Operation Manual

EE600

Differential Pressure Sensor

Summary of Contents for EE600

Page 1: ...BA_EE600_e v1 1 technical data are subject to change Operation Manual EE600 Differential Pressure Sensor...

Page 2: ...and found to comply with the limits for a Class A digital device pursuant to part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference when the...

Page 3: ...e with S3 and S4 7 4 3 Select the display unit with S5 and S6 7 4 4 Select the backlight for the display 7 4 5 Select the Output Signal with S8 7 5 Installation 8 5 1 Pressure connection 8 6 Maintenan...

Page 4: ...damage the device Do not use EE600 in explosive atmosphere or for measurement of aggressive gases Do not apply the nominal voltage to the output terminals 1 1 2 Mounting start up and operation The EE6...

Page 5: ...ng conditions Consequential damages are excluded from the liability 1 2 Environmental aspects Products from E E Elektronik are developed and manufactured observing of all relevant requirements with re...

Page 6: ...LED Fig 2 Design and components 15 35 V DC 24 V AC 20 Fig 3 Connection diagram 4 Initial Setup Each EE600 leaves the E E factory with the default setup all switches on 0 Measurement range 100 of the f...

Page 7: ...e response time with S3 and S4 Tab 2 DIP switch settings Response time 4 3 Select the display unit with S5 and S6 Tab 3 DIP switch settings Display unit 4 4 Select the backlight for the display S7 Bac...

Page 8: ...3 Connection diagram Close tightly the cable gland This is essential for the compliance with the IP65 NEMA4 protection class of the EE600 enclosure Fig 5 Mounting orientation 5 1 Pressure connection F...

Page 9: ...ose route Important Make sure to connect the higher pressure at the pressure connector and the lower pressure at the pressure connector Inverted connection leads to out of range information on the opt...

Page 10: ...is used to correct an eventual zero point deviation a Remove the tubes from both pressure connections of the EE600 By this the pressure is same at both connections b Press zero point button 1 2sec see...

Page 11: ...a case the set point adjustment can be forced by pressing and holding the span point button for 10 sec f The successful zero point adjustment is confirmed by the green LED turning on for 2 seconds 6 3...

Page 12: ...r negative pressure due to inverse pressure connection the display indicates out of range out of range p 5 MR or inverse pressure connection p 105 MR Fig 10 Failure indication Green LED flashing 1s in...

Page 13: ...5 Additionally the analogue outputs indicate measurement out of range as follows Indication of p 5 MR and of negative difference pressure due to inverted pressure connection Output signal Indication...

Page 14: ...1 mA selectable with and4 DIP switches1 0 20 mA or 4 20 mA 3 wire RL 500 Ohm General Power supply 15 35 V DC or 24 V AC 20 Current consumption typ 18 mA without Display at 0 Pa 24 V DC typ 43 mA with...

Page 15: ...15 Preliminary operation manual EE600 Differential Pressure Sensor...

Page 16: ...0 6460 Office Stuttgart Tel 49 151 538 37 500 E E Elektronik Italy info epluse it Tel 39 02 2707 86 36 E E Elektronik France info epluse fr Tel 33 4 74 72 35 82 E E Elektronik USA office epluse com Of...