light flash In case that failure is happened and utility is too low or too high the UPS output will disable and the bypass and line LED wi...

Page 32: ...Receptacle 4 IEC320 C19 1 Battery Voltage 24 V 48V 72V Battery Type Lead acid 12V 8 5Ah Back up Time Typical 3 5mins 800W 4mins 1600W 5mins 2100W Battery Recharge Time 6 Hours After Complete Discharge to Recover 80 Transfer Time Transfer Time Zero LED Status On lineΕBypassΕOn batteryΕOverloadΕBattery LowΕFaultΕBattery ReplaceΕBattery LevelΕLoad Level LED Alarm Buzzer DB9 RS232 Dry Contact SNMP Slo...

Page 33: ...ce or irresistible force i e war fire natural disaster etc and this warranty also expressly excludes all inci dental and consequential damages Maintenance service for a fee is provided for any damage out of the warranty period If any maintenance is required please directly contact the supplier or Seller WARNING The individual user should take care to determine prior to use whether the environment a...

Page 34: ......

Page 35: ......

Page 36: ......