background image

1U Rack Model
5P 1550G RL

Copyright © 2017 

Eaton

All rights reserved.

Installation 
and User Manual

Summary of Contents for 5P 1550G RL

Page 1: ...1U Rack Model 5P 1550G RL Copyright 2017 Eaton All rights reserved Installation and User Manual ...

Page 2: ...Page 2 ...

Page 3: ...for incineration or land fills and minimize any potential negative impact on human health and environment Li ion FCC Class B Supplier s Declaration of Conformity 47 CFR 2 1077 Compliance Information Unique Identifier EATON 5P 1550G RL Responsible Party U S Contact information Applicant Eaton Corporation Address 8609 Six Forks Road Raleigh NC 27615 USA Phone Number 800 356 5794 FCC Compliance State...

Page 4: ...ly accessible The system can be disconnected from the AC power source by opening this circuit breaker Check that the indications on the rating plate correspond to your AC powered system and to the actual electrical consumption of all the equipment to be connected to the system For PLUGGABLE EQUIPMENT the socket outlet shall be installed near the equipment and shall be easily accessible Never insta...

Page 5: ......

Page 6: ...d bear the appropriate identification symbol 01 PET n i r e b m u N s n o i t a i v e r b b A s l a i r e t a M the symbols 1 0 T E P t a l a h t h p e r e t e n e l y h t e y l o P 2 0 E P D H e n e l y h t e y l o p y t i s n e d h g i H 3 0 C V P e d i r o l h c l y n i v y l o P 4 0 E P D L e n e l y h t e y l o p y t i s n e d w o L 5 0 P P e n e l y p o r p y l o P 6 0 S P e n e r y t s y l ...

Page 7: ...Page 7 2 Presentation 2 1 Standard Installations Dimensions H W D Description Weights lb kg Dimensions inch mm D x W x H 5P 1550G RL 42 7 19 4 21 8 x 17 2 x 1 7 554 x 438 x 43 ...

Page 8: ...ication Card Socket for Connection to AC Power Source Ground Screw RS232 Communication Port Connector for ROO or RPO Control Outlets for Connection Equipment Primary Group Group 1 Programmable Outlets for Connection of Equipment Group 2 Programmable Outlets for Connection of Equipment ...

Page 9: ...ttery Indicator yellow Power On Indicator green On Off Button Down Enter Escape The following table shows the indicator status and description Indicator Status Description Green On Normal mode Yellow On Battery mode Red Active alarm see Troubleshooting on page 19 Normal mode 100 10min 100 720 W 800VA Efficiency 98 Up ...

Page 10: ... mode The UPS is operating normally The UPS is powering and protecting the equipment In AVR mode No beep The UPS is operating normally but the utility voltage is outside normal mode thresholds The UPS is powering the equipment through a Automatic Voltage Regulation device The equipment is still normally protected On Battery Battery LED is on 1 beep every 10 seconds A utility failure has occurred a...

Page 11: ...ddress 2 6 User Settings The following table displays the options that can be changed by the user Description Available Settings Default Settings Local Settings Language English Français Deutsch Italiano Português Español Русский Menus status notices and alarms UPS fault Event Log data and settings are in all supported languages English User selectable when UPS is powered for the first time LCD se...

Page 12: ...ait 10 seconds prior to restart if disabled shutdown sequence will not complete and restart will occur immediately Enable Auto restart Disable Enable Enables the product to restart automatically when mains recovers after a complete battery discharge Enable Energy saving Disable Enable If enabled UPS will shutdown after 5 min of back up time if no load is detected on the output Disable Sleep mode D...

Page 13: ...l local regulations concerning waste Recycling symbols are printed on the packing materials to facilitate sorting Front Panel Parts 5P UPS 1U Rack Kit Quick Start Safety Instructions Cable Locking Systems 1x6 Outlets RS232 Communication Cable Two Connecting Cables for the Protected Equipment USB Communication Cable ...

Page 14: ...Page 14 3 Installation 3 2 Rack Installation Follow Steps 1 through 4 for mounting the UPS on the rails 1 1 2 2 3 3 4 4 The rails and necessary hardware are supplied by Eaton ...

Page 15: ...Page 15 3 Installation 3 3 Wall Mount Installation Follow Steps 1 and 2 for mounting the UPS on the wall 2 2 2 1 1 1 ...

Page 16: ...l standard on the Network bundle models 3 It is not necessary to shutdown the UPS before installing a communication card 1 Remove the slot cover 3 secured by screws 2 Insert the communication card in the slot 3 Secure the card cover with the 2 screws Characteristics of the optocouplers communication port optional Pins 1 3 4 5 6 10 not used Pin 2 common user Pin 7 low battery Pin 8 operation on bat...

Page 17: ...ON OFF Settings on page 12 To start the UPS on battery 1 Press the button on the UPS front panel until the display illuminates and shows UPS starting The UPS cycles through Standby mode to Battery mode The indicator illuminates solid and the UPS powers your equipment 2 Check the UPS front panel display for active alarms or notices other than the Battery mode notice and notices that indicate missin...

Page 18: ...nctions are obtained by opening a contact connected between the appropriate pins of connector 4 on the rear panel of the UPS see figures below 4 Remote Control Connection and Test 1 Check that the UPS is OFF and disconnected from the AC input source 2 Remove connector 4 3 Connect a normally closed volt free contact 60 Vdc 30 Vac max 20 mA max 0 75 mm2 18 AWG cable cross section between the two pin...

Page 19: ...e of the equipment from the UPS The UPS continues to operate but may shutdown if the load increases The alarm resets when the condition becomes inactive End of battery life The end of the battery life is reached Contact your service representative for battery replacement Event A UPS event occurs Example Remote Power OFF the RPO contact has been activated to shutdown the UPS and now prevents restar...

Page 20: ... remove watches rings bracelets and all other metal objects from the hands and arms use tools with an insulated handle Battery Module Removal This operation must be performed when the UPS is OFF Battery Module Replacement Carry out the above instructions in reverse order To ensure safety and high performance use only batteries supplied by Eaton Take care to firmly press together the two parts of t...

Page 21: ... 104 F 0 to 40 C Storage temperature range 5 to 122 F 15 to 50 C Relative humidity 0 to 85 without condensation Noise level 40 dBA 1 The high and low thresholds can be adjusted using UPS settings 2 Up to 40 Hz in low sensitivity mode programmable using UPS settings 3 Adjustable to 200 208 220 230 240V must be set to the identical AC power source value When the appliance is used in EU area use an e...

Page 22: ...614 08148 01 ...

Reviews: