APPLICATION

Linear LED luminaires are suitable for use in the following hazardous (classi-

fied) locations as defined by the National Electrical Code (NEC

®

):

The assembled luminaire shall be installed in accordance with the National 

Electric Code NFPA70.

NEC/CEC

•  Class I, Division 1, Groups C, D

•  Class I, Zone 1, Group IIB

•  Class II, Division 1, Groups E, F, G

•  Class III

•  Wet location, IP66, Type 4X
These luminaire housings shall be used with UL Listed Eaton’s Crouse-Hinds 

Series hazardous locations luminaire fitting mounting means, Cat. Nos. PM Kit 

1.25, PM Kit 1.5, PM Kit 2.0, ZP1050MTK, ZP1057MTK, MP1054MTK KIT.

UL Standards:

•  UL844 Luminaires for use in Hazardous (Classified) Locations

•  UL1598 Luminaires, UL1598A Marine

•  UL8750

CSA Standard:

•  CSA C22.2 No. 250

•  CSA C22.2 No. 137
Refer to the luminaire nameplate for specific classification information, maxi-

mum ambient temperature suitability and corresponding operating temperature 

(T-number).
Linear LED luminaire construction is designed for use indoors and outdoors in 

marine and wet locations, where moisture, dirt, corrosion, vibration and rough 

usage may be present.

INPUT VOLTAGE:

•  UNV1: 120-277 VAC 50/60 Hz

STORAGE ENVIRONMENT:

The ZPL Luminaire and accessories must be stored in an ambient from -40°C 

to +85°C.

WARNING

To avoid fire, shock and/or explosion, 

This product should be installed, inspected and maintained by a qualified 

electrician only, in accordance with all applicable electrical codes.

!

WARNING

To avoid electric shock, 

Be certain electrical power is OFF before and during installation and 

maintenance.  Fixture must be supplied by a wiring system suitable for 

Class I, Division 1 per NEC with an equipment grounding conductor.  

To avoid burning hands, make sure luminaire is cool when performing 

maintenance.

!

WARNING

To avoid explosion, 

Make sure the supply voltage is the same as the fixture voltage.
Do not install where the marked operating temperatures exceed the 

ignition temperature of the hazardous atmosphere.
Do not operate in ambient temperatures above those indicated on the 

fixture nameplate.
Use only replacement parts from Eaton’s Crouse-Hinds Division.
Use proper supply wiring as specified on the fixture nameplate.
All gasket seals must be clean and undamaged.
Before opening, electrical power to the fixture must be turned off.  Keep 

tightly closed when in operation.

!

WARNING

To avoid explosion, 

Seal luminaire conduit within 18 inches (457mm) distance and in 

accordance with local electrical code requirements and NEC Article 501 

(CEC Section 18).

!

WARNING

In RAV1 (combo) luminaire, use switch to illuminate one color at a time, 

illuminating both colors at a time may compromise product performance 

over time due to excessive heating of the internal components.

!

1132.5

44.59

165.1

6.50

895.2

35.25

45.8

1.80

74.4

2.93

112.6

4.43

103.6

4.08

63.5

2.50

Figure 1. Overall Dimensions

Summary of Contents for Crouse-Hinds Pauluhn ZPL RV1

Page 1: ...must be stored in an ambient from 40 C to 85 C WARNING To avoid fire shock and or explosion This product should be installed inspected and maintained by a qualified electrician only in accordance with...

Page 2: ...e on the top of the luminaire and position it near the center 5 Tighten the two 2 1 4 set screws on each slide bracket until they bottom see Figure 4 Torque to 78 in lbs 8 8 N m 6 Adjust the position...

Page 3: ...naPro bracket holes may be spaced as required it is recommended to keep them at least 12 305mm apart see Figure 7 4 Attach MP1054MTK kit brackets to ceiling Make sure the brackets are parallel to each...

Page 4: ...IF 1897 10 19 Copyright 2019 Eaton s Crouse Hinds Division Page 4 Figure 9 Wiring diagram for RV1 OR AV1 Luminaire Figure 10 Wiring diagram for RAV1 Luminaire...

Page 5: ...ions contained herein are based on information and tests we believe to be reliable The accuracy or completeness thereof are not guaranteed In accordance with Eaton s Crouse Hinds Division s Terms and...

Page 6: ...re ZPL et ses accessoires doivent tre stock s une temp rature ambiante comprise entre 40 C et 85 C AVERTISSEMENT Pour viter les risques d incendie de d charge lectrique ou d explosion ce produit doit...

Page 7: ...les deux 2 vis de pression de 1 4 po sur chaque support coulissant voir la figure 4 Serrer avec un couple de 8 8 N m 78 lb po 6 Ajuster la position du luminaire l angle d sir et serrer les deux 2 bou...

Page 8: ...staller un 1 adaptateur de profil avec support coulissant sur chaque support MP1054MTK Glisser le bord long de l adaptateur profil dans les fentes du support et serrer les deux 2 vis cruciformes aux e...

Page 9: ...T DE COMMANDE NOIR DU CIRCUIT DE COMMANDE 22 AWG NOIR 67 3 cm 26 5 po NOIR DU CIRCUIT DE COMMANDE VERT BLANC DU CIRCUIT DE COMMANDE NOIR DU CIRCUIT DE COMMANDE MISE LA TERRE DU BO TIER CARTE DE CIRCUI...

Page 10: ...iques contenues dans le pr sent document sont bas es sur des informations et des essais que nous croyons fiables Leur exactitude ou leur exhaustivit ne sont pas garanties Conform ment aux conditions d...

Reviews: