Summary of Contents for CMC-PD01

Page 1: ...5011692604 CPD4 2014 07 02 ...

Page 2: ...erminal on CMC PD01 is correctly grounded in order to prevent electromagnetic interference FR CMC PD01 est un module OUVERT Il doit être installé que dans une enceinte protectrice boitier armoire etc saine dépourvue de poussière d humidité de vibrations et hors d atteinte des chocs électriques La protection doit éviter que les personnes non habilitées à la maintenance puissent accéder à l appareil...

Page 3: ...ceptibility Test IEC 61800 5 1 IEC 6100 4 6 Operation storage Operation 10 to 50ºC temperature 90 humidity pollution degree 2 Storage 25 to 70ºC temperature 95 humidity non condensing Shock vibration resistance International standards IEC61131 2 IEC68 2 6 TEST Fc IEC61131 2 IEC 68 2 27 TEST Ea Installation Note The contents below are about installing CMC PD01 on C2000 PROFIBUS DP Connector PIN PIN...

Page 4: ...s only able to read write the frequency word and control word of C2000 after the communication parameters are set Parameter Function Set value Explanation P00 20 Setting up source of frequency command 8 The frequency command is controlled by the communication card P00 21 Setting up source of operation command 5 The operation command is controlled by the communication card P09 30 Decoding method fo...

Page 5: ...nalog input signals 2661h R b15 b0 Percentage of ACI analog input signals AI 2662h R b15 b0 Percentage of AUI analog input signals 26A0h RW b15 b0 Percentage of AFM1 analog output signals AO 26A1h RW b15 b0 Percentage of AFM2 analog output signals Correspondence for the address 2600 Number Bit 0 Bit 1 Bit 2 Bit 3 Bit 4 Bit 5 Bit 6 Bit 7 I O on the control panel FWD REV MI1 MI2 MI3 MI4 MI5 MI6 EMC ...

Page 6: ... light on Power supply in normal status Off No power Check if the connection between CMC PD01 and C2000 is normal NET LED LED status Indication How to correct Green light on Normal status Red light on CMC PD01 is not connected to PROFIBUS DP master 1 Check if the configuration address of CMC PD01 is consistent with the actual address 2 Check if CMC PD01 is normally connected to PROFIBUS DP bus 3 C...