background image

 www.e-t-a.de

Electronic Circuit Protector ESX10-T.-DC 24 V

1822

1

  4

Description

ESX10-TD

E-T-A’s ESX10-T electronic circuit protector is only 12.5 mm wide and 
selectively protects all DC 24 V load circuits, thereby increasing the 
uptime of machines and systems. This is achieved by a combination 
of active electronic current limitation in the event of a short circuit and 
overload disconnection typically from 1.1 times rated current. The 
ESX10-T responds faster than frequently used DC 24 V switch mode 
power supplies without tripping fast and thus prevents disastrous 
voltage dips of the supply. It works with a single trip curve for all loads. 
Even capacitive loads up to 75,000 μF can be handled very easily.  
Besides fixed current ratings from 0.5 A  to 12 A, adjustable current 
rating versions are also available. The integral fail-safe element (fuse) 
is adjusted to the circuit protector’s rated current and can thus very 
easily be synchronised with the wired cable cross section. This makes 
planning much easier.

Features

Information online

Your benefits

l

 

Track-mountable

l

 

Active linear current limitation

l

 

Capacitive loads up to 75,000 μF

l

  ESX10-TA/-TB: fixed current ratings 0.5 A…12 A 

l

   ESX10-TD: adjustable current ratings, e.g. [0,5 A / 1 A / 2 A];  

[2 A / 4 A / 6 A]; [6 A / 8 A / 10 A]

Approvals: UL, CSA, GL

l

  OPTION: Control inputs, signalling

l

  OPTION: ATEX approval 

l

  

Increases machine uptime through clear failure detection and 

 

stable power supply

l

  Reduces downtimes through quick fault resolution

l

  Simplifies planning through clear sizes and ratings 

l

   Saves costs and time through fast and flexible mounting including 

integral power distribution solution

Preferred types

Short description

Preferred ratings (A)

ESX10-TA/-TB

fixed current rating

0.5

1

2

3

4

6

8

10

12

0.5/1/2 2/4/6 6/8/10

ESX10-TA-100-DC24V-

without auxiliary contacts

ESX10-TB-101-DC24V-

auxiliary contact  

“make contact”

ESX10-TD

adjustable current rating

0.5

1

2

3

4

6

8

10

12

0.5/1/2 2/4/6 6/8/10

ESX10-TD-101-DC24V-

auxiliary contact  
“make contact”

Preferred types – for more details on all configurations please see order numbering code 

Preferred types are E-T-A products most frequently used by E-T-A 

customers. We manufacture E-T-A preferred types in particularly high 

volumes. Our preferred types are supplied at shorter lead times than 

non-standard versions.

Approvals

http://www.e-t-a.de/qr1006/   

For access to the latest documents please follow:

Compliances

Summary of Contents for ESX10-T -DC Series

Page 1: ...on l Capacitive loads up to 75 000 F l ESX10 TA TB fixed current ratings 0 5 A 12 A l ESX10 TD adjustable current ratings e g 0 5 A 1 A 2 A 2 A 4 A 6 A 6 A 8 A 10 A l Approvals UL CSA GL l OPTION Cont...

Page 2: ...ntrol signal OFF device is switched off l No operating voltage UB Reset input RE ESX10 T 124 127 Electrical data voltage max DC 32 V High DC 8 V DC 32 V Low DC 3 V 0 V current consumption typically 2...

Page 3: ...pping length 10 mm tightening torque EN60934 1 5 1 8 Nm multi lead connection 2 identical cables rigid flexible 0 5 4 mm2 flexible with wire end ferrule without plastic sleeve 0 5 2 5 mm2 flexible wit...

Page 4: ...l output only ESX10 TA 1 signal make contact 2 signal break contact 4 status output SF only 114 124 7 status output inverted only ESX10 T 127 Operating voltage DC 24 V voltage rating DC 24 V Current r...

Page 5: ...0 mV 1 8 x IN 1 A 1 A 1 A 2 A 130 mV 1 8 x IN 2 A 2 A 2 A 3 A 80 mV 1 8 x IN 3 A 3 A 3 A 4 A 100 mV 1 8 x IN 4 A 4 A 4 A 6 A 130 mV 1 8 x IN 6 A 6 A 6 A 8 A 120 mV 1 5 x IN 8 A 8 A 8 A 10 A 150 mV 1 5...

Page 6: ...DC 24 V 0 5 A 16 A UL ISA 12 12 01 2015 Class Division 2 Groups A B C D E320024 DC 24 V 0 5 A 12 A UL UL 508 C22 2 No 14 E322549 DC 24 V 0 5 A 16 A DNV GL Rules VI part 7 GL 2012 category C EMC1 4676...

Page 7: ...lymers Corporation Type Epi Fine 4616L 160PK Casing Material Generic Name Liquid Crystal Polymer Supplier Sumitomo Chemical Type E4008 E4009 or E6008 RECOMMENDATION Periodically inspect the device nam...

Page 8: ...erating condition SF 24 V OK fault condition SF 0 V LINE 1 14 13 2 LOAD 0V 3 ESX10 TB 101 without signal input with signal output F single signal N O operating condition 13 14 closed fault condition 1...

Page 9: ...on ESX10 T and tolerance of the shut off point typically 1 1 x IN 1 05 1 35 x IN has already been taken into account ESX10 T current rating adjustment IN in A e g trip current Iab 1 25 x IN in A Rmax...

Page 10: ...13 grey remove protection against brush contact from bottom side 12 5 x n 3 length of busbars 0 5 e g 12 5 x 5 3 59 5 0 5 insert protection against brush contact continuous busbar 500 mm length cut 5...

Page 11: ...3 0V 2 LOAD 2 LOAD 2 LOAD Connection diagrams and application examples ESX10 T Signal contacts are shown in OFF or fault condition ESX10 TA 100 ESX10 TB 101 group signalling series connection line en...

Page 12: ...2 or X 222 611 xx LINE busbar X 222 611 02 or X 222 611 xx single signalling per way by means of an LED 22 1 LINE RE SF 23 22 1 LINE RE SF 23 22 1 LINE RE SF 23 reset button power supply DC 24 V 24 V...

Page 13: ...mp 0 V busbar X 222 611 02 or X 222 611 xx power supply DC 24 V 24 V 0 V line entry 0 5 A ESX10 TA 100 1 LINE 1 LINE 1 LINE 1 LINE 2 LOAD 2 LOAD 2 LOAD 2 LOAD 11 11 11 12 12 12 line entry ESX10 TB 102...

Page 14: ...for aux contacts and reset inputs suitable for signal busbars ESX10 TB ampacity with one input Imax 1 A with aux contacts connected in series Imax 0 5 A grey insulated length 500 mm part no X 222 005...

Page 15: ...from their marking Accessories ESX10 TD Application example of adhesive label switch for current rating adjustment cover label with adjusted rating e g 4 A see accessories ESX10 TD cover for current...

Reviews: