The Series DW-WIFI Wireless Wi-Fi Data Logger
measures and
records up to 1,000,000 temperature and/or humidity readings and
shares the data with any PC or server on the same Wi-Fi network.
Software settings allow the user to set the high and low alarms, the
sampling rate, and the temperature scale. If the Wi-Fi connection is lost,
the sensor will continue to store any records until it can regain
communication with the network. Stored data can be viewed at any time
after the communications have been restored. Each data logger includes
a wall bracket that allows the data logger to be mounted to any wall or
flat surface.
SOFTWARE INSTALLATION/LOGGER SET-UP
Upon start-up, a reading may be displayed on the LCD; however, the
product set-up must be completed in order to connect to a Wi-Fi network.
1. Before connecting the unit, download the free configuration and
logging software for this series, which is available on our website,
http://www.dwyer-inst.com/DW-USBSoftware.
2. After the software is installed, plug the data logger into the PC’s USB
port using the supplied cable and open the software.
3. Click on the “Set-Up Sensor” button.
4. Click on your Wi-Fi network and enter your password, if required.
Series DW-WIFI Wireless Wi-Fi Data Logger
Installation and Operating Instructions
Bulletin PC-DW-WIFI
SPECIFICATIONS
Range:
Temperature:
DW-WIFI-T(-HA), DW-WIFI-TH(-HA): -4 to 140°F (-20 to 60°C);
DW-WIFI-TP(-HA): -40 to 257°F (-40 to 125°C);
DW-WIFI-TC:
Supplied K-Type Thermocouple: 32 to 752°F (0 to 400°C);
Full Range (Probe Dependent): -454 to 2372°F
(-270 to 1300°C);
Humidity (TH models only): 0 to 100%.
Accuracy (typ.):
Temperature:
DW-WIFI-T: ±1.0°F (±0.5°C) @ 14 to 122°F (-10 to 50°C);
DW-WIFI-TH: ±0.6°F (±0.3°C) @ 41 to 140°F (5 to 60°C);
DW-WIFI-TP: ±1.2°F (±0.6°C) @ 14 to 158°F (-10 to 70°C);
DW-WIFI-TC: ±3.0°F (1.5°C);
DW-WIFI-T-HA: ±0.2°F (±0.1°C) @ 14 to 140°F (-10 to 60°C);
DW-WIFI-TH-HA: ±0.4°F (±0.2°C) @ 41 to 140°F (5 to 60°C);
DW-WIFI-TP-HA: ±0.2°F (±0.1°C) @ 14 to 158°F (-10 to 70°C);
Humidity (TH models only):
DW-WIFI-TH: ±2.5% RH @ 20 to 80% RH;
DW-WIFI-TH-HA: ±2.5% RH @ 10 to 90% RH.
Display Resolution:
Temperature:
DW-WIFI-T, DW-WIFI-TP, DW-WIFI-TC: 0.1°F (0.1°C);
DW-WIFI-TH(-HA): 0.5°F (0.5°C);
DW-WIFI-T-HA, DW-WIFI-TP-HA: 0.01°F (0.01°C).
Humidity (TH models only): 1.0% RH.
Memory Size:
1,000,000 readings; 500,000 each for DW-WIFI-TH(-
HA).
Sampling Mode:
Continuous recording.
Sampling Rate:
Selectable from 10 s to 12 hrs.
Transmission Rate:
Selectable from 1 min to 24 hrs.
Temperature Limits:
-4 to 140°F (-20 to 60°C).
Power Requirements:
4.5 to 5.5 VDC; (1) 3.7 V rechargeable lithium
ion battery, installed functional, factory replaceable (cable for charging
included).
Alarms:
Programmable high/low.
Interface:
Wi-Fi connection.
Probe Length:
DW-WIFI-TP: 11.8 in (30 cm);
DW-WIFI-TC: 59 in (150 cm).
Weight:
7.2 oz (204 g).
Agency Approvals:
CE, RoHS.
ALL MODELS
3-7/8
[97.30]
1
[26.36]
2-3/4
[71.30]
DWYER INSTRUMENTS, INC.
Phone: 219/879-8000
www.dwyer-inst.com
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46360, U.S.A.
Fax: 219/872-9057
e-mail: info@dwyermail.com
The logger will arrive partially charged, but for maximum
performance, charge it for 24 hours before the first use.
NOTICE