Installation and User Manual

MX

5000 RT — UPS
EXB RT — Extended 
Battery
Transformer 5000

Pulsar Series

Summary of Contents for Pulsar EX RT 5000

Page 1: ...www eato n co m Installation and User Manual MX 5000 RT UPS EXB RT Extended Battery Transformer 5000 Pulsar Series...

Page 2: ......

Page 3: ...er 5000 Revision History MX Installation and User Manual 86 87050 00 Revision A00 ECN 004747 04 2006 Revision A01 ECN 004773 05 2006 Copyright 2008 EATON All rights reserved For Technical Support Cust...

Page 4: ......

Page 5: ...to UPS 19 2 8 Connection to Output Receptacles 20 2 9 Connection of Extended Battery Module UPS and Transformer 20 3 Operation 3 1 Initial Start Up 21 3 2 Final Start Up Sequence 21 3 3 Operating Mode...

Page 6: ...wer Sub Module 33 7 2 Hot Swapping the Battery Sub Module 33 8 Appendices 8 1 Technical Specifications 35 EATON Customer Care Center Technical Support and Product Services Who to Contact Scheduling Fi...

Page 7: ...The cardboard we use comprises over 50 of recycled cardboard w Sacks and bags are made of polyethylene w Packing materials are recyclable and bear the appropriate identification symbol Follow all loc...

Page 8: ...andling remove watches rings bracelets and any other metal objects use tools with insulated handles Do not lay tools or metal parts on top of batteries Product Safety w The UPS connection instructions...

Page 9: ...Symbol Usage Important instructions that must always be followed Information advice help Visual indication Action Audible signal LED off LED on 86 87050 00 Page 7...

Page 10: ...86 87050 00 A02 Page 8 This page left blank intentionally...

Page 11: ...5 x 131 x 650 Transformer 5000 17 5 x 3 5 x 25 6 444 5 x 88 9 x 650 Weights in lbs kg MX 5000 RT 125 57 MX EXB RT 154 70 Transformer 5000 84 38 Dimensions H x W x D in inches mm MX 5000 RT 5 16 x 17...

Page 12: ...L6 30P 4 Connector for additional battery module 5 Slot for optional communication card 6 USB communication port 7 RS232 communication port 8 Communication port by relay 9 Connector for Remote Power O...

Page 13: ...roll down 26 Function buttons scroll up 27 Enter confirm button 28 UPS OFF button 29 UPS ON button 30 Rectifier LED 31 Battery LED 32 Inverter LED 33 Bypass LED 34 Load supplied LED 1 4 Accessories fo...

Page 14: ...X EXB RT MX EXB RT Battery Integration System Kit with Casters 86005 The Battery Integration System is intended for extended backup time configurations to conveniently stack and secure up to 5 modules...

Page 15: ...dards Recycling icons are displayed for easy selection A dangerous voltage is present inside the power module and the battery module Any operations to be carried out on these modules must be done so b...

Page 16: ...Installation in Tower Position Follow steps 1 to 3 in the illustration below to adjust the tower stands for the upright position 6 inches 17 7 inches Always keep 6 inches free space behind the UPS rea...

Page 17: ...ion Adjustment of the orientation of the logo and control panel 2 3 1 UPS module rack mounting MX RT is very heavy To ease its rack integration we strongly recommend to remove the battery tray as show...

Page 18: ...low steps 1 to 4 for rack mounting the UPS onto the rails The rails and the necessary mounting hardware are supplied by EATON Note for step 1 It is possible to adjust the position of both front mounti...

Page 19: ...ort 42 1 Connect the RS232 42 or USB 44 communication cable to the serial or USB port on the computer equipment 2 Connect the other end of the RS232 cable 42 to the RS232 7 communication port or the U...

Page 20: ...urn to normal operation Note The internal batteries will remain connected to the power sub module after RPO activation The cable is not included Installation of optional communication card 66102 2 6 R...

Page 21: ...included screwdriver 2 Insert the output cable conduit provided by others through the cable knockout 2 3 Connect the outlet cable to the output terminal block 4 Tighten the cable conduit flange and r...

Page 22: ...xceed 30 Amps 2 9 Connection of Extended Battery Module UPS and Transformer TRANSFORMER INPUT CABLE BATTERY MODULE BATTERY MODULE UPS MODULE MX TRANSFORMER MODULE 12 13 10 11 4 53 53 53 52 1 Check tha...

Page 23: ...mal AC source but not protected by the UPS Batteries are recharging an 8 hour recharge period is necessary to get full backup time LED 22 is ON LEDs 33 and 34 are green UPS Set Up i If UPS personaliza...

Page 24: ...reen The equipment is protected by the UPS ECO mode The main advantage of the Eco mode see glossary is that it reduces the consumption of electrical power Under normal condition Normal AC source avail...

Page 25: ...ment is protected by the UPS and supplied by the battery The display indicates the battery remaining backup time Low battery warning LEDs 20 21 are ON LEDs 31 32 34 are green The audible alarm beeps e...

Page 26: ...nfirmation 3 Press the scroll button 25 to select yes 4 Press confirm button 27 The UPS is now fully shut down 1 Press and hold the 0 off button 28 for 3 seconds The buzzer beeps once The load is no l...

Page 27: ...M Statistics Operation limits UPS input measurements Status and Alarms UPS output measurements Battery measurements 4 2 Access to Measurements Press the scroll button 25 to access measurements for vol...

Page 28: ...matically when Normal AC source is restored Energy Saving Disabled Enabled Automatic shutdown on battery if output load level 10 Sleep Mode Enabled Disabled Remote Command Enabled Disabled Enables con...

Page 29: ...ement User Battery Settings UPS reads number of battery modules connected From 0 to 40 Ah 5 Ah increment Deep DischargeProtect Yes No Protection against deep discharge If disable EATON warranty will b...

Page 30: ...86 87050 00 A02 Page 28 This page left blank intentionally...

Page 31: ...ry connections see section 7 2 INV THERM OVERLOAD The UPS shuts down automatically because of a major overload Check the power drawn by the connected devices and disconnect any non priority devices IN...

Page 32: ...Enter button 27 to display details See after sales support at www eaton com Follow the power sub module replacement procedure see sections 7 1 and 7 2 BATT MODULE FAULT Battery fault detected during t...

Page 33: ...CONTACT www eaton com Battery is approaching its reliability end of life Risk of dramatically reduced backup time Reset or disable LCM In case of any LCM messages displayed w For temporary reset Pres...

Page 34: ...86 87050 00 A02 Page 32 This page left blank intentionally...

Page 35: ...he faulty power sub module by another one with same power rating MX 5000 7 2 Hot Swapping the Battery Sub Module This operation must be carried out by qualified electrical personnel only The battery c...

Page 36: ...86 87050 00 A02 Page 34...

Page 37: ...X EXB Output power 5000 VA 1 4500 W 2 Electrical supply network w Rated input voltage w Input voltage range w Frequency w Power factor w Leakage current Single phase 208 V 120 156 V to 280 V 3 50 60 H...

Page 38: ...86 87050 00 A02 Page 36...

Page 39: ...Customer Care Center Customer FAQ please visit our website www eaton com Scheduling Field Service Engineer Support Scheduling of the EATON Field Service Engineers typically should be done 7 to 10 days...

Page 40: ...86 87050 00 A02 Page 38...