background image

ENGLISH

5PX 1000 RT2U 
5PX 1500 RT2U  
5PX 2200 RT2U
5PX 3000 RT2U 
5PX 3000 RT3U 
5PX EBM 48V RT2U 
5PX EBM 72V RT2U 
5PX EBM 72V RT3U

Installation  
and user manual 

Copyright © 2010 

EATON

 

All rights reserved.

Service and support:

Call your local service representative

614-03797-00_EN

Summary of Contents for 5PX 1000 RT2U

Page 1: ...PX 2200 RT2U 5PX 3000 RT2U 5PX 3000 RT3U 5PX EBM 48V RT2U 5PX EBM 72V RT2U 5PX EBM 72V RT3U Installation and user manual Copyright 2010 EATON All rights reserved Service and support Call your local se...

Page 2: ...Page 2 614 03797 00_EN...

Page 3: ...nstallation and maintenance of the UPS and batteries The 5PX models that are covered in this manual are intended for installation in an environment within 0 to 40 C free of conductive contaminant This...

Page 4: ...d be easily accessible p p The system can be disconnected from the AC power source by opening this circuit breaker Check that the indications on the rating plate correspond to your AC powered system a...

Page 5: ...16 3 6 Connection with a FlexPDU Power Distribution Unit module optional 17 3 7 Connection with a HotSwap MBP module optional 17 3 8 UPS connection without a FlexPDU or HotSwap MBP module 18 4 Operati...

Page 6: ...ver 50 of recycled cardboard p p Sacks and bags are made of polyethylene p p Packing materials are recyclable and bear the appropriate identification symbol p p 01 PET Materials Abbreviations Number i...

Page 7: ...20 6 x 17 4 x 3 4 522 x 441 2 x 86 2 5PX 1500 RT2U 64 70 29 36 5PX 2200 RT2U 65 30 29 61 5PX 3000 RT2U 87 20 39 54 25 5 x 17 4 x 3 4 647 x 441 2 x 86 2 5PX 3000 RT3U 85 60 38 80 19 6 x 17 4 x 5 1 497...

Page 8: ...ditional battery module 4 Slot for optional communication card 5 Connector for ROO remote ON OFF or RPO Remote Power OFF control 6 Connector for additional battery module 7 30A outlet L5 30R for conne...

Page 9: ...yellow Alarm Indicator red Normal mode 100 17min 1EBM 100 2 7kW 3kVA Efficiency 98 Escape Up Down Enter On Off button The following table shows the indicator status and description Indicator Status D...

Page 10: ...al mode The UPS is operating normally The UPS is powering and protecting the equipment In AVR mode Load protected LED is ON No beep The UPS is operating normally but the utility voltage is outside nor...

Page 11: ...tions that can be changed by the user Description Available settings Default settings Local settings Language English French German Italian Portuguese Spanish Russian Menus status notices and alarms U...

Page 12: ...gy saving Disable Enable If Enable UPS will shutdown after 5 min of back up time if no load is detected on the output Disable Sleep mode Disable Enable If disable LCD and communication will turn OFF i...

Page 13: ...n cable 18 Software CD ROM 19 Manual CD ROM 20 Safety instructions 21 Quick start 22 Mounting kit for 19 inch bays 23 2 supports for the upright position Rack Tower 2U version only 24 NMC communicatio...

Page 14: ...battery Note A small amount of arcing may occur when connecting the batteries This is normal and does not damage the UPS or present any safety concern A C B A Connect the battery module never pull on...

Page 15: ...3 3Tower installation Note The two supports for the tower position are used on the RT 2U version only 3 4 Rack installation Follow steps 1 to 4 for module mounting on the rails 1 1 3 4 4 3 2 The rail...

Page 16: ...ion cards optional standard on the Netpack versions It is not necessary to shutdown the UPS before installing a communication card 1 Remove the slot cover 4 secured by screws 2 Insert the communicatio...

Page 17: ...eplace the UPS without affecting the connected loads HotSwap function UPS ON OK to switch Normal UPS OUT UPS IN AC POWER ByPass HotSwap MBP 5PX 28 29 30 31 34 32 33 1 Connect the input socket 34 on th...

Page 18: ...lexPDU or HotSwap MBP module Check that the indications on the name plate located on the back of the UPS correspond to the AC power source and the true electrical consumption of the total load 10 9 8...

Page 19: ...bled See the Cold start setting in ON OFF Settings on page 12 To start the UPS on battery 1 Press the button on the UPS front panel until the UPS front panel display illuminates and shows a status of...

Page 20: ...on to shut down the UPS These functions are obtained by opening a contact connected between the appropriate pins of connector 5 on the rear panel of the UPS see figures below 5 Remote control connecti...

Page 21: ...ect the equipment anymore Note The alarm message and the UPS Serial Number then contact your service representative Troubleshooting a UPS equipped with the HotSwap MBP module Indication Diagnostic Cor...

Page 22: ...nd all other metal objects from the hands and arms p p use tools with an insulated handle p p Battery module removal E D C A B A Remove the middle panel B Remove the left hand side of the front panel...

Page 23: ...red LED on the HotSwap MBP module goes ON indicating that the load is supplied directly with AC input source power 2 Stop the UPS by pressing the button on the UPS control panel LED 29 UPS ON OK to sw...

Page 24: ...Standard l Additional modules possible up to 4 EBM 4 x 12 V 7 2 Ah 4 x 12 V 9 Ah 6 x 12V 9Ah 5PX EBM 48V RT2U 4 5PX EBM 72 V RT2U 5 5PX EBM 72 V RT3U 5 Environnement l Operating temperature range l St...

Page 25: ...Module with UPS outlets for installation in a bay There are different modules with different types of outlets HotSwap MBP UPS manual bypass module for maintenance There are different modules with diff...

Reviews: