background image

Installation Instructions

for the

DS7433 8 Input Module

1.0

General Information

The DS7433 is an 8 input Module for use with the DS7400(Xi) Series
Control/Communicator. It connects directly to the DS7400(Xi) and is
designed to expand it to 16 hard wired points. One DS7433 may be
used per DS7400(Xi) system.

Current Draw: 65 mA Standby. 80 mA with one point in alarm.
Add 15 mA per additional point in alarm.

Maximum Loop Impedance: 60 ohms.

End Of Line Resistor: 2.21 K ohm.

12 VDC Nominal Operating Voltage.

2.0

Installation

Warning:

Failure to follow the mounting instructions in this
manual may result in damage to the DS7400(Xi)
Control Panel.

Caution:

The DS7433 and DS7400(Xi) contain static sensitive
components and must be handled with care. Follow
anti-static procedures when handling the boards.

Install the DS7433 board prior to installing the DS7400(Xi) board
into the control enclosure. If the DS7400(Xi) board is already
installed in the control panel enclosure, remove the 7400(Xi) board
this time.

Place the DS7400(Xi) board on a flat surface with the component
side of the module facing up.

Install the four plastic standoffs in the holes provided in the
DS7400(Xi) module. Avoid bending or flexing the DS7400(Xi) board
when inserting the standoffs. Be sure the standoff tabs are aligned
so that they do not touch any components on the module. Be sure
that the stand-offs are firmly pressed into the board so that the
“ears” can expand out. See drawings.

Install the DS7433 board onto the standoffs, noting that the
connector pins from the DS7400(Xi) are properly aligned to install
into the connector on the DS7433. Avoid bending or flexing the
boards while pressing them onto the standoffs.

The DS7400(Xi) control board may be installed into the control
panel enclosure at this time.

3.0 Wiring

Points 9-16 are intended for the connection of normally open or normally
closed alarm contacts. These points may also be used with compatible
2 wire smoke detectors.

4.0 Programming

Refer to your control panel Installation Guide for programming
information.

DS7433 Wiring

Installing the DS7433 on the DS7400(Xi)

Be sure that the Stand-off is pressed firmly

through the Printed Circuit Board, so that

the Stand-off ears can expand outward.

Stand-off “Ears”

Stand-off

Printed Circuit

Board (PCB)

DS7433 Front View

2-wire fire End-of-Line resistors are P/N 25899

Burglar End-of-Line resistors are P/N 25944

NO

NC

NC

NO

NO

NC NC

NO

NO

NC NC

NO

NO

NC

NC

NO

Remote Points (supervised)

9

LP+

10 11

LP+

12 13

LP+

14 15

LP+

16

2.21K

2.21K

2.21K

2.21K

2.21K

2.21K

2.21K

2.21K

9

LP+

10 11

LP+

12 13

LP+

14 15

LP+

16

DS7433

1

2

3

4

5

6

7

8

A

C

A

+

9

10

11

12

13 14

15

16

17

18

19

20

21

22

23 24

25

26 27

28

29

30

R

B

G

Y

B

G

R

S

PO1 PO2 1– LP+ 2– 3–

5–

6–

7–

8–

4–

LP+

LP+

LP+

O

P

T

I

O

N

R
B
G
Y

A/CPower Indication LED

Expansion Port

Stand-Offs (4)

DS7400(Xi)

Install DS7433 Here

Reviews: