__________________________________________________________________________________________________________________
European Safety Systems Ltd.
Impress House, Mansell Road, Acton, London W3 7QH sales@e2s.com Tel: +44 (0)208 743 8880
www.e2s.com Fax: +44 (0)208 740 4200
Document No. D211-00-601-IS-SC Issue: F 02-03-2020 Sheet 1 of 9
INSTRUCTION & SERVICE MANUAL
D2xC2 ALARM HORN AND STROBE
For Use In Hazardous Locations
1) Warnings
DO NOT OPEN WHEN AN EXPLOSIVE
ATMOSPHERE IS PRESENT
DO NOT OPEN WHEN ENERGISED
POTENTIAL ELECTROSTATIC CHARGING
HAZARD - CLEAN ONLY WITH A DAMP
CLOTH
HIGH VOLTAGE SHOCK HAZARD. WAIT 5
MINUTES AFTER REMOVING POWER
BEFORE OPENING THE ENCLOSURE
DO NOT PAINT
Avertissement:
NE PAS OUVRIR UN PRESENCE
D’ATMOSPHERE EXPLOSIVE
NE PAS OUVRIR ENERGIE
DANGER POTENTIEL CHARGE
ÉLECTROSTATIQUE - NETTOYER
UNIQUEMENT AVEC UN CHIFFON HUMIDE
HAUT TENSION, RISK DE CHOC. ATTENDEZ
5 MINUTES APRES AVOIR DEBRANCHE
L’ALIMENTATION AVANT D’OUVRIR LA
BOITIER
NE PAS PEINTURER
2) Rating & Marking Information
2.1 Fire Alarm Ratings
The Following models are certified for use
an Audible &
Visual Appliance for use in Fire Alarm Systems Private Mode
in accordance with UL464 Tenth Edition & UL1638 Fifth
Edition.
D2xC2X05DC024
D2xC2X10DC024
On-axis light output per UL1638 at 1Hz:
Model
Lens cover colour
Light output in cd
D2xC2X05DC024
clear 17.4
red 5.4
D2xC2X10DC024
clear 53.4
red 17.4
For Fire Alarm applications, the Sounder Volume must be at
the highest setting, (see volume control section).
The sounder section produces a sound pressure level above
75dB(A) at 10 feet.
For fire alarm use, the temporal pattern tone No. 12 as per the
tone table provided in these instructions must be selected. This
tone produces a minimum sound pressure level of:
CAN/ULC-S525: 100.4dB(A)* at 10 feet.
(*anechoic room)
UL464:
92.2dB(A)
†
at 10 feet.
(
†
reverberation room)
2.2 surge current ratings for use in fire alarm systems
Model Peak
Surge
current
RMS surge current
Beacon Sounder Beacon Sounder
D2xC2X05DC024 1.04A 3.18A
437mA 1.3A
D2xC2X10DC024 0.99A 3.18A
620mA 1.3A
2.3 NEC & CEC Class / Division Ratings for US / Canada
The D2xC2 combined sounder beacon complies with the
following standards:
ANSI/ISA 12.12.01-2015
CSA C22.2 No. 213-16
The D2xC2X05DC024 Combined unit is rated as follows:
Class I Div 2 ABCD T3 Ta -40°C to +50°C
Class II Div 2 FG T6 Ta -40°C to +50°C
Class III Div 1&2 Ta -40°C to +50°C
The D2xC2X10DC024 Combined unit is rated as follows:
Class I Div 2 ABCD T2A Ta -40°C to +50°C
Class II Div 2 FG T6 Ta -40°C to +50°C
Class III Div 1&2 Ta -40°C to +50°C
The D2xC2X05DC048 & D2xC2X05AC Combined units are
rated as follows:
Class I Div 2 ABCD T3 Ta -40°C to +50°C
Class II Div 2 FG T5 Ta -40°C to +50°C
Class II Div 2 FG T6 Ta -40°C to +40°C
Class III Div 1&2 Ta -40°C to +50°C
The D2xC2X10DC048 & D2xC2X10AC Combined units are
rated as follows:
Class I Div 2 ABCD T2B Ta -40°C to +50°C
Class II Div 2 FG T5 Ta -40°C to +50°C
Class II Div 2 FG T6 Ta -40°C to +40°C
Class III Div 1&2 Ta -40°C to +50°C
Installation must be carried out in compliance with the National
Electric Code / Canadian Electric Code
2.4 NEC Class / Zone ratings US
The D2xC2X05 and D2xC2X10 Xenon beacons comply with the
following standards:
UL 60079-0-2013
UL 60079-15-2013
UL 60079-31-2015
The D2xC2X05DC024 Combined unit is rated as follows:
Class I Zone 2 AEx nA IIC T3 Gc Ta -40°C to +50°C
Zone 22 AEx tc IIIC 75°C Dc Ta -40°C to +50°C