Rack / Tower Advanced Users Guide

Eaton Tripp Lite SmartOnline Series

Summary of Contents for Tripp Lite SmartOnline Series

Page 1: ...TXLCD2U SU1000RTXLCD2UN SU1500RTXLCD2U SU1500RTXLCDN SU2200RTXLCD2U SU2200RTXLCDN SU3000RTXLCD2U SU3000RTXLCD2UN SUINT1000LCD2U SUINT1500LCD2U SUINT2200LCD2U SUINT3000LCD2U BP36RT BP48RT BP72RT Rack T...

Page 2: ...nstruction manual may cause harmful interference to radio communications Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be requir...

Page 3: ...tes that waste electrical and electronic equipment as well as waste batteries and accumulators should not be discarded together with unseparated household waste but must be collected separately The pr...

Page 4: ...es 0 C to 40 C with batteries The system is not for use in a computer room AS DEFINED IN the standard for the Protection of Information Technology Equipment ANSI NFPA 75 US installations only S Sp pe...

Page 5: ...PS and Extended Battery Pack Tower Installation 13 2 4 4 Extended Battery Pack Tower Connections 14 3 3 I In nt te er rf fa ac ce es s a an nd d C Co om mm mu un niic ca at tiio on n 1 15 5 3 1 Contro...

Page 6: ...5 4 Replacing batteries 33 5 5 Recycling the used equipment 36 6 6 T Tr ro ou ub blle es sh ho oo ot tiin ng g 3 37 7 6 1 Typical Alarms and Faults 37 6 2 Silencing the Alarm 41 6 3 Service and Suppo...

Page 7: ...ro ot te ec ct tiio on n Tripp Lite by Eaton has implemented an environmental protection policy Products are developed according to an eco design approach Substances This product does not contain CFC...

Page 8: ...occur when you least expect it and power quality can be erratic These power problems have the potential to corrupt critical data destroy unsaved work sessions and damage hardware causing hours of los...

Page 9: ...42 5 19 3 17 7 x 17 3 x 3 4 450 x 440 x 86 5 SU2200RTXLCD2U SU2200RTXLCDN 61 6 27 9 23 8 x 17 3 x 3 4 605 x 440 x 86 5 SU3000RTXLCD2U SU3000RTXLCD2UN 63 28 6 23 8 x 17 3 x 3 4 605 x 440 x 86 5 SUINT10...

Page 10: ...itional battery module 5 Primary group outlets for connection of critical equipment 6 Group 1 programmable outlets for connection of equipment 7 Group 2 programmable outlets for connection of equipmen...

Page 11: ...or to the other battery modules 13 Connectors for automatic recognition of battery modules BP72RT 13 13 12 12 Table 3 UPS Accessories Part number Description BP36RT BP48RT BP72RT Extended Battery Mod...

Page 12: ...6 Tripp Lite by Eaton SmartOnline Series User Guide 614 21325 Rev 01 Rear Panels...

Page 13: ...ervice representative NOTE Check the battery recharge date on the shipping carton label If the date has passed and the batteries were never recharged do not use the UPS Contact your service representa...

Page 14: ...Safety instructions 21 Quick start 22 Mounting kit for 19 inch enclosures 23 2 supports for tower position Elements supplied depending on the version or optional 26 LXE communication card optional st...

Page 15: ...control panel to the UPS Do not pull on the cable or disconnect it A small amount of arcing may occur when connecting the internal batteries This is normal and will not harm personnel Connect the cabl...

Page 16: ...heir final location Figure 7 UPS Tower Install Adjustment of the orientation of the LCD panel and of the logo Figure 8 Adjusting the LCD 2 2 3 3 2 2 U UP PS S R Ra ac ck k I In ns st ta alllla at tiio...

Page 17: ...tt te er ry y P Pa ac ck k I In ns st ta alllla at tiio on n 2 2 4 4 1 1 E Ex xt te er rn na all B Ba at tt te er ry y R Ra ac ck km mo ou un nt t I In ns st ta alllla at tiio on n The external batte...

Page 18: ...ur when connecting an external battery pack to the UPS This is normal and will not harm personnel To connect the external battery packs to the UPS 1 Insert the external battery pack cable into the UPS...

Page 19: ...external battery pack s Figure 11 Rackmount External Battery Pack Connections BP36RT BP48RT BP72RT 2 2 4 4 3 3 U UP PS S a an nd d E Ex xt te en nd de ed d B Ba at tt te er ry y P Pa ac ck k T To ow...

Page 20: ...e er r C Co on nn ne ec ct tiio on ns s NOTE A small amount of arcing may occur when connecting an external battery pack to the UPS This is normal and will not harm personnel To connect the external b...

Page 21: ...4 Control Panel Online mode indicator green Fault indicator red Escape Up Down Enter On Off button Battery mode indicator orange Bypass mode indicator orange ONLINE MODE LOAD 100 2700W ESC Indicator S...

Page 22: ...gure 15 LCD Description LCD mode description Load equipment status ONLINE MODE LOAD 100 2700W ESC The following table describes the status information provided by the UPS Note If other indicator appea...

Page 23: ...ttom Row Values Displays the UPS mode load percentage and W LOAD 100 2700W ONLINE MODE The LOAD data screen specifies the amount of power that connected equipment is currently using in terms of percen...

Page 24: ...nuous data on the KWh kilowatt hour that connected equipment has consumed in the last one hour period 3 3 4 4 D Diis sp plla ay y F Fu un nc ct tiio on ns s Press the button from the UPS Home Menu to...

Page 25: ...menu AUTO START Auto start can be enabled or disabled through this menu START ON BYPASS Start on bypass can be enabled or disabled through this menu SLEEP MODE Sleep mode can be enabled or disabled th...

Page 26: ...Submenu Submenu Menu Function CONTROL GO TO BYPASS GO BACK NORMAL GO TO BYPASS GO BACK NORMAL GO TO BYPASS command is used to force ups to bypass mode from ONLINE MODE GO BACK NORMAL command is used t...

Page 27: ...ine UPS to restart automatically when mains recovers after a complete battery discharge AUTO START ENABLED Default ENABLED DISABLED The SmartOnline UPS starts up as soon as mains power is available ST...

Page 28: ...t that will actuate Output signal parameters through external contact connector INPUT DB9 4 NO Default NO ROO RPO BUILDING ALARM FORCED BYPASS ON GENERATOR SHUTDOWN CMD Delay time and active cannot se...

Page 29: ...AULT BYPASS UPS OK LOAD PROTECTED LOAD POWERED GENERAL ALARM BAT CHARGING OVLD PREALARM BAT DISCONN Sets events or fault that will actuate Output signal parameters through external contact connector o...

Page 30: ...tes 3 programmable signal inputs one Remote Power Off RPO input terminal one Remote On Off ROO input terminal one RS 232 input pin 4 Signal inputs can be configured see 3 5 User Settings Settings Com...

Page 31: ...ty connected circuits Reinforced insulation to the utility is required The RPO switch must be a dedicated latching type switch not tied into any other circuit The RPO signal must remain active for at...

Page 32: ...ys test the RPO function before applying your critical load to avoid accidental load loss Programmable Signal Outputs The Tripp Lite by Eaton SmartOnlineUPS incorporates 4 programmable signal outputs...

Page 33: ...tOnlineUPS models have one available communication bay for the following connectivity cards Network card WEBCARDLXE Provides monitoring and control using an SNMP network management platform web browse...

Page 34: ...events and it notifies you of important UPS or power information If there is a power outage and the SmartOnline UPS battery power becomes low the PowerAlert Software suite can automatically shut down...

Page 35: ...ta ar rt tiin ng g t th he e U UP PS S o on n B Ba at tt te er ry y NOTE By default the Cold Start or battery start setting is enabled from the factory To start the UPS on battery 1 Press the button o...

Page 36: ...PS The indicator illuminates Depending on overload conditions the UPS remains in Bypass mode for at least 5 seconds and will stay in this mode if three transfers to Bypass occur within 20 minutes The...

Page 37: ...ng discharge the low battery alarm is activated if the remaining runtime goes below 3 minutes or less than the setting capacity threshold 0 by default This threshold can be modified Restart battery le...

Page 38: ...32 Tripp Lite by Eaton SmartOnline Series User Guide 614 21325 Rev 01 Retrieving the Event Log...

Page 39: ...date has passed and the batteries were never recharged do not use them Contact your service representative 5 5 3 3 W Wh he en n t to o R Re ep plla ac ce e B Ba at tt te er riie es s Tripp Lite by Eat...

Page 40: ...battery supplies not having a grounded supply circuit ELECTRIC ENERGY HAZARD Do not attempt to alter any battery wiring or connectors Attempting to alter wiring can cause injury Disconnect charging so...

Page 41: ...xtended battery pack 2 Replace the extended battery pack s See 5 5 Recycling the used equipment for proper disposal A small amount of arcing may occur when connecting an extended battery pack to the U...

Page 42: ...d acid batteries and must be disposed of properly For more information contact your local recycling reuse or hazardous waste center This symbol indicates that you should not discard waste electrical o...

Page 43: ...al UPS Conditions Conditions Possible cause Action Battery mode LED is On 1 beep every 10 seconds A utility failure has occurred and the UPS is in battery mode The UPS is powering the equipment with b...

Page 44: ...to normal operation when the temperature drops 5 C below the warning level If the condition persists shut down the UPS Clear vents and remove any heat sources Allow the UPS to cool Ensure the airflow...

Page 45: ...UPS has transfered to bypass or stop 706 UPS TEMP FAULT UPS internal temperature is high due to temperature UPS has transfered to bypass or stop 70C MIN INV VOLT Inverter voltage is too low 70D MAX I...

Page 46: ...t present Please check if batteries are connected rightly or fuse is open 612 BAT TEST ABORTED Battery test condition is not met Check UPS mode is AC online or HE Load must be greater than 10 Battery...

Page 47: ...local service representative and ask for a UPS technical representative Please have the following information ready when you call for service Model number Serial number Firmware version number Date of...

Page 48: ...42 Tripp Lite by Eaton SmartOnline Series User Guide 614 21325 Rev 01 Service and Support...

Page 49: ...VA 675W SU1000RTXLCD2U SU1000RTXLCD2UN 1000VA 900W SU1500RTXLCD2U SU1500RTXLCDN 1500VA 1350W SU2200RTXLCD2U SU2200RTXLCDN 2000VA 1800W SU3000RTXLCD2U SU3000RTXLCD2UN 3000VA 2700W SUINT1000LCD2U 1000VA...

Page 50: ...CD2U 61 2 27 8 23 8 x 17 3 x 3 4 605 x 440 x 86 5 BP36RT 48 1 21 8 17 7 x 17 3 x 3 4 450 x 440 x 86 5 BP48RT 59 5 27 17 7 x 17 3 x 3 4 450 x 440 x 86 5 BP72RT 86 4 39 2 23 8 x 17 3 x 3 4 605 x 440 x 8...

Page 51: ...LV models 96 for 1K SUINT models 95 8 for 1 5K LV models 96 5 for 1 5K SUINT models 96 8 for 2K LV models 98 for 2K SUINT models 97 2 for 3K LV models 98 for 3K SUINT models 83 for 750 LV models 83 f...

Page 52: ...Primary 2 5 15R Group 1 2 5 15R Group 2 No SU1000RTXLCD2U SU1000RTXLCD2UN SU1500RTXLCD2U SU1500RTXLCDN SU2200RTXLCD2U SU2200RTXLCDN 5 20R 2 L5 20R 1 Primary 5 20R 2 Group1 5 20R 2 Group2 No SU3000RTX...

Page 53: ...losure IP rating IP20 Storage Temperatures 0 to 40 C 32 to 104 F with batteries 25 to 55 C 13 to 130 F without batteries Transit Temperature 25 to 55 C 13 to 130 F Relative Humidity 0 to 96 no condens...

Page 54: ...614 2132501 614 21325 01...