Installation Leafl et 

IL04209007E-HVR

C441 Motor Insight™ Overload Relay (120V
Control Powered) Product Installation Leafl et

                  

DANGER 

HAZARDOUS VOLTAGE CAN CAUSE ELECTRIC SHOCK AND 
BURNS. TO AVOID SHOCK HAZARD, DISCONNECT ALL POWER 
BEFORE ANY WORK IS PERFORMED ON THIS DEVICE. FAILURE 
TO DO SO WILL RESULT IN PERSONAL INJURY, DEATH OR 
SUBSTANTIAL PROPERTY DAMAGE 

              

AVERTISSEMENT 

UNE TENSION ÉLECTRIQUE DANGEREUSE PEUT CAUSER DES 
CHOCS ÉLECTRIQUES ET DES BRÛLURES. POUR ÉVITER DES 
CHOCS ÉLECTRIQUES, DÉBRANCHER L’ALIMENTATION AVANT 
D’Y EFFECTUER DU TRAVAIL. L’INOBSERVATION DE CES 
INSTRUCTIONS ENTRAÎNERA DES BLESSURES CORPORELLES 
GRAVES, LA MORT OU DES DÉGÂTS MATÉRIELS SUBSTANTI-
ELS.

Voltage Ratings 

Motor Insight overload relay is powered by 120V control 
power between X1 - X2. This voltage range for the vari-
ous models is given in the following table.

Table 1.  Voltage Range

Nominal Rating

Catalog 
Number

Voltage

CONTROL POWER 
INPUT
110 - 120V

C441P3309NOUI-HVR
C441059ONOUI-HVR

110 - 120 Vac; 
(50/60 Hz)
+10% - 15%

Line Voltage

C441P3309NOUI-HVR
C441059ONOUI-HVR

0 - 1200Vac

Wiring

Pass motor leads through Motor Insight overload relay 
CT pass through. If multiple passes of the motor leads 
are required, make sure that the current flow is from 
top to bottom through Motor Insight overload relay. If 
external CTs are used, pass the 5 amp secondary of the 
external CTs through Motor Insight overload relay inter-
nal CTs. See 

Table 3A

 for wrap and CT multiplier.

Figure 1. Mount with 10-32 Hardware Torque to 25 
in-lb.

                                                                                             

Figure 2.  Typical Starter Application Sample Wiring 
Diagram

Motor Insight overload relay is factory set for manual 
reset operation. See 

Table 5

 for automatic reset opera-

tion.

      

WARNING AVERTISSEMENT 

AUTOMATIC RESET IS NOT INTENDED FOR TWO-WIRE CON-
TROL DEVICES. 

CE DISPOSITIF DE REENCLENCHEMENT AUTOMATIQUE NE 
CONVIENT PAS AUX COMMANDES À DEUX 
CONDUCTEURS. 

ATTENTION

CONTROL CIRCUITS ARE B300 RATED USE A

CPT AND SEPRATATE CONTROL WHEN LINE

VOLTAGE IS ABOVE 240VAC.

REMOTE PILOT DEVICES

2 WIRE CONTROL

3
1

NOT FOR USE

WITH AUTO RESET

OL RELAYS.

3 WIRE CONTROL

STOP

START

3

1

2

WHEN MORE THAN ONE

PUSH BUTTON STATION IS

USED OMIT CONNECTOR

“A” AND CONNECT PER

SKETCH BELOW.

STOP

START

STOP

START

“A”

3

1

2

3 PHASE

AC MOTOR

T1

L X1 N X2             95    96   97   98     X1   X2   R1    R2

A1      A2

2/T1

4/T2

6/T3

M

1 / L1    3 / L2   5 / L3

NOTE:

   X1, X2 - 120V Control Power Input.

   R1, R2 - 120V RESET INPUT

T2 T3

2/13

3/14

120V

CPT

3.90 (99.1)

3.90

 (99.1)

3.50

(88.9)

3.31 (84.1)

0.20

 (5.1)

4 Places