background image

 

MN04012006E

For more information visit: 

 

www.EatonElectrical.com

 

BACnet MS/TP Option Board OPTCJ for 9000X Drives

 

User Manual

 

August 2006
New Information

Summary of Contents for BACnet MS/TP OPTCJ

Page 1: ...MN04012006E For more information visit www EatonElectrical com BACnet MS TP Option Board OPTCJ for 9000X Drives User Manual August 2006 New Information...

Page 2: ......

Page 3: ...ALING OR USAGE OF TRADE ARE MADE REGARDING THE INFORMATION RECOMMENDATIONS AND DESCRIPTIONS CONTAINED HEREIN In no event will Eaton Electrical Inc be responsible to the purchaser or user in contract i...

Page 4: ...ings and Cautions v CHAPTER 1 GENERAL 1 1 OPTCJ Board 1 2 BACnet Fieldbus Board Layout and Connections 1 3 CHAPTER 2 INSTALLATION 2 1 Grounding Cable Shield 2 1 LED Indications 2 5 Installing the BACn...

Page 5: ...on the BACnet Board 2 5 Figure 3 1 Changing the BACnet Board Commissioning Parameter Values 3 1 Figure 3 2 Communication Status 3 2 List of Tables Table 1 1 BACnet Option Board Technical Data 1 2 Tabl...

Page 6: ...d can result in minor to moderate injury or serious damage to the product The situation described in the CAUTION may if not avoided lead to serious results Important safety measures are described in C...

Page 7: ...ngs and Cautions WARNING Internal components and circuit boards are at high potential when the drive is connected to the power source This voltage is extremely dangerous and may cause death or severe...

Page 8: ...Modbus TCP Option Board OPTCi for 9000X Drives User Manual vi For more information visit www EatonElectrical com MN04012006E August 2006...

Page 9: ...proprietary communication protocol conceived by a consortium of building management and system users BACnet has been adopted by ASHRAE American Society of Heating Refrigeration and Air conditioning En...

Page 10: ...Description Specification Connections Interface OPTCJ Pluggable connector 5 08 mm Data transfer method RS 485 MS TP half duplex Transfer cable Twisted pair 1 pair and shield Electrical isolation 500V...

Page 11: ...munication with the control board of the drive takes place through the standard Cutler Hammer Interface Board Connector Figure 1 1 Cutler Hammer BACnet Option Board OPTCJ Table 1 2 OPTCJ Bus Connector...

Page 12: ...BACnet MS TP Option Board OPTCJ for 9000X Drives User Manual 1 4 For more information visit www EatonElectrical com MN04012006E August 2006...

Page 13: ...he net Note Normally the option board has already been installed in slot D or slot E of the control board It is not necessary to detach the whole board for the grounding of the bus cable shield Just d...

Page 14: ...m MN04012006E August 2006 3 Insert the data conductors of both cables into terminals 3 Line B and 4 Line A 4 Strip the cable at such a distance from the terminal that you can fix it to the frame with...

Page 15: ...block 1 Strip about 5 cm of the cable and cut off the gray cable shield Remember to do this for both bus cables except for the last device 2 Leave no more than 1 cm of the cable outside the terminal...

Page 16: ...e RS 485 bus state should be within 200 mV to 7V or 200 mV to 7V Illegal bus state is from 200 mV to 200 mV Table 2 1 Bias Resistor Size vs Number of Node Fail Safe Biasing in OPTCJ Option Board Conne...

Page 17: ...ivation command from the drive Blinking fast once sec Option board is activated and in RUN state Option board is ready for external communication Blinking slow once 5 secs Option board is activated an...

Page 18: ...E August 2006 Installing the BACnet MS TP Option Board in an 9000X Drive CAUTION Make sure that the drive is switched OFF before an option or fieldbus board is changed or added Table 2 4 Installing th...

Page 19: ...the BACnet Option Board Continued Item Description D Install the BACnet option board in slot E on the control board of the drive Make sure the grounding plate shown below fits tightly in the clamp E M...

Page 20: ...BACnet MS TP Option Board OPTCJ for 9000X Drives User Manual 2 8 For more information visit www EatonElectrical com MN04012006E August 2006...

Page 21: ...he parameters associated with the expander board Enter the following menu level G with the Menu button right At this level you can browse through slots A to E with the Browser buttons to see what expa...

Page 22: ...Index Number is used by BACnet networks to uniquely identify BACnet nodes over the entire network including subnets The number may be programmed manually from the keypad to any in the range of 0 65535...

Page 23: ...pe are dynamically creatable using the CreateObject service 2 Whether objects of this type are dynamically deletable using the DeleteObject service 3 List of the optional properties supported 4 List o...

Page 24: ...Type X X X System Status X Vendor Name X Vendor Identifier X Model Name X Firmware Revision X Appl Software revision X Protocol Version X Protocol Revision X Services Supported X Object Types Support...

Page 25: ...General 3 Application specific bit from drives General Status Word 0 1 R BV11 General 4 Application specific bit from drives General Status Word 0 1 R BV12 General 5 Application specific bit from dri...

Page 26: ...4 Application Specific bit from the Fixed Control Word 0 1 C BV30 FBFixedControlWord Bit_15 Application Specific bit from the Fixed Control Word 0 1 C Instance ID Object Name Description Units Present...

Page 27: ...1 0 R AV21 FBProcessDataOut7 Application specific 32768 0 to 32767 0 resolution 1 0 R AV22 FBProcessDataOut8 Application specific 32768 0 to 32767 0 resolution 1 0 R AV23 Active Fault Code Active Faul...

Page 28: ...BACnet MS TP Option Board OPTCJ for 9000X Drives User Manual 3 8 For more information visit www EatonElectrical com MN04012006E August 2006...

Page 29: ...tion board added Reset 39 Device removed Option board removed Reset 40 Device unknown Unknown option board 53 Fieldbus fault The board has lost all contact with other devices on the network Duplicate...

Page 30: ...BACnet MS TP Option Board OPTCJ for 9000X Drives User Manual 4 2 For more information visit www EatonElectrical com MN04012006E August 2006...

Page 31: ......

Page 32: ...owerware Durant Heinemann Holec and MEM which globally serve the changing needs of the industrial utility light commercial residential and OEM markets For more information visit www EatonElectrical co...