background image

The 

Series 634ES Pressure Transmitter 

senses a single

air, compatible gas or liquid pressure and converts it into
a standard 4-20 mA output signal. Ranges are available
from 0-10 through 0-6000 psi. All models are field
adjustable so any range within these limits can be
achieved by recalibration using the easily accessible
span and zero potentiometers. 

Positive pressure can be measured within an accuracy of
±0.5% of span. The Series 634ES uses an isolated
piezoresistive pressure sensor to produce a resistance
change across a wheatstone bridge. The signal is condi-
tioned and converted into a 4-20 mA output signal.

For applications requiring direct pressure or percent of
full span readings, the optional A-701 digital readout
makes an ideal companion device, providing a bright .6”
high, 3-1/2˝ digit LED and supplying power to the Series
634ES Transmitter.

PHYSICAL DATA
GENERAL
Maximum Pressure:

See chart on this page.

Wetted Parts: 

316, 316L Stainless Steel.

Housing:

Designed to meet NEMA-4X.

ELECTRICAL
Power Supply: 

12.3-35 VDC-2 wire.

Output Signal:

4-20 mA DC (limited at 38 mA DC).

Loop Resistance:

0 - 1100 ohms from 12.3 to 35 VDC.

R

L max

=

Current Consumption: 

DC: 38 mA max.

MATERIALS
Housing: 

Cast aluminum; textured gray polyurethane

finish. 

Pressure Connection: 

Stainless Steel.

MECHANICAL
Weight:

1 lb., 12 oz.  (.8 kg).

Span and Zero Adjustments:

Protected potentiome-

ters, located in auxiliary housing.

Pressure Connection:

1/4˝ female NPT x 1/2˝ male

NPT.

PERFORMANCE AT 70°F (21.1°C)
Zero Output:

4 mA DC. 

Full Span:

16 mA DC.

Accuracy:

±0.5% of span.

Warm-up Time: 

10 minutes.

STABILITY/ENVIRONMENTAL
Operating Temperature: 

20 to 120˚F (- 6.7 to 48.9˚C). 

Thermal Errors:

± 0.02%/˚F typical.

Stability:

1% F.S./yr.

STANDARD ACCESSORIES

(3) “Z” mounting brackets.
(3) 10-32 x 4” RH machine screws.

Series 634ES Pressure Transmitter

Specifications - Installation and Operating Instructions

Bulletin E-69ES

Vps-12.3V

20 mA

Series 634ES Models and Ranges in PSI (bar)

634ES-0
634ES-1
634ES-2
634ES-3
634ES-4
634ES-5
634ES-6
634ES-7
634ES-8
634ES-9

10 (.69)

30 (2.07)
50 (3.45)
100 (6.9)

200 (13.8)
300 (20.7)
500 (34.5)

1000 (69)

2000 (138)
4000 (276)

10 (.69)

20 (1.38)
40 (2.76)
60 (4.14)
100 (6.9)

250 (17.2)
350 (24.1)
600 (41.4)

1250 (86)

2500 (172)

20 (1.38)
40 (2.76)
60 (4.14)
120 (8.3)

250 (17.2)
350 (24.1)
600 (41.4)

1250 (86)

2500 (172)
6000 (414)

30 (2.07)
60 (4.14)
100 (6.9)

200 (13.8)
400 (27.6)
500 (34.5)

1000 (69)

2000 (138)
4000 (276)
7500 (517)

Model Number 

As Stocked         Min. Range

Max. Range

Max Pressure

DWYER INSTRUMENTS, INC.

Phone: 219/879-8000

www.dwyer-inst.com

P.O. BOX 373 • MICHIGAN CITY, INDIANA 46361, U.S.A.

Fax: 219/872-9057  

e-mail: info@dwyer-inst.com

Lit-By Fax: 888/891-4963

2-1/2 [63.50]

TYP

1-11/16

[42.86]

5-5/16

[134.94]

1/4NPT

1/2NPT

2-7/8 [73.03]

1/16 [1.59]
25/32 [19.84]

03-3/8 [85.73]

3/4 NPT

1-9/16

[39.69]

(3) #10-32 x 1/4 [6.35] DP HOLES

EQUALLY SPACED ON A 2-1/2 [63.50] B.C.

E-69ES (634ES)-4.0  6/26/02  11:05 AM  Page 1

Summary of Contents for 634ES Series

Page 1: ...2 oz 8 kg Span and Zero Adjustments Protected potentiome ters located in auxiliary housing Pressure Connection 1 4 female NPT x 1 2 male NPT PERFORMANCE AT 70 F 21 1 C Zero Output 4 mA DC Full Span 16 mA DC Accuracy 0 5 of span Warm up Time 10 minutes STABILITY ENVIRONMENTAL Operating Temperature 20 to 120 F 6 7 to 48 9 C Thermal Errors 0 02 F typical Stability 1 F S yr STANDARD ACCESSORIES 3 Z mo...

Page 2: ...CAUTION DO NOT EXCEED SPECIFIED SUPPLY VOLT AGE RATINGS PERMANENT DAMAGE NOT COVERED BY WARRANTY WILL RESULT THIS UNIT IS NOT DESIGNED FOR AC VOLTAGE OPERATION Electrical connections to the Series 634ES Transmitter are made inside the enclosure Remove the cover feed stripped and tinned leads through the conduit opening and connect to terminal block screws marked and See Figure A for locations of t...

Page 3: ...letin E 69ES Page 3 OPERATING REGION MAXIMUM VALUE 1100 TOTAL RECEIVER RESISTANCE Vps 12 3 20mA DC WIRE LENGTH The maximum length of wire connect ing transmitter and receiver is a function of wire size and receiver resistance Wiring should not contribute more than 10 of receiver resistance to total loop resistance For extremely long runs over 1000 feet choose receivers with higher resistances to m...

Page 4: ...ter is that any number of receivers can be connected in series in the current loop Thus an A 701 Digital Readout Accessory an analog panel meter a chart recorder process control ling equipment or any combination of these devices can be operated simultaneously It is only necessary that these devices all be equipped with a standard 4 20 mA input and that proper polarity of the input connections be o...

Reviews: