background image

Control Panel Compatibility

FSB-210 smoke detectors are addressable system detec-
tors that are only for use with DSC fire and security con-
trol panels equipped with the compatible interface. The
FSB-210 smoke detectors cannot be used with a standard
2-wire smoke detector interface. Any standard 2-wire
smoke detector, including the DSC FSA Series, will not
operate on an addressable circuit. The FSB-210 series and
the FSA Series are not compatible, interchangeable or
substitutable.
The addressable interfaces have a proprietary power and
signaling system. Voltage ratings are not indicative of
compatibility. The current rating is provided for circuit
loading calculations only. Please refer to the control panel
information for details on the installation of addressable
circuits.
FSB-210 detectors are compatible with the following con-
trol units:
• PC5010/PC5015/PC5020/PC5020CF v2.x with PC5100

interface module. Maximum 32 detectors can be
installed.

• PC4010/PC4010CF/PC4020/PC4020CF v3.x. Maximum

112 detectors can be installed.

Operation

Approximately every 7 to 8 seconds the unit tests for a
smoke or heat alarm condition. During this sequence the
unit also performs self diagnostics, and checks for faults.
During normal operation the LED will flash every 50 seconds.

Smoke Alarm

The smoke detector has a nominal fixed alarm sensitivity
(refer to the 

Specifications

 section on the back page) and

it will go into alarm when the signal level exceeds the

'alarm' threshold and send the alarm signal to the control
panel. During an alarm the LED will flash every second. 

Smoke - Drift Compensation

The detector automatically compensates for long-term
environmentally induced changes to maintain a constant
smoke sensitivity. When the drift compensation has
reached its high or low limit of adjustment, the detector
will go into the trouble state.

Heat Alarm

The heat detector will go into alarm when the heat signal
level exceeds the heat alarm threshold (135ºF/57ºC); and
send the alarm signal to the control panel. During an
alarm the LED will flash every second.

Alarm Indications

Installer Instructions

1. Smoke Detector Placement

On smooth ceilings, detectors
may be spaced 9.1m (30ft)
apart as a guide. Other spac-
ing may be required depend-
ing on ceiling height, air
movement, the presence of
joists, uninsulated ceilings,
etc. Consult National Fire
Alarm Code NFPA 72, Chap-
ter 11 or other appropriate
national standards for instal-
lation recommendations. 

• Do 

NOT

 locate smoke detectors at the top of peaked or

gabled ceilings; the dead air space in these locations may
prevent the unit from detecting smoke. Avoid areas with
turbulent air flow, (near doors, fans or windows). Rapid
air movement around the detector may prevent smoke
from entering the unit. 

• Do 

NOT

 locate detectors in areas of high humidity.

• Do 

NOT

 locate detectors in areas where the temperature

rises above 38ºC (100ºF) or falls below 5ºC (41ºF).

FSB-210 Series Smoke Detector

Installation and Operating Instructions

Read this instruction sheet thoroughly before installation and use of the FSB-210 Series Smoke Detector

This Installation Sheet must be used in conjunction with the appropriate Alarm Controller Installation Manual.

PA

IN

T

Alignment Marks

LED

Place magnet here

DO

DO

NO

T

Condition

LED

Normal/Sensitivity in Production Range

Flash 1/50s

Alarm Smoke/Heat

Flash 1/1s

Low Power Trouble

OFF

Other Fault/Trouble

OFF

Smoke Test - Failed

OFF

Summary of Contents for FSB-210 Series

Page 1: ...ctor automatically compensates for long term environmentally induced changes to maintain a constant smoke sensitivity When the drift compensation has reached its high or low limit of adjustment the detector will go into the trouble state Heat Alarm The heat detector will go into alarm when the heat signal level exceeds the heat alarm threshold 135ºF 57ºC and send the alarm signal to the control pa...

Page 2: ...tion of any other type of device will impair operation Devices other than addressable series devices which require power to operate must be powered separately Do NOT use looped wire under terminals for system supervision Break the wire run to provide supervision of connections 4 Mounting Detector Installation Position the detector on to the base plate using the detector and base plate alignment ma...

Page 3: ...its use Keep all exits clear Be sure to remove snow from all paths in the winter and remove objects that are block ing any of the exits Have a predetermined assembly point where everyone can be accounted for for example across the street or in a parking lot Once everyone is out of the home building call the Fire Department A good plan emphasizes a quick escape Do not inves tigate first or attempt ...

Page 4: ...ed to try to correct the interference by one or more of the fol lowing measures Re orient the receiving antenna Increase the separation between the equipment and receiver Connect the equipment into an outlet on a circuit different from that to which the receiver is connected Consult the dealer or an experienced radio television technician for help The user may find the following booklet prepared b...

Reviews: