HGD-2000 Hydrogen Gas Detector 

Installation & Operation Instructions - Dual Relay Model 

Hydrogen gas is only 7% the density of air, and thus rises. Your hydrogen gas detector, 
therefore, should be installed at the highest, draft-free location in the battery room or 
compartment where hydrogen gas would accumulate. 

Remove the cover from the detector box using care not to break the hinge 
connection at the top of the box. 

Attach the detector to the wall, ceiling, or optional junction box using the 
mounting holes at the top and bottom of the detector box. 

 

 

For hard wiring using conduit, the detector box will fit the following junction boxes: Appleton 

25075, Bowers 702 SPL, Raco 951, or Steel City 2G-1/2&3/4. If you have difficulty finding one 
of these junction boxes, you can order one from your dealer. 

The detector has a terminal block for connection to a single-phase ac power source and to one 
or two internal relays. The relays can be used to switch a remote exhaust fan and/or alarm on 
and off. 

For 120 volts ac power, use an 18 gage SJT 3-condustor PVC jacketed cable (Belden 19348, 
equivalent or better). For relay wires, use 14 gage wire (Belden 9989, equivalent or better). 

The detector's relay dry contacts are rated at 10A / 250VAC, sufficient for most 1/3 HP exhaust 
fans. For higher current requirements, add external relays. 

Ensure that your installation complies completely with all relevant local, state, federal, and 
OSHA safety and health regulations. 

An optional 2 inch (5 cm.) square remote box with duplicate LEDs, test button, and buzzer if 
wanted, can be placed anywhere. This remote box connects to the detector box via a standard 
style 6-connector, 6-contact telephone-type modular cable. 

 

Operation 

Keep the detector on at all times. If the green LED is lit, power is on. 

When power is first turned on, approximately 10 minutes will elapse before the detector will start 
to function. This delay is to prevent false activation of the internal relay and alarm. 

If the unit has been stored un-energized for more than 1 week, the sensor will require 7 days or 
more to stabilize. During this period the sensor will be overly sensitive to hydrogen gas. This 

Alarm on & off 