INSTRUCTION & SERVICE MANUAL 

D2xC2LD2 ALARM HORN AND LED 

For Use In Hazardous Locations 

 

 

 
 
 
 
 
 
 
 
 
 
 
 

 

1) 

Warnings 

 DO NOT OPEN WHEN AN EXPLOSIVE 

ATMOSPHERE IS PRESENT 

 DO NOT OPEN WHEN ENERGISED 

 POTENTIAL ELECTROSTATIC CHARGING 

HAZARD - CLEAN ONLY WITH A DAMP 
CLOTH 

 DO NOT PAINT 

 

Avertissement: 

 NE PAS OUVRIR UN PRESENCE 

D’ATMOSPHERE EXPLOSIVE 

 NE PAS OUVRIR ENERGIE 

 DANGER POTENTIEL CHARGE 

ÉLECTROSTATIQUE - NETTOYER 
UNIQUEMENT AVEC UN CHIFFON HUMIDE 

 NE PAS PEINTURER 

 

2) 

Rating & Marking Information 

 

2.1  Public Mode Fire Alarm Ratings 

 
The D2xC2LD2DC024 is certified for use a as public mode 
audible and visual alarm device in accordance with UL464 & 
UL1971 / UL1638. 
 
For use in public-mode fire alarm systems the equipment 
must be installed without the wire guard or plastic lens cover 
on the beacon. 
 
The beacon must be set to one of the certified flash patterns 
of 1Hz, 1.5Hz or 2Hz (for DIP switch settings see section 10). 
 
For light output ratings of the beacon see section 12. 
 
The sounder section produces a sound pressure level above 
75dB(A) at 10 feet: 
 
For Fire Alarm applications, the Sounder Volume must be at 
the highest setting, (see volume control section). 
 
For fire alarm use, the temporal pattern tone No. 12 as per the 
tone table provided in these instructions must be selected.  
This tone produces a minimum sound pressure level of: 
 
CAN/ULC-S525:  100.4dB(A)* at 10 feet. 

(*anechoic room) 

UL464:  

92.2dB(A)

 at 10 feet. 

(

reverberation room)

 

Testing of synchronization requirements of UL1971 & UL1638 / 
CAN/ULC-S526 were conducted by UL using a total of 6 units 
connected to the same wire run. Auto-synchronization does not 
require the use of any external sync modules or protocols. 
Providing the correct cable has been selected (see section 6) an 
unlimited number of units will remain synchronized when 
powered from the same source. 
 

2.2  Private Mode Fire Alarm Ratings 

 
The D2xC2LD2DC024 is approved for use as Audible and 
Visual Appliance for use in Fire Alarm Systems – Private Mode. 
 
For private mode fire alarm use the beacons must only be fitted 
with clear or red plastic lens covers and must be set to one of 
the certified flash patterns of 1Hz, 1.5Hz or 2Hz (for DIP switch 
settings see section 10). 
 
For light output ratings see section 12. 

 

2.3  NEC & CEC Class / Division Ratings for US / Canada 

 
The D2xC2LD2 LED beacon complies with the following 
standards: 
 

ANSI/ISA 12.12.01-2015 
CSA C22.2 No. 213-16 

 
The D2xC2LD2 LED beacon is rated as follows: 
 

Class I Div 2 ABCD T4 Ta -40°C to +50°C 
Class I Div 2 ABCD T4A Ta -40°C to +40°C 
Class II Div 2 FG T6 Ta -40°C to +50°C 
Class III Div 1&2 Ta -40°C to +50°C 
 

Installation must be carried out in compliance with the National 
Electric Code / Canadian Electric Code 
 

2.4  NEC Class / Zone ratings US 

 
The D2xC2LD2 LED beacon complies with the following 
standards: 
 

UL 60079-0-2013 
UL 60079-15-2013 
UL 60079-31-2015 

 
The D2xC2LD2 LED beacon is rated as follows: 
 
Class I Zone 2 AEx nA IIC Gc T4 Ta -40°C to +50°C 
AEx tc IIIC 75°C Dc Ta -40°C to +50°C 
 
Installation must be carried out in compliance with the National 
Electric Code. 
 

2.5  CEC Class / Zone ratings Canada 

 
The D2xC2LD2 LED beacon complies with the following 
standards: 
 

CAN/CSA C22.2 No. 60079-0:2015 
CAN/CSA C22.2 No. 60079-15:2016 
CAN/CSA C22.2 No. 60079-31:2015 

 
The D2xC2LD2 LED beacon is rated as follows: 
 

Summary of Contents for D2xC2LD2 Series

Page 1: ...om UL464 92 2dB A at 10 feet reverberation room Testing of synchronization requirements of UL1971 UL1638 CAN ULC S526 were conducted by UL using a total of 6 units connected to the same wire run Auto...

Page 2: ...e rating per UL50E NEMA250 4 4X 3R 13 To maintain the ingress protection rating the cable entries must be fitted with suitably rated certified cable entry and or blanking devices during installation 2...

Page 3: ...on this cable run The wire size and total length of the cable run determining the total resistance of this cable run The minimum output voltage supplied by the power supply The voltage drop and input...

Page 4: ...Simply connect the supply voltage to the L and N supply terminals see fig 3a b The Strobe is powered via factory installed wires connected to the sounder The wires connecting the alarm horn and strob...

Page 5: ...their supply input lines An end of line monitoring resistor can be connected across the ve and ve terminals If an end of line resistor is used it must have the following values 24V DC Alarm Horn and...

Page 6: ...ip Switch 1 ON 0 OFF Example shown 100000 Flashing 1Hz Default setting 13 Interchangeable Spare Parts The Beacon lens cover is interchangeable contact E2S Ltd for a replacement lens cover available in...

Page 7: ...out to the correct NFPA standards and guidelines 15 1 Horizontal Light Output Dispersion for wall mounting public mode 0 15 15 30 45 60 75 90 90 30 45 60 75 Fig 13 Horizontal dispersion angles for wal...

Page 8: ...sion for wall mounting public mode 75 60 45 30 15 0 90 Fig 14 Vertical dispersion angles for wall mounting Table 4 Vertical Light Output Dispersion for Wall Mounting Viewing Angle Of Rating Intensity...

Page 9: ...per UL 1971 UL1638 CAN ULC S526 at worst case min input voltage 15 4 On axis light output rating private mode Table 5 Vertical Light Output Dispersion for Ceiling Mounting Viewing Angle Of Rating Inte...

Page 10: ...z 47 4mA 47 4mA Flashing 1 5Hz 50 3mA 50 3mA Flashing 2Hz 51 1mA 51 1mA Flashing Double Strike 62 2mA 62 2mA Flashing Triple Strike 69 2mA 69 2mA D2xC2LD2AC115 115Vac 60Hz 115 120Vac 50 60Hz Steady Hi...

Page 11: ...0 208 740 4200 Document No D211 00 611 IS SC Issue E 02 03 2020 Sheet 11 of 13 17 Sound Directional Characteristics for Canadian Fire CAN ULC S525 Horizontal Axis Angle OSPL Angle OSPL Reference 90 10...

Page 12: ...n 0 5s off x3 1s gap ISO 8201 Temporal Pattern 0 1 0 1 0 0 44 1 8 12 1000Hz 0 5s on 0 5s off x3 1s gap ISO 8201 Temporal Pattern 1 1 0 1 0 0 44 1 8 13 422 775Hz 0 85 on 0 5 off x3 1s gap NFPA Temporal...

Page 13: ...1 44 24 12 49 560 1055Hz 0 18Hz Sweeping 0 0 0 0 1 1 44 24 12 50 560 1055Hz 3 3Hz Sweeping 1 0 0 0 1 1 44 24 12 51 600 1250Hz 0 125Hz Sweeping 0 1 0 0 1 1 44 24 12 52 660 1200Hz 1Hz Sweeping 1 1 0 0 1...

Reviews: