background image

 

i-on40 

Security System 

Installation Guide 

 

Issue 7 

Summary of Contents for i-on40

Page 1: ...i on40 Security System Installation Guide Issue 7...

Page 2: ...but will not damage the equipment Caution Describes actions that will physically damage the equipment and prevent its proper function WARNING Describes actions that are hazardous to health or cause in...

Page 3: ...on 15 Step 4 Connect Wired Zones 15 Four Wire Closed Circuit Connections 15 Two Wire Closed Circuit Connections 15 Fully Supervised Loop Connections 15 Connecting Wired Zones on KEY KPZ01 only 16 Step...

Page 4: ...i on40 Page iv This page is intentionally blank...

Page 5: ...odules are i dig02 ATS2 A switched telephone network PSTN module that allows the control unit to report alarm information using standard protocols such as Fast Format SIA and Contact ID and can also s...

Page 6: ...lease see the i on Web Server Setup Guide for more instructions Note that Eaton s Security Business recommends using Internet Explorer Other browsers may not be fully compatible with the web browser i...

Page 7: ...persecurity co uk for more information about the factors affection radio signal strength Siting the Control Unit Do site the unit Upright battery at the bottom Within a protected zone As high as possi...

Page 8: ...Connector pins for Lid Tamper 5 Printed circuit board PCB 6 Cable entry holes for detector and keypad wiring 7 Transformer 8 Mains connector block Note yellow power rating label fitted next to the con...

Page 9: ...y not used in UK Figure 4 Control Unit Main Connectors i KP01 Controls and Displays 1 LCD display 2 x 20 characters 2 Programming keys 3 Navigation keys 4 Alert LEDs 5 Setting and unsetting keys 6 Pan...

Page 10: ...losed and open 6 Hold Up Alarm HUA keys 7 Number text keys Figure 9 KEY K01 KP01 KPZ01 Controls and Displays Opening the KEY K01 KP01 KPZ01 To open the unit unclip the caps covering the screws on the...

Page 11: ...onnector for control unit bus 6 Jumpers for 6a Addressing not used in i onEX control units 6b LED functions and RS485 bus termination Figure 13 KEY KP01 Keypad PCB 1 Tamper switch 2 Sounder 3 Connecto...

Page 12: ...an i on40 control unit two i kp01 keypads and 15 wired PIRs the system takes the following total quiescent current Device Current Control unit PCB 130mA 15 x PIRs at 15mA each 225mA i sd02 communicato...

Page 13: ...ck Tamper Fit and connect the combined lid back tamper provided Ensure that the switch is oriented as shown in Figure 16 Figure 16 Lid Back Tamper Item 2 in Figure 3 shows the connector for the lid ba...

Page 14: ...if the installation site has equipment that produces high levels of R F Radio Frequencies for example welding equipment If screened cable is required you should keep to the following guidelines 1 Avoi...

Page 15: ...m Re using a V2 0 Keypad From an i onEX If you wish to use a keypad that has previously been working on an i onEX system then you must first default the keypad address Eaton s Security Business recomm...

Page 16: ...ypad s local programming mode Entering Local Programming Mode 1 Apply 12Vdc to the keypad 2 Enter Installer Menu on the control unit if the keypad is connected to a system 3 Open the keypad tamper 4 P...

Page 17: ...r KEY EP used by the KEY KPZ01 1 LED window 2 Retaining Screw 3 Removable Fixing Plate 4 Permanently attached cable Figure 22 External Prox Reader KEY EP Siting the External Prox Reader Do site the Ex...

Page 18: ...igure 25 shows the wiring connections at the keypad Figure 25 Connecting the External Prox Reader Tone Volume All Keypads To alter the volume of non alarm tones from the keypad adjust the keypad sound...

Page 19: ...tem Options Wire Zone Type Panel Zones option and select 2 wire CC If required you can use one pair of zone terminals as a common tamper provided you program that zone with the type Tamper from the In...

Page 20: ...d 3 Zone 1 35 35 Alarm Keypad 3 Zone 2 36 35 Tamper Keypad 4 Zone 1 33 33 Alarm Keypad 4 Zone 2 34 33 Tamper To select the wiring type for the keypad zones use Installer Menu System Options Wired Zone...

Page 21: ...an example of a general method of using the outputs to connect a wired sounder It is possible to program the TR terminal on the control unit see item 8 in Figure 4 as either CC or FSL Use Installer Me...

Page 22: ...ector The communicator must provide 12Vdc to indicate a line fault for example if the Line Fault output at the communicator uses a relay connect the common terminal of the relay to 12Vdc and the norma...

Page 23: ...oad the Profile Or Press to start with a blank system Note The Profile may not be EN50131 compliant The factory default is EN50131 compliant The control unit loads your choice of profile and then show...

Page 24: ...of the Installer Menu 5 Assemble and close the control unit a Hook the lid of the control unit into the bottom of the case b Close the lid and then tighten the two fixing screws NOTE It is possible fo...

Page 25: ...other sub options Leaving the Installer Menu If you wish to leave the Installer Menu at any time 1 Press until the display shows the words Leave installer mode 2 Press to leave Installer menu Press if...

Page 26: ...Installer Menu and then leave it again The navigation key LEDs should now glow green Note The log is protected and cannot be erased by the Installer Restoring Factory Defaults If you wish to restore a...

Page 27: ...Way Set Instant Duress Enable User reset Zone alarms 7 Zone tampers System tampers Confirmation UK Confirmation Mode Basic DD243 BS8243 Confirmation time 8 After entry 8 Entry keypad lock 8 Sounder o...

Page 28: ...Appears only if System Options Confirmation Mode is BS8243 10 Appears only when Masking is ON 11 Appears only in EUR version 12 Appears in this position only in part setting systems 13 Appears only wh...

Page 29: ...ntly clean the lenses of any PIRs with a clean soft dry cloth Do not use water solvents or any proprietary cleaning materials Walk test all detectors Test any external sounders and strobes Replacing o...

Page 30: ...ocking Blocked for 90s after four incorrect codes or prox tags in series Blocked for a further 90s after each additional incorrect code or prox tag until next correct code or prox tag entered Proximit...

Page 31: ...to EN50130 4 Emissions Conforms to EN61000 6 3 Outputs O P 1 2 Voltage free single pole relay contacts rated 24VDC 1A O P 3 4 Open collector transistor 12VDC when inactive 0V when active 500mA max Plu...

Page 32: ...el top button is disabled 706rEUR 00 Two button HUD tilt switch transmitter 710rEUR 00 Two button HUD 726rEUR 50 Long range hand held HUD 726rEUR 60 Short range hand held HUD Detectors 713rEUR 00 Pet...

Page 33: ...N Communication ARC only i gsm02 GSM communications module i sd02 PSTN Communication module with speech dialling Accessories 703rEUR 00 4 channel 2 zone transmitter 762rEUR 00 Two Channel Receiver 768...

Page 34: ...i on40 Page 30 NOTES...

Page 35: ...i on40 Page 31 NOTES...

Page 36: ...ww coopersecurity co uk Product Support UK Tel 44 0 1594 541978 Available between 08 30 to 17 00 Monday to Friday Product Support Fax 01594 545401 email techsupport coopersecurity co uk Part Number 12...

Reviews: