background image

Installation and Operating Manual

for DALI Gateways 

 

DCI 4 DALI

Instructions No. 3931312

|

 Last revised: 06/2014

Doepke

DE EN

Summary of Contents for DCI 4 DALI

Page 1: ...Installation and Operating Manual for DALI Gateways DCI 4 DALI Instructions No 3931312 Last revised 06 2014 Doepke DE EN...

Page 2: ...5 6 Organising lighting groups 20 5 7 Organising lighting scenes 27 5 8 Directly assigning control addresses and or inputs 32 5 9 Directly assigning feedback addresses and or outputs 33 5 10 Configur...

Page 3: ...ned application area Individual lighting groups can be dimmed between adjustable minimum and maximum values with configurable dimming speeds that can be separately set for each individual lighting gro...

Page 4: ...accident prevention regula tions must be observed The unit must not be opened or operated other than in accordance with its technical specifications Disconnect the unit from the power supply before w...

Page 5: ...nsulation where DALI circuits and power lines are laid together External DALI voltage sources must not be connected Only connect DALI devices to the DALI interface The USB port is intended solely for...

Page 6: ...es not exceed 0 6 Nm 3 1 Network topology There is no need to take into account any specific network topologies The only requirement is to avoid ring networks It is possible to combine star or tree to...

Page 7: ...EVG 1 EVG 20 EVG 4 EVG 8 EVG 2 EVG 16 EVG 6 EVG 14 EVG 19 EVG 9 EVG 17 EVG 11 EVG 12 EVG 13 EVG 18 DCI 4 DALI EVG 15 EVG 10 EVG 7 EVG 5 EVG 21 EVG 3 max cable length 300 m 4 Indicators and controls T...

Page 8: ...menu items by pressing or 4 1 Display during normal operation The gateway displays several messages for information only during normal operation Message Description Ready for use Gateway is configure...

Page 9: ...e it therefore does not respond to switch commands via the inputs or the Dupline bus Flashing 1 s An error was detected Possible error sources are described in the following section 4 3 Display of sys...

Page 10: ...he Search for new device command in the Device setup menu DALI error short circuit The DALI bus s overcurrent monitoring has responded usually due to a short circuit The gateway attempts to restart th...

Page 11: ...e DALI sys tem the DALI gateway must be configured This procedure is described in detail in the following sections The following paragraph only provides a brief description of commissioning 5 2 1 Requ...

Page 12: ...re factory defaults but the following values can be adjusted separately for each group 1 Minimum brightness down to which lighting should be dimmed see Section 5 6 3 Configuring lighting groups on pag...

Page 13: ...create light scenes select address select address scan all devices con gure light groups operate light group operate light scene un lock light scenes voltage recovery language device diagnostics dele...

Page 14: ...e electronic ballasts off 0 These values are set together with the fading speed Note the parameters for minimum and maximum brightness and for dim ming and fade speeds are preconfigured by the manufac...

Page 15: ...ss of the lamp depends on the particular elec tronic ballast that is used An identical illuminance can only be achieved by using the same types of equipment ballast and lamp The group is smoothly adju...

Page 16: ...u pressing calls up the lighting scene that consists of previ ously defined groups Pressing saves the current brightness values of the associated groups as a lighting scene in memory location 07 in th...

Page 17: ...the end of the teach in process data is transferred to the devices Note data transfer please wait It is then possible to assign the groups to light ing scenes Select the following menu item in order...

Page 18: ...ge or removed devices from the DALI bus The gateway rebuilds the device list without altering any group or scene affiliations for devices that have not changed To do this in the following display pres...

Page 19: ...essage Teach in device i e it is set to the factory defaults or you want to build an entirely new configuration When this function is selected the gateway deletes the list of all known control gear an...

Page 20: ...ostic information during operation in the system settings under Dev diagnostics 5 6 Organising lighting groups The gateway supports the use of up to 16 lighting groups as provided for in the DALI spec...

Page 21: ...ting configuring or working on lighting groups This menu item lets you create or work on lighting groups L i g h t g r o u p s C r e a t e Pressing key or brings up the menu for creating a lighting gr...

Page 22: ...ady being used for a different group or scene If you nevertheless opt to enter this data the gateway deletes the previous assignment Assigning a feedback address The next step allows you to assign the...

Page 23: ...r by pressing key you can add the currently selected device to the group key or if it already exists remove it key In every case you are taken back to the above menu item via which you can terminate t...

Page 24: ...ause the sensitivity of the human eye is also logarithmic The minimum values depend however on the control gear LEDs for example can be dimmed down to a value of 1 but this value can be as high as 128...

Page 25: ...second Dimming levels 1 357 8 6 63 3 11 11 2 2 253 0 7 44 7 12 7 9 3 178 9 8 31 6 13 5 6 4 126 5 9 22 4 14 3 9 5 89 5 10 15 8 15 2 8 The higher this number is between 1 and 15 the more slowly the devi...

Page 26: ...in the subsequent dialogue G r 0 2 F a d e t i m e E s c 0 5 O K Pressing and configures the fade time factory default is 5 After confirming by pressing this value is adopted and the next menu appears...

Page 27: ...selected A lighting scene must comprise at least one lighting group Lighting scenes can then be linked to the Dupline addresses Note you must also include groups that are to be switched off in a light...

Page 28: ...ng scene 16 1 1 x E s c Explanation of symbols used Scene has not been defined x Scene has been defined but no control address has been assigned cannot be used 1 Scene has been defined and a control a...

Page 29: ...een used in a different function The displayed address is currently assigned to the scene Pressing key or selects the Dupline address to be assigned to the lighting scene Pressing confirms this addres...

Page 30: ...ght setting for the group in the following menu G r 0 2 a c t 1 2 8 d i m O K Key assignment dim Increases or reduces the brightness of the group Reduces the brightness of the group incrementally Incr...

Page 31: ...quits the menu without saving the previously set status and pressing accepts the displayed status When a lighting scene is disabled exter nal keys cannot be used to save any lighting scenes 5 7 4 Del...

Page 32: ...nge is to be made Only those groups and or scenes that have already been allocated are shown An exclamation mark denotes that an address has already been assigned to this group Pressing selects the it...

Page 33: ...those groups that have already been allocated are shown An exclamation mark denotes that an address has already been assigned to this group Pressing selects the item and takes you to the menu in which...

Page 34: ...following menu item by pressing key or S e t u p P r i o r i t y 5 10 1 Response in the event of a DALI bus fault Every DALI control gear device makes it possible to specify and save a brightness valu...

Page 35: ...rn Do not change parameter can also be selected You can specify this value in the follow ing menu item D u p I i n e f a u l t 5 0 Pressing key or then selects the brightness Pressing key or takes you...

Page 36: ...or it is indicated on the display Restart Start 5 s Restart the unit if the key is held down the unit counts down and restarts at 0 s Factory default Start 5 s Reset to factory default if the key is h...

Page 37: ...e is opened without authorisation 7 Technical data DCI 4 DALI minimum typical maximum DALI Output voltage SELV1 short circuit proof 11 5V DC 16 5V DC 17V DC Nominal current 128 mA Short circuit discon...

Page 38: ...perating voltage SELV 21 5V DC 24V DC 26 5V DC Current consumption3 24 mA 26 mA 31 mA Permissible ripple voltage 100 mVpp Terminals Type Screw terminal with strain relief clamp Clamping area 0 4 mm 2...

Page 39: ...s standards IP20 EN 60669 2 1 EN 50428 EN 50491 3 4 1 5 1 5 2 EN 60929 EN 62386 101 103 Order number 09501243 1 Only applies if entire installation is carried out in accordance with requirements for S...

Page 40: ...1 Dimming level setup 10 20 30 40 50 60 70 80 90 100 1 10 20 30 40 50 60 70 80 90 100110120130140150160170180190200210220230240250260 in Helligkeit light intensity Dimmwerteinstellung dimming level va...

Page 41: ...LS1 LS2 kurz lang lang 1 Dimmgeschwindigkeit dimming speed 2 berblendgeschwindigkeit fading speed Zeit time LS Lichtszene light scene long short long dimmen max dimming max dimmen min dimming min Memo...

Page 42: ...iring diagram 24 V DC 0 V DC 1 8 DC 2 3 2 7 4 3 4 7 DCI 4 DALI zentral ein zentral aus central off central on DA DA DA DA USB Dupline D D D D central ON OFF Dupline 1 3 1 7 1 4 DC 0 V 24 V DALI 42 Doe...

Page 43: ...10 Dimensions 58 43 23 6 85 72 45 DE EN 43...

Page 44: ...Model no 3931312 Last revised 06 2014 Technical specifications subject to change Doepke Schaltger te GmbH Stellmacherstra e 11 D 26506 Norden...