Your Advantage

•  Preventive fire and system protection

•  Increasing the availability of plants by early fault detection

•  Universal usage at AC/DC mains

•  Protection against manipulation by sealable transparent cover 

  over setting switches

Features

•  According to IEC/EN 62020, VDE 0663

•  For AC and DC systems Type B

•  To detect earth faults in grounded voltage systems

•  4 setting ranges from 10 mA to 3 A

•  Manual reset, with alarm and pre-warning

•  With adjustable switching delay

•  Energized or de-energized on trip

•  LED indicator for operation, pre-alarm and alarm

•  With test function

•  LED-chain indicates fault current

•  As option with analogue output

•  Broken wire detection

•  Width: 52.5 mm

The residual current monitor type B is designed to monitor DC systems 
and AC systems up to 250 Hz.

green LED „ON“: 

On, when auxiliary supply connected

yellow LED „Pre-Alarm“: Flashes during time delay t

v

   

 

On, when pre-alarm active

red LED „Alarm“: 

Flashes during time delay t

v

  

 

On, when alarm active

yellow and red LED: 

Flashes on broken wire or extremely high input   

  

 

signal

yellow LED-chain: 

LED chain indicates fault current in % of adjusted  

   

 

alarm value

1)

 RN 5883 Variant /61;   

2)

 ND 5015

The devices measure AC and DC current (AC / DC sensitive. Due to the 
measurement principle they also detect magnetic fields in the next to the 
current transformer.
When planning a panel with AC/DC sensitive residual current monitors 
please make sure that no components are placed next to the CT that 
create a magnetic field, e.g. contactors, transformers etc.
If an influence is detected, also a rotation of the CT by 90° could positively 
reduce the influence.

The AC/DC sensitive residual current monitor RN 5883 allows an early 
detection of insulation faults and detects differential currents with AC 
as well as DC components in grounded voltage systems (type B). The 
measurement takes place via an external current transformer. 

Contrary to an RCD the residual current monitor RN 5883 does not dis-
connect the mains when detecting a fault but only indicates it. Besides 
the easy to read LED chain indicating the actual current several LEDs 
display operation, pre-alarm and alarm. The 4 measuring ranges cover 
10 to 3 A. Additional features are broken wire detection, test function and 
adjustable pre-alarm.
The residual current monitor RN 5883 provides early information for precise 
and cost effective maintenance before the plant stops.

RN 5883

M11213

11

14

A1

k1

k2

12

21

22

24

U+ U-

A2

i1

i2

X1 X2

A1

X1

i1

i2

k1

k2

A2

X2

11

21

12

22

14

24

Alarm

Pre - Alarm

IF

0...10V

U+

U-

Installations- / Monitoring Technique

VARIMETER RCM

Residual Current Monitor, Type B for AC and DC Systems
RN 5883

Approvals and Markings

Product Description

Circuit Diagram

Application

Indication

Notes

Connection Terminals

Terminal designation

Signal description

A1, A2

Auxiliary voltage U

H

i1, k1, i2, k2

Connection of an external 
residual current transformer

X1, X2

Parameterization input
energized or de-energized on trip

11, 12, 14

Contacts alarm signal

21, 22, 24

Contacts pre-alarm signal

U-, U+

Analogue output (option)

ND 5015/035

ND 5015/070

Canada / USA

1)

A025518

Canada / USA

2)

All Technical Data in this list relate to the state at the moment of edition. We reserve the rigth for 
technical improvements and changes at any time.

Summary of Contents for VARIMETER RCM

Page 1: ...c If an influence is detected also a rotation of the CT by 90 could positively reduce the influence The AC DC sensitive residual current monitor RN 5883 allows an early detection of insulation faults...

Page 2: ...nge between energized and de energized on trip A change of the function will only be valid after interrup tion of the supply voltage Terminal X1 X2 external link De energized on trip open Energized on...

Page 3: ...kV 2 EMC Surge voltages Class 3 5 kV 0 5 J DIN VDE 0435 303 Electrostatic discharge 8 kV air IEC EN 61000 4 2 HF irradiation 80 MHz 2 7 GHz 20 V m class 3 IEC EN 61000 4 3 HF wire guided 10 V class 3...

Page 4: ...larm Energized or de energized on trip Without analogue output Auxiliary voltage UH AC DC 80 230 V Width 52 5 mm ND 5015 035 61 Article number 0066841 Residual current transformer for RN 5883 Diameter...

Page 5: ...ting clips ET5018 art no 0058754 set with 2 pcs for DIN rail mounting or screw mounting ND 5015 070 D L H H1 B C F k E G Dimensions mm 70 111 110 115 32 37 55 4 2 50 74 Weight g approx 220 Drill toler...

Page 6: ...onitor ND 5018 105 for DIN rail mounting Disassembling Residual Current Monitor ND 5015 024 and 035 M11123 Disassembling Residual Current Monitor ND 5015 070 D B L H M9777_b G ND 5018 105 D L B H G Di...

Page 7: ...PE PE PE N N L1 L L1 L1 L2 L L2 L2 L3 L3 L3 M8362_a PE L1 L2 L3 N i1 i2 k1 k2 X1 X2 11 12 14 21 22 24 A1 A2 RN5883 i1 i2 k1 k2 X1 X2 open operating current X1 X2 bridged de energized alarm indicator...

Page 8: ...8 04 03 20 en 201A E DOLD S HNE KG D 78114 Furtwangen e mail dold relays dold com internet http www dold com POBox1251 Telephone 49 7723 654 0 Telefax 49 77 23 654 356...

Reviews: