Service and support:

Call your local service representative

620-00082-02-i (en)

Tower models
5P 650i
5P 850i
5P 1150i
5P 1550i

1U Rack models
5P 650i R
5P 850i R
5P 1150i R
5P 1550i R

Installation  
and user manual

Summary of Contents for 5P 1150i

Page 1: ... All rights reserved Service and support Call your local service representative 620 00082 02 i en Tower models 5P 650i 5P 850i 5P 1150i 5P 1550i 1U Rack models 5P 650i R 5P 850i R 5P 1150i R 5P 1550i R Installation and user manual ...

Page 2: ...waste center This symbol indicates that you should not discard waste electrical or electronic equipment WEEE in the trash For proper disposal contact your local recycling reuse or hazardous waste center Information advice help UPS directives Safety IEC 62040 1 2008 C2 EMC IEC 62040 2 2005 VCCI Performance IEC 62040 3 2010 CE mark EN 62040 1 2008 and EN 62040 2 2006 C1 Class B emission level CISPR ...

Page 3: ...of tower models 13 3 3 Wall installation of rack models 650i R 850i R 1150i R 13 3 4 Installation of rack models 650i R only 14 3 5 Installation of rack models 850i R 1150i R 1550i R 14 3 6 Communication ports 15 4 Operation 16 4 1 Start up and Normal operation 16 4 2 Starting the UPS on Battery 16 4 3 UPS Shutdown 16 4 4 Operation on Battery Power 16 4 5 Return of AC Input Power 17 4 6 UPS remote...

Page 4: ...es over 50 of recycled cardboard Sacks and bags are made of polyethylene Packing materials are recyclable and bear the appropriate identification symbol 01 PET Materials Abbreviations Number in the symbols Polyethylene terephthalat PET 01 High density polyethylene HDPE 02 Polyvinyl chloride PVC 03 Low density polyethylene LDPE 04 Polypropylene PP 05 Polystyrene PS 06 Follow all local regulations f...

Page 5: ...x 233 13 6 x 5 9 x 9 2 5P 1150i 10 91 24 10 345 x 150 x 233 13 6 x 5 9 x 9 2 5P 1550i 15 95 35 20 445 x 150 x 233 17 5 x 5 9 x 9 2 Rack models H W D Description Weights kg lb Dimensions mm inch D x W x H 5P 650i R 8 6 19 00 363 5 x 438 x 43 2 14 3 x 17 2 x 1 7 5P 850i R 13 8 30 40 509 x 438 x 43 2 20 0 x 17 2 x 1 7 5P 1150i R 14 64 32 70 509 x 438 x 43 2 20 0 x 17 2 x 1 7 5P 1550i R 19 36 42 70 55...

Page 6: ...munication port 2 RS232 communication port 3 Slot for optional communication card 4 Connector for ROO remote ON OFF or RPO Remote Power Off control 5 Outlets for connection of critical equipment Primary group 6a Group 1 programmable outlets for connection of equipment 6b Group 2 programmable outlets for connection of equipment 7 Socket for connection to AC power source 8 Ground screw ...

Page 7: ... communication port 2 RS232 communication port 3 Slot for optional communication card 4 Connector for ROO remote ON OFF or RPO Remote Power Off control 5 Outlets for connection equipment Primary group 6a Group 1 programmable outlets for connection of equipment 6b Group 2 programmable outlets for connection of equipment 7 Socket for connection to AC power source 8 Ground screw ...

Page 8: ...00 720W 800VA Efficiency 98 Escape Up Down Enter On Off button Rack models Normal mode 100 10min 100 720 W 800VA Efficiency 98 Alarm Indicator red On battery Indicator yellow Power On Indicator green On Off button Up Down Enter Escape The following table shows the indicator status and description Indicator Status Description Green On The UPS is operating normally Yellow On The UPS is on battery mo...

Page 9: ...r Equipment is not powered until button is not pressed Normal mode The UPS is operating normally The UPS is powering and protecting the equipment In AVR mode No beep The UPS is operating normally but the utility voltage is outside normal mode thresholds The UPS is powering the equipment through a Automatic Voltage Regulation device The equipment is still normally protected On Battery Battery LED i...

Page 10: ...2 7 User settings The following table displays the options that can be changed by the user Description Available settings Default settings Local settings Language English Français Deutsch Italiano Português Español Русский Menus status notices and alarms UPS fault Event Log data and settings are in all supported languages English User selectable when UPS is powered for the first time LCD settings ...

Page 11: ...able Energy saving Disable Enable If enabled UPS will shutdown after 5min of back up time if no load is detected on the output Disable Sleep mode Disable Enable If disabled LCD and communication will turn OFF immediately after UPS is OFF If enabled LCD and communication stays ON 1h30 min after UPS is OFF Disable Remote command Disable Enable If enabled shutdown or restart commands from software ar...

Page 12: ...e CDROM 4 2 connection cables for the protected equipment 5 RS232 communication cable 6 USB communication cable 7 Cable locking systems 1 x 4 outlets 650i R and 850i R models 1 x 6 outlets 1150i R and 1550i R models 8 1U Rack kit ears only for 650i R model Packing materials must be disposed of in compliance with all local regulations concerning waste Recycling symbols are printed on the packing ma...

Page 13: ...Page 13 620 00082 02 i en ENGLISH 3 Installation 3 2 Installation of tower models 3 3 Wall installation of rack models 650i R 850i R 1150i R 1 1 2 2 ...

Page 14: ...ls 850i R 1150i R 1550i R Follow steps 1 to 4 for module mounting on the rails 3 Installation 1 1 2 2 3 3 4 4 The rails and necessary hardware are supplied by EATON 3 4 Installation of rack models 650i R only Follow steps 1 to 3 for rack mounting 2 3 2 3 1 ...

Page 15: ...nstallation of the communication cards optional 3 It is not necessary to shutdown the UPS before installing a communication card 1 Remove the slot cover 3 secured by screws 2 Insert the communication card in the slot 3 Secure the card cover with the 2 screws Characteristics of the optocouplers communication port optional Pins 1 3 4 5 6 10 not used Pin 2 common user Pin 7 low battery Pin 8 operatio...

Page 16: ...See the Cold start setting in ON OFF Settings on page 11 To start the UPS on battery 1 Press the button on the UPS front panel until the UPS front panel display illuminates and shows a status of UPS starting The UPS cycles through Standby mode to Battery mode The indicator illuminates solid The UPS supplies power to your equipment 2 Check the UPS front panel display for active alarms or notices be...

Page 17: ... UPS These functions are obtained by opening a contact connected between the appropriate pins of connector 4 on the rear panel of the UPS see figures below 4 Remote control connection and test 1 Check that the UPS is OFF and disconnected from the AC input source 2 Remove connector 4 after unscrewing the screws 3 Connect a normally closed volt free contact 60 V DC 30 V AC max 20 mA max 0 75 mm2 cab...

Page 18: ...move some of the equipment from the UPS The UPS continues to operate but may shutdown if the load increases The alarm resets when the condition becomes inactive End of battery life The end of the battery life is reached Contact your service representative for battery replacement Event An UPS event occurs Example Remote Power OFF the RPO contact has been activated to shutdown the UPS and now preven...

Page 19: ...an insulated handle Battery tray removal on tower models A A Remove the front panel B B Disconnect the battery block by separating the two connectors never pull on the wires C C Remove the plastic protection cover in front of the battery one screw D D Pull the plastic tab to remove the battery block and replace it Mounting the new battery module Carry out the above instructions in reverse order To...

Page 20: ...the two connectors never pull on the wires D D Remove the metal protection cover in front of the battery two screws E E Pull the plastic tab to remove the battery block and replace it Mounting the new battery module Carry out the above instructions in reverse order To ensure safety and high performance use only batteries supplied by EATON Take care to firmly press together the two parts of the con...

Page 21: ...wer 1 x 12 V 9 Ah 2 x 12 V 7 Ah 2 x 12 V 9 Ah 3 x 12 V 9 Ah Rack 2 x 6 V 9 Ah 4 x 6 V 7 Ah 4 x 6 V 9 Ah 6 x 6 V 9 Ah Environment Operating temperature range 0 to 35 C 0 to 40 C Storage temperature range 15 to 50 C Relative humidity 0 to 90 without condensation Noise level 40 dBA 1 The high and low thresholds can be adjusted using UPS settings up to 150 294 V 2 Up to 40 Hz in low sensitivity mode p...

Page 22: ...Page 22 620 00082 02 i en ...