domat UC300 

01/2019 Subject to technical changes. 

 

 

 

UC300 

Communicative floor heating 
controller 

 

 

 

 

 

Summary 
 
 

UC300  is  a  communicative  floor  heating  controller  with  one  PWM  output  for 
control of a thermic actuator, or electric floor heater. It can work autonomously, 
or  in  connection  to  a  primary  controller  (MiniPLC  or  SoftPLC),  building 
management  system  (RcWare  Vision  or  any  SCADA),  or  to  UCWEB 

  the  web 

interface. 
 
UC300 

 basic version with display and knob 

UC300/DK 

 version without knob and display 

 

Applications 
 
 

 

Systems with water or electrical floor heating 

 control and measuring of 

room temperature 

 

monitoring and communication of room temperatures 
 

Function 
 
 
 
 

The  controller  reads  actual  room  temperature,  floor  temperature  with  an  external 
Pt1000 sensor, setpoint shift by a knob, and set operation status which is set by short 
push  of  the  knob.  Measured  and  set  values  are  processed  in  a  PI  algorithm,  at  the 
output of which there is a PWM controlled triac. All values are displayed on a large LCD 
display. 
 
The floor sensor located in the floor body or at supply water limits the temperature of 
the floor and prevents overheating. Maximum floor or water temperature (measured 
by the floor sensor) is set in the configuration program or in the controller menu. In 
case the sensor is not connected (missing or broken), the limitation is not active and 
the controller uses room setpoint and actual value only. 
 
The output works either as PWM controlled by a PI controller, or on/off (thermostat). 
The functionality and control parameters, i.e. P and I constants, and hysteresis, can be 
set  with 

ModComTool

,  the  configuration  software,  which  is  free  to  download  at 

http://domat-int.com/en/downloads/software

. 

 
The controller contains real time clock with a weekly scheduler (6 events per day). It 
changes between three operation modes: Day, Night, and Off. A short push in the Night 
mode switches to Party mode 

 Comfort extension by 2 hours. 

 

Summary of Contents for UC300

Page 1: ...set values are processed in a PI algorithm at the output of which there is a PWM controlled triac All values are displayed on a large LCD display The floor sensor located in the floor body or at supply water limits the temperature of the floor and prevents overheating Maximum floor or water temperature measured by the floor sensor is set in the configuration program or in the controller menu In ca...

Page 2: ...ent 0 4A recommended thermic actuators are Siemens STA71 Danfoss TWA 24V types etc Inputs 1x digital input for presence or window contact 1x analogue input for external temperature sensor Pt1000 Setpoint correction according to configuration 10 to 1 K Communication 2 wire RS485 Modbus RTU slave optically separated 1200 115 200 bps Display LCD 60 x 60 mm Terminals screw terminals for 0 14 1 5 mm2 w...

Page 3: ...ure correct values of temperature i e in the height of about 150 cm with no direct sunlight or other heat cool source AHU outlets refridgerator electrical appliances The device consists of two parts bottom with screw terminal block and cover containing PCB display and the knob The bottom part is fixed by 2 or 4 screws to any flat surface or a flush mounting box Ø 50 mm At the back of the bottom th...

Page 4: ...t list There may be up to 6 events per day Time schedule settings Switch to the time schedule settings mode with a long push 1 s The controller switches to settings mode clock icon Turn the knob to select the weekday 1 to 7 Then short push to confirm the selection Turn the knob to select the event large number 1 to 6 Each event displays the mode activated by this event Short push to confirm the ev...

Page 5: ...mode Temperature Cooling Night are flashing Setpoint temp Cooling Off mode Temperature Cooling Empty house are flashing Select the requested value by a short push Turn knob to change value Confirm by a short push again If there is no user activity for 30 s the controller goes to the basic display mode Default values Default values as well as all other settings PI parameters address baud rate can b...

Page 6: ...are twisted such as with the LAM DATAPAR or Belden 8205 cable A terminal is designed for maximum 3 wires of 0 8 mm2 With cable types as above maximum starting power of the controller and valve of ca 7 VA and acceptable voltage drop of max 15 the maximum cable length for 10 controllers is about 50 m If the controllers and valves are at higher distance than 50 m from the transformer or more valves a...

Page 7: ...ompliance with local regulations Safety note The device is designed for monitoring and control of heating ventilation and air conditioning systems It must not be used for protection of persons against health risks or death as a safety element or in applications where its failure could lead to physical or property damage or environmental damage All risks related to device operation must be consider...

Page 8: ...r downloading software and related products 09 2016 Changed the format and reference to the configuration software 03 2017 Added picture and description of the installation and link on the datasheet with other colours 10 2017 Added Safety note description UC300 DK version change pictures 05 2018 Technical data change 01 2019 Technical data change ...

Reviews: