34008030 /AD – Page 1
1. SOFTWARE UPDATE
Step 1
Pulsar MX 4000/5000 RT
Pulsar MX Frame
Connect the RS232 cable to the UPS and serial port of the computer.
Make sure there are no other software packages utilising the Serial Com port on your computer (like
PSP or the comm. Modules BIL.exe or CILRS232.exe).
***IMPORTANT NOTE***
1.
Make sure that all the computer power saving functions are disabled, like sleep mode or
screen saver functions. If these modes activate during the upgrade process the upgrade may
corrupt.
2.
Make sure there is no current alarms or faults on the LCD display of Pulsar MX FRAME. If
there are any alarms/faults present they must be cleared/solved before running the
upgrade.
For example, the LCD display should show a message like below with no faults on line 3:
L O A D P R O T E C T E D
x . x k V A / x x x % L O A D E D
O N L I N E MO D E
S I N G L E U P S
Below an example of a displayed internal fault that has to be solved before starting the firmware
upgrade:
L O A D P R O T E C T E D
x . x k V A / x x x % L O A D E D
I N T E R N A L F A U L T
S I N G L E U P S