Description 

The Cutler Hammer C30CN Series is a magnetically operated 
lighting contactor, and is available in both open and enclosed 
forms.  These contactors are field configurable for up to twelve 
poles, with a maximum of eight normally closed “NC” poles.  
 

 

Figure 1: Mechanically Held Contactor 

 
1 MAIN 

BASE 

 
1.1  Description

 

The base of the lighting contactor (see Figure 1) has provisions 
to accept power poles at positions “1” to “6”.  Provisions are 
also provided for up to 2 “NO” and 2 “NC” auxiliary contacts.  
 

1.2 Installation 

1.  Remove all packing material from the base and all the kits. 
2.  Contactor must be mounted in the 

vertical position

 on a 

sturdy support. 

3.  Additional over-current protection may be required. Refer 

to the National Electrical Code or local electrical code as 
required.  

4.  Refer to Section 5.3 and Table D on page 3 for the wire 

size and the required torque for the coil terminals. 
 
 
 

 
2 POWER 

POLES: C320PRP1 & C320PRP2 

 
2.1 Description 

Power poles are available in both single pole  (C320PRP1) and 
double pole (C320PRP2) versions.  A maximum of twelve 
poles may be installed on the base. Positions “1” to “4” on the 
base can be configured as either normally open “NO” or “NC” 
while positions “5” and “6” can be configured as “NO” only. 

 

2.2 Removal and Conversion of Power Poles 

1.  If installed ensure that all power is disconnected. 
2.  For multiple possible configurations of the power poles, 

refer to Table A below. 

 
 

 

    Table A 

 
3.  Remove block by using a screwdriver to pull the clip as 

shown (see Figure 2).  Rotate block 180 degrees to convert 
from NO to NC or from NC to NO and install per 2.3 
below. 
 

 

Figure 2 

 

2.3 Installation of Power Poles 

1.  Check moving carrier to assure free movement  
2.  Install the block by sliding foot into slot; using a 

screwdriver pull the clip, and position block onto base. 
Release the clip.  

3.  Check for the lettering on the base. “NO” should be 

visible if the power pole is assembled as normally open, 
and  “NC” should be visible if it is assembled as normally 
closed (see Figure 3).  

# of NC Contacts Desired (3) 

Standard Catalog # C30CNE43A0 

WARNING

 

!

 

Main Base 

NO Aux. 

Contact 

NC Aux. 

Contact 

# of NO Contacts Desired (4) 

C30CN Lighting Contactor Series 

Instruction Sheet                       Pub50765

Revision A                                            Page 1 of 4

     

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DEH-41043

ECR LT#10001

Reviews: