General
Eaton's Cooper Power™ series 600 A, 25 kV Class
PUSH-OP™ adapter cap is a factory assembled
loadbreak reducing tap plug and bushing extender
with a stainless steel shroud and tin-plated copper
probe. It meets all the requirements of IEEE
Std 386™-2006 standard, Separable Connector
Systems.
The device is used to cap a 600 A PUSH-OP
type bushing interface with the 200 A loadbreak
interface, allowing for live testing and visible
grounding.
It is 200 A three-phase switching and three-
phase fault close rated. When used with Eaton's
Cooper Power series 200 A insulated protective
cap, M.O.V.E. arrester or a grounding elbow, the
PUSH-OP adapter cap provides a fully shielded,
submersible unit.
Installation
The PUSH-OP adapter cap is installed on a
de-energized 600 A special PUSH-OP bushing
interface using a clampstick tool. Refer to
Service
Information S600-19-1, 600 A, 15, 25, and 35 kV
Class PUSH-OP Bushing Adapter Cap Installation
Instructions
for installation instructions.
Production tests
Tests are conducted in accordance with IEEE Std
386™-2006 standard.
•
AC 60 Hz 1 Minute Withstand
•
40 kV
•
Minimum Corona Voltage Level
•
19 kV
Tests are conducted in accordance with Eaton
requirements.
•
Physical Inspection
•
Periodic Dissection
•
Periodic Fluoroscopic Analysis
600 A 25 kV class PUSH-OP
™
insulated adapter cap
Deadbreak Connectors
Catalog Data
CA650103EN
Effective September 2016
Supersedes 600-39 January 1990
COOPER POWER
SERIES