background image

FX32EV - 00 :

FX32EV - R4 :

 

FX32EV - R2 :

 

FX32EV - A1 :

1 2

4

3

5 6

8

7

9 10 11

AC100 - 240 V ~

pressure

50/60Hz

FX32EV

OP

TIO

N

MO

DU

LE

RS-485 COMM.

OPTION MODULE

1
2
3
4

TRX
TRX
SG

1
2
3
4

RXD
TXD
GND

1
2
3
4

4~20mA
4~20mA
SG

RS-232 COMM.

OPTION MODULE

4~20mA Output

OPTION MODULE

FX32EV

%

1

0

100

50

 

 

 

 

bar

1

-1

99

bar

1

-1

99

-1

bar

0.1

-9.9

9.9

0.0

‘C

0.1

-19.9

19.9

0.0

sec

0.1

O F F

9.9

O F F

9

48

 : 4800BPS, 

96

 : 9600BPS,  

I92

 : 19200BPS, 

384

 : 38400BPS

96

M O T

B D R

L O C

R T Y

2 2

: R22

I 3 4

: R134A

4 0 4

4 I 0

: R410A

7 I 7

: R717

: R404A

2 3

: R23

4 0 7

: R407C

0:Rotation, 1:Superheat, 2:Temperature, 3:Suction pressure

0:Always operation, 1:Remote operation, 2:Communication operation

0:Pressure transmission output, 1:Control output (for 4~20mA type valve control)

S H
S L
P O F
T O F

REV. 2010. 5. 3

FX32EV

Ev

reset

SH

 T
 P

Ev
SH
T

1

2

300

301

302

303

304

307

308

319

temp

start

EVout

Alarm

mv

bar

bar

rst

rst

mv

EV

2 2

B I R

ID1 Pt1k COM 4~20mA +V

28

35

70

78

8

FX32EV

Ev
SH

T
P

reset

mv

Connection Diagram

Dimensions and Panel Cut-Out Form

Constitution

Operation Button

Order Information

Basic model
RS-485 communication function model (MODBUS RTU MODE) 
(※ communication cable is included) 
RS-232 communication function model (MODBUS RTU MODE) 
(※ communication cable is included) 
Pressure transmission output function model or 
For 4~20mA type electronic expansion valve

Lighting when expansion valve is on

The degree of superheat

Temperature

P

Pressure

℃ : Temperature, bar : Pressure

Lighting when trip, flickering when alarm

Program setup
Push twice successively and 
quickly when clearing alarm
of manual return type 

Execution of options or 
input of setup value

Move between menus & 
Increase of setup value 
Confirmation of valve control 
output (during pushing button)

Menu movement or 
decrease of setup value

Basic Specification

Power

AC100 - 240V ~ , 50/60Hz (MAX 4VA)

Control Mode

Electronic expansion valve control unit using PID control algorithm

SSR output 1 point (expansion valve on/off), Relay output 1 point (alarm port)
Pt1000Ω temp. sensor 1 point, 4~20mA 
pressure sensor input 1 point (built-in sensor loop power)

Temp. -10~50℃ (when no dew condensation)

Temp. -20~60℃, Humidity Under 90%RH

Temp. sensor (DPR-PT1K-P6D50L,-100~100’C) 
Pressure sensor (-1~9bar or 0~30bar)

Indication is possible in 0.1℃ unit between -19.9 and 99.9. 
outside of that range, in 1℃

screw bolt terminal block (1.5mm  wire available)

2

PreCaution for Use

Accessory

Sensor type : Pt1000Ω
Measurement range : -100 ~ 100℃
Accuracy : ±0.3℃
Probe : Dia.6, 50mm,SUS304
Protection level : IP67
Cable : 2C X 0.5mm, Stainless mesh shield teflon cable

Suction Pressure Sensor : DP506

Pressure measure range : -1~9bar, 0~30bar, 0~16bar
Operating temperature : -40 ~ 125℃
Accuracy : ±0.5% FS
Protection level : IP67
Signal output : 4~20mA (2 Wire)

Indicator Lamp

Option

Set-up of the degree of superheat

Outline

Error Messages

How to change setting 1 group and 2 group

* Minimum Valve ON Time : It makes compulsorily valve ON during setup time if it needs control for period which is shorter than setup time when controlling valve ON/OFF. 
  This function do not work when setup is OFF.
* Expansion Valve Control Cycle : Setup control cycle of ON/OFF type expansion valve. Setup 6 sec. for AKV series of Danfoss.
* Output when Sensor Error : Setup output ratio of expansion valve to output compulsorily when temperature or pressure sensor error occurs.
* Expansion Valve Control Slope : Input control various value of expansion valve to increase or decrease per second. It is used when rapid control is needed.
* Display Mode : Display in order Superheat --> Temperature --> suction pressure when rotation mode.

Setting 1 Group Table

Setting 2 Group Table

UNIT

STEP

MIN.

MAX.

DEFAULT

USER SETUP

DESCRIPTION

CODE

NO.

Bias

002

003

004

005

006

007

008

009

013

014

015

016

019

 

‘C

0.1

0.5

99.9

5.0

D F R

Proportional Band

 

SEC

1

0

999

30

I R T

Integral Time

 

SEC

1

0

999

0

D R T

Derivative Time

 

K

0.1

-9.9

99.9

0.0

L S H

Low Superheat Alarm

 

K

0.1

-9.9

99.9

19.0

H S H

High Superheat Alarm

 

bar

0.1

-1.0

99.9

0.5

L O P

Pressure Lower Limit Alarm (LOP)

 

bar

0.1

-1.0

99.9

8.0

H O P

Pressure Upper Limit Alarm (MOP)

 

%

1

0

100

100

H I 0

Expansion Valve Control Upper Limit

 

%

1

0

0

0

L O 0

Expansion Valve Control Lower Limit

 

K

0.1

0

5.0

0.1

D B N

No Response Control Range

 

SEC

1

0

300

5

R D T

Operation Delay Time

 

%

1

0

100

oFF

M A 0

Expansion Valve Compulsory Control

Lock Selection

Refrigerant

Upper Limit Input Range of Pressure Sensor 

Lower Limit Input Range of Pressure Sensor 

Pressure Sensor Compensation

Temperature Sensor Compensation

Minimum Valve ON Time

sec

1

O F F

60

6

P R T

309

Expansion Valve Control Cycle

%

1

0

100

0

S F O

310

Output when Sensor Error

%

1

O F F

100

5

0

1

0

J E K

311

Expansion Valve Control Slope

D

 

I S

312

Display Mode

R M T

313

Remote Operation Function

A O M

315

Analogue Output Function (-A1 model)

  1 ~ 32

1

I D

318

Communication ID (-R4 model)

Communication Speed (-R4 model)

:

:

 

Setting 1 group Lock
Setting 1,2 group and superheat setup Lock

:

Setting 1, 2 group Lock

Lock clear

Model

Input/
Output

Operation

Storage

Sensor

Display

Connection
Terminal

Initialization of Setup Values

If pushing for 10 sec. at the same time, setup values are initialized

* Bias : Initial control output value of expansion valve (expansion valve open ratio at point which setting superheat value is equal to current superheat value).
* Proportional Band : Initial control range value of expansion valve (when setting superheat is 6.0K and proportional band is 5.0K, it can be controlled within range of 
  3.5K(0%) ~ 8.5K(100%)) - Please increase proportional band if width of vibration of superheat value is large.
* Integral Time : It controls open ratio of expansion valve by accumulating error each integral time - increase integral time if cycle of vibration of superheat value is short.
* Derivative Time : It is used in circumstance where It needs instant response. Generally setting value is '0'.
* Low Superheat Alarm : Input low superheat alarm value. It closes valve until become control lower limit value of expansion valve if superheat is lower than low superheat alarm value.
* High Superheat Alarm : Input high superheat alarm value. It opens valve until become control upper limit value of expansion valve if superheat is higher than high superheat alarm value.
* Pressure Lower Limit Alarm : It opens expansion valve to 100% if suction pressure is lower than pressure lower limit alarm.
* Pressure Higher Limit Alarm : It closes expansion valve to 0% if suction pressure is higher than pressure upper limit alarm.
* Expansion Valve Control Upper Limit : Setup maximum open ratio of expansion valve (but, It opens valve to 100% regardless of upper limit value if pressure lower limit alarm occurs.)
* Expansion Valve Control Lower Limit : Setup minimum open ratio of expansion valve (but, It closes valve to 0% regardless of lower limit value if pressure upper limit alarm occurs.)
* No Response Control Range : Keep open ratio of expansion valve if superheat is controlled within setting sup/- (no response control range).
* Operation Delay Time : Start to control after setup delay time if there is operation start input.
* Expansion Valve Manual Control : It is used when user compulsorily controls expansion valve at open ratio which is set by user. compulsory control function is not used if setup is OFF.

Operation 
Mode

Set-up by using ▲ ▼ button

● If push SEL button for 3 sec. then setup is completed and returns 
    to operation mode.

● If there is no input for 180 sec. during setup, it returns to operation mode.

First setting parameter

Last setting parameter

Push for 3 sec. in case of setting 1 group
Push for 5 sec. in case of setting 2 group

Operation 
Mode

Set-up by using ▲ ▼ button

Push for 3 seconds.

FX32EV is especially designed for control and management of electronic expansion valve 
at refrigeration unit. It is a electronic expansion valve controller to control the degree of 
superheat by using PID control and through measuring pressure and temperature.

This unit is composed of EX32EV main board, temperature sensor and pressure sensor 
for gauging suction pressure.

- FX32E supports ON/OFF electronic expansion valve (AKV-danfoss).

- R22, R134a, R404a, R407c, R410a, R717, R23 
  (Currently supported refrigerant August 2009)
- R507c, R290, R600, R600a, R744, R728 (Planned)

FX32EV can control superheat of various refrigerant.

- PID superheat control through protection and safety compensation function.
- Electronic expansion valve control unit which is controlled by 4~20mA signal

Control method of electronic expansion valve

FX32EV is a control unit for ON/OFF type electronic expansion valve.
(It doesn't support step motor type expansion valve.)

- It can control in 0.1% unit from 0.0 to 100.0% through PWM (open ratio control) 
  control method
- Control cycle can be set from 1 sec. to 60 sec. (control in 10msec. unit) 

D

O

T

E

C

H

A

3

0

F

1

0

0

.1

0

0

6

12

18

t(sec)

50%

25%

75%

On

Off

Control cycle : 6 seconds

Pressure sensor and Temperature sensor

FX32EV has adopted pressure sensor and temperature sensor which are especially designed for refrigerant gas to secure accuracy and safety.

- Pressure sensor : -1 ~ 9 bar (4~20mA) or 0 ~ 30 bar (4~20mA) It can be selected
- Temperature sensor : -100 ~ 100’C, Pt1000Ω

Electronic expansion valve control regulated by 4~20mA signal

FX32EV-A1 model can transmit pressure value measured by 4~20mA method and can be used for electronic expansion valve which is controlled by 4~20mA signal.

Built-in RS485 communication function 

FX32EV-R4 with RS485 can interface with another device and supports MODBUS RTU/ASCII type protocol.

Compulsory parameter for operation

Second degree parameter for optimum operation

※ Panel Cut-Out Form : 71 X 29 mm

POP

Pressure sensor is disconnected.
Check pressure sensor.

PST

Pressure sensor is short-circuited.
Check pressure sensor.

TOP

Temperature sensor is disconnected.
Check temperature sensor.

TST

Temperature sensor is short-circuited.
Check temperature sensor.

Operation State Messages

MOP

Maximum operation pressure is detected.

LOP

Minimum operation pressure is detected.

HSH

Upper limit the degree of superheat is detected.

LSH

Lower limit the degree of superheat is detected.

Electronic expansion valve control unit 

FX32EV

1. This product may cause an electric shock in handling. Please do not attempt to open it with power 
   turned on.
2. This product should be installed in a place fixed secured by a rack or panel.
3. This product can be used under the following environmental condition
   ① Indoor ②Pollution Degree 2 ③At an altitude of 2000m or below ④Installation CategoryⅡ
4. To turn on or turn off power supply for this product, please the circuit breaker or switch of a standard 
   product of IEC 60947-1 or IEC 60947-3 product and install it within a close distance allowing 
   convenient operation by user.
5. Please be understood that if this product is dismantled or modified discretionary, after sales service
   will not be able to be provided.
6. An output wire to be used for this product should be inflammable grade FV1 (V-1 grade or above),
   the thickness of the wire should be AWG No. 20 or above. (0.50㎟)
7. In order to prevent it from an inductive noise, please maintain the high-voltage wire and power wire
   separated.
8. Please avoid installing the product in a place where a strong magnetism, noise, severe vibration 
   and impact exist.
9. When extending the sensor wire, use a shield wire and do not extend it unnecessary long.
10. The sensor wire and signal wire should be away from the power and load wires using conduits 
     separately installed.
11. Please avoid using the product near a device generating strong high frequency noise (high-frequency
     welding machine, high-frequency sewing machine, high-frequency radiotelegraph, high capacity SCR
     controller)
12. PRODUCT’S DAMAGES OTHER THAN THOSE DECRIBED IN THE GUARANTEE CONDITIONS PROVIDED 
     BY THE MANUFACTURER SHALL NOT BE RESPOINSIBLE BY US.

Please use this product after attaching double or more safety device without fail if you use this product for 
control of equipment which have a big effect on human life or on property (e.g.:nuclear control, medical 
instrument, vehicle, railroad, aviation, combustion apparatus, amusement equipment, safety device, etc.)

Temperature Sensor : DPR-PT1K-P6D50L*3m

(unit : mm)

UNIT

STEP

MIN.

MAX.

DEFAULT

USER SETUP

DESCRIPTION

CODE

NO.

DOTECH,INC  l  http://www.dotech21.com
                     business@dotech21.com

6F, JOONGANG-ILBO 778 Wonsi-Dong, Danwon-Gu, Ansan-Si,
Gyeonggi-Do, Korea TEL : +82-31-495-3767 / FAX : +82-31-495-3917

Reviews: