European Safety Systems Ltd.

   Impress House, Mansell Road, Acton, London W3 7QH 

 sales@e-2-s.com 

    Tel: +44 (0)208 743 8880 

   www.e-2-s.com   

 Fax: +44 (0)208 740 4200 

Document No.D156-00-501-IS 

Issue 1 

 11-12-15 

 Sheet 1 of 3

 

INSTRUCTION MANUAL (ATEX / IECEx) 

GNExJ

2

 Flameproof Junction Box

 

For use in Flamma

 

ble Gas and Dust Atmospheres

 

1)

Introduction

The GNExJ2 is a flameproof junction box which is certified to 
meet the requirements of the ATEX directive 94/9/EC and the 
IECEx  scheme.  The  junction  box  can  be  used  in  hazardous 
areas where potentially flammable gas and dust atmospheres 
may  be  present.  The  GNExJ2  can  be  used  in  Zone  1  and 
Zone  2  areas  with  gases  in  groups  IIA,  IIB  and  IIC  and 
Temperature  Classifications  of  T1,  T2,  T3,  T4,  T5  and  T6. 
The unit can be used in Zone 21 and Zone 22 with dusts in 
groups  IIIA,  IIIB  and  IIIC  and  Temperature  Classifications  of 
T1, T2, T3, T4, T5 and T6. 

2)

Marking

All  units  have  a  rating  label,  which  carries  the  following 
important information:- 

Unit Type No.    GNExJ2 

Max. Voltage: 

60Vdc / 260Vac 50/60Hz 

Max Power Dissipation: 5W 

Codes: 

Ex db IIC Gb T6 Ta -50°C to +70°C

 

Ex tb IIIC Db T80°C Ta -50°C to +70°C 

Certificate No. 

DEMKO 15ATEX1448X 
IECEx UL15.0003X 

“Warnings” 

     

POTENTIAL ELECTROSTATIC CHARGING HAZARD 
DO NOT OPEN WHEN AN EXPLOSIVE     
ATMOSPHERE IS PRESENT 
ALL ENTRIES M20 X 1.5 
IF TEMPERATURE EXCEEDS 70ºC AT ENTRY OR 80ºC AT 
BRANCHING POINT USE SUITABLE RATED CABLE AND CABLE 
GLANDS 

3)

Type Approval Standards

The  junction  box  has  an  EC  Type  examination  certificate 
issued  by  UL  and  have  been  approved  to  the  following 
standards:- 

EN60079-0:2012 / IEC60079-0:2011 (Ed 6): Explosive Atmospheres 
- Equipment. General requirements  
EN60079-1:2014 / IEC60079-1:2014 (Ed 7): Explosive Atmospheres 
- Equipment protection by flameproof enclosures "d"  
BS EN 60079-31:2014 / IEC 60079-31:2013 (Ed 2): Explosive 
Atmospheres - Equipment dust ignition protection by enclosure "t" 

4)

Installation Requirements

The  junction  box  must  only  be  installed  by  suitably  qualified 
personnel in accordance with the latest issues of the relevant 
standards: 

EN60079-14 / IEC60079-14: Explosive atmospheres - Electrical 
installations design, selection and erection 
EN60079-10-1 / IEC60079-10-1: 

Explosive atmospheres - 

Classification of areas. Explosive gas atmospheres 
EN60079-10-2 / IEC60079-10-2: 

Explosive atmospheres - 

Classification of areas. Explosive dust atmospheres 

The installation of the units must also be in accordance with 
any  local  codes  that  may  apply  and  should  only  be  carried 
out  by  a  competent  electrical  engineer  who  has  the 
necessary training. 

The GNExJ2 is not intended for directly supporting live parts. 
All  conductors  must  be  suitably  insulated  and  secured 
against loosening. 

The Junction Box may be fitted with terminal blocks or active 
modules up to a power consumption of 5W. Any module fitted 
must  be  secured  to  the  mounting  bosses  in  the  base  of  the 
junction box  and  must maintain  a  minimum  gap  of  10mm  to 
all walls of the enclosure. 

5)

Zones,  Gas  Group,  Category,  IP  Rating  and
Temperature Classification

The units can be installed in locations with the following 
conditions:- 

Area Classification Gas: 

Zone 1 

Explosive  gas  air  mixture  likely  to  occur  in 
normal operation. 

Zone 2 

Explosive gas air mixture not likely to occur, 
and if it does, it will only exist for a short time. 

 

Gas Groupings: 

Group IIA 

Propane 

Group IIB 

Ethylene 

Group IIC 

Hydrogen and Acetylene 

Temperature Classification: 

T1 

450

o

 C 

T2 

300

o

 C 

T3 

200

o

 C 

T4 

135

o

 C 

T5 

100

o

 C 

T6 

85

o

 C 

Area Classification Dust: 

Zone 21 

Explosive  dust  air  mixture  likely  to  occur  in 
normal operation. 

Zone 22 

Explosive dust air mixture not likely to occur, and 
if it does, it will only exist for a short time. 

Dust Groupings: 

Group IIIA 

Combustible Flyings 

Group IIIB 

Non-conductive Dust 

Group IIIC 

Conductive Dust 

IP Rating: 

IP6X to EN/IEC60079-0 and IP66 to EN/IEC60529 

0518 

II  2G 
II  2D 

Epsilon x 
Equipment Group and 
Category: 

CE Marking 
Notified Body No. 

Reviews: