background image

 

 

 

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Eaton 9130 Series 

DSP firmware upgrade instructions 

 
 

 
 

10 28 349 Revision P4 

2012-04-27 

 

Summary of Contents for 9130 Series

Page 1: ...Eaton 9130 Series DSP firmware upgrade instructions 10 28 349 Revision P4 2012 04 27 ...

Page 2: ... be downloaded from http www powerware com software downloads asp Purpose Periodically Eaton releases firmware upgrades for some of its products With each new release new features become available and often some issues are improved Please reference the document Tracking of Modify table V1 28 doc in the firmware upgrade package if you are interested in knowing what enhancements and changes have bee...

Page 3: ... 9600bps Settings User Settings Serial Port Configuration Port RS232 Speed 9600 4 Connect RS 232 cable between the computer and the UPS 5 Start Watcher UpsFlash software 6 Select COM port and Bit Rate 9600bps and press Open 7 Press Open File and select an S file to be flashed e g V1 22 S 8 Press Flash Normal and unplug input power cord from the UPS 9 Wait until Flash ok notice will appear and pres...

Page 4: ...Extract the package to a temporary directory 1 2 DSP Firmware Upgrading via RS 232 Flash Normal Follow the procedure below while upgrading the DSP firmware of the UPS via RS 232 cable 1 If the UPS is feeding any load computer or other equipment turn off the load s supported by the UPS Then command the UPS to standby state by pushing button for at least three seconds In case the UPS is off complete...

Page 5: ...ade guide 1028349 Rev P4 2012 Eaton Corporation Page 5 of 11 5 Choose the right COM port typically COM1 and Bit rate 9600 then press to open COM port Choose Ups Flash Tab 6 Press and select S file to be flashed and click ...

Page 6: ... below will appear instead return to item 1 in this procedure to verify the cabling COM port settings and that the UPS is in standby state 8 Unplug the input power cord from the UPS and click The flashing will begin after a few seconds Note If Flash firmware NG message will appear during the flashing go to Chapter 1 3 DSP Firmware Upgrading via RS 232 Flash Error ...

Page 7: ...30 firmware upgrade guide 1028349 Rev P4 2012 Eaton Corporation Page 7 of 11 9 The LCD display Flashing in progress Wait until the Flash OK message will appear Click and buttons and exit from the software ...

Page 8: ...pted with Flash firmware NG message buzzer of the UPS may beep all the time 1 Keep the input power cord disconnected from the UPS 2 If Watcher UpsFlash software is not running start up the software and choose the right COM port typically COM1 and Bit rate 9600 then press to open COM port 3 Press button and select S file to be flashed e g V1 22 S and click 4 Click button The DSP flashing should beg...

Page 9: ...9130 firmware upgrade guide 1028349 Rev P4 2012 Eaton Corporation Page 9 of 11 5 Wait until the Flash OK message will appear Click and buttons and exit from the software ...

Page 10: ...9130 firmware upgrade guide 1028349 Rev P4 2012 Eaton Corporation Page 10 of 11 ...

Page 11: ...of 11 1 Wait until the Flash OK message will appear Click and buttons and exit from the software 2 Restart LanSafe Power Monitor service if it was stopped by running Services msc from Windows command prompt and there click on LanSafe Power Monitor and select Start the service ...