STExJ2 

 

 

 

1)  Warnings  

 

 

 

  POTENTIAL ELECTROSTATIC CHARGING HAZARD. 

  DO NOT OPEN WHEN AN EXPLOSIVE ATMOSPHERE IS 

PRESENT. 

  ALL ENTRIES M20 X 1.5MM. 

  USE  SUITABLE  RATED  CABLES  AND  CABLE  GLANDS 

IF  TEMPERATURE  EXCEEDS  AS  PER  STANDARDS 
INDICATIONS BELOW. 
FOR ATEX / IECEx STANDARDS: 

70ºC AT ENTRY OR 80ºC AT BRANCHING POINT. 

FOR NEC / CEC STANDARDS: 

60ºC AT ENTRY OR 60ºC AT BRANCHING POINT. 

 

2)  Marking & Rating Information 

 
All  units  have  a  rating  label,  which  carries  the  following 
important information: 
 

Unit Type No.: 

STExJ2 

Max. Voltage: 

60Vdc 

260Vac 50/60Hz 

Max Power Dissipation: 

5W 

Table 1: Electrical Ratings. 

 

2.1. ATEX / IECEx Ratings 

 

Standards 

EN60079-0:2012+A1:2013 / IEC60079-0:2011 (Ed 6): 

Explosive Atmospheres - Equipment. General requirements  

EN60079-1:2014 / IEC60079-1:2014 (Ed 7): 

Explosive Atmospheres - Equipment protection by 
flameproof enclosures "d"  

BS EN 60079-31:2014 / IEC 60079-31:2013 (Ed 2): 

Explosive Atmospheres - Equipment dust ignition protection 
by enclosure "t" 

Ratings 

STExJ2 
 

Ex db IIC T5 Gb Ta -50°C to +70°C  
Ex db IIC T6 Gb Ta -50°C to +65°C  
Ex tb IIIC T85°C Db Ta -50°C to +70°C 

 

Certificate No.    

DEMKO 16 ATEX 1466X  
IECEx ULD 16.0017X 

Epsilon x, Equipment 
Group and Category: 

 

II  2G 
II  2D 

CE Marking 
Notified Body No. 

 

2813 

 

2.2. NEC / CEC Ratings 

 

 

 
All  models  are  approved  for  use  as  Visual  Signal  Device  for 
use as General Signalling: 
 

UL1638A & CSA C22.2 No 205-17 

 

NEC Class / Zone Ratings US Codes 

 

Standards 

UL 60079-0 (Ed. 7) 04/15/2020 

Explosive Atmospheres - Part 0: Equipment - General 
Requirements 

UL 60079-1 (Ed. 7) 2015 

Explosive Atmospheres - Part 1: Equipment Protection by 
Flameproof Enclosures 'd' 

Ratings 

STExJ2 
 

Class 1 Zone 1 AEx db IIC T5 Gb Ta -50°C to +70°C 
Class 1 Zone 1 AEx db IIC T6 Gb Ta -50°C to +65°C 

 
Installation must be carried out in compliance with the National 
Electric Code. 

 
 

 

Summary of Contents for STExJ2

Page 1: ...EC60079 0 2011 Ed 6 Explosive Atmospheres Equipment General requirements EN60079 1 2014 IEC60079 1 2014 Ed 7 Explosive Atmospheres Equipment protection by flameproof enclosures d BS EN 60079 31 2014 I...

Page 2: ...likely to occur in normal operation Zone 22 ATEX IECEx only Explosive dust air mixture not likely to occur in normal operation and if it does it will only exist for a short time Gas Groupings Group I...

Page 3: ...ve atmospheres Classification of areas Explosive gas atmospheres EN60079 10 2 IEC60079 10 2 Explosive atmospheres Classification of areas Explosive dust atmospheres NEC Class Zone CEC Class Zone and N...

Page 4: ...y or 60 C at branching point Therefore suitable heat resisting cables and cable glands must be used with a rated service temperature at least as stated in the Instructions document of the product bein...

Page 5: ...el in accordance with the current relevant standards EN60079 19 IEC60079 19 Explosive atmospheres Equipment repair overhaul and reclamation EN 60079 17 IEC60079 17 Explosive atmospheres Electrical ins...

Page 6: ...Netherlands B V Utrechtseweg 310 6812 AR Arnhem Netherlands Quality Assurance Notification Module D SIRA 05 ATEX M342 Provisions fulfilled by the equipment II 2G Ex db IIC T6 T3 Gb II 2D Ex tb IIIC T...

Page 7: ...e and Place of Issue London 03 12 2021 EU Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on the m...