background image

Operating instructions

W3GZ50-FB02-01

Translation of the original operating instructions

ebm-papst Mulfingen GmbH & Co. KG

Bachmühle 2
D-74673 Mulfingen
Phone +49 (0) 7938 81-0
Fax +49 (0) 7938 81-110
info1@de.ebmpapst.com
www.ebmpapst.com

CONTENTS

1. SAFETY REGULATIONS AND INFORMATION

1

1. SAFETY REGULATIONS AND INFORMATION

Read these operating instructions carefully before starting work on the
device. Observe the following warnings to prevent malfunctions or
danger to persons.
These operating instructions are to be regarded as part of the device.
The device is only to be sold or passed on together with the operating
instructions.
These operating instructions may be duplicated and distributed to inform
about potential dangers and their prevention.

1.1 Hazard levels for warnings

1

1.1 Hazard levels for warnings

These operating instructions use the following hazard levels to indicate
potentially hazardous situations and important safety regulations:

DANGER

Indicates an imminently hazardous situation which will result in
death or serious injury if the specified actions are not taken.
Compliance with the instructions is imperative.

WARNING

Indicates a potentially hazardous situation which can result in
death or serious injury if the specified actions are not taken.
Exercise extreme caution while working.

CAUTION

Indicates a potentially hazardous situation which can result in
minor or moderate injury or damage to property if the specified
actions are not taken.

NOTE

A potentially harmful situation can occur and, if not avoided, can
lead to property damage.

1.2 Staff qualifications

1

1.2 Staff qualifications

The device may only be transported, unpacked, installed, operated,
maintained and otherwise used by suitably qualified, trained and
authorized technical staff.
Only authorized specialists are permitted to install the device, to carry
out a test run and to perform work on the electrical installation.

1.3 Basic safety rules

1

1.3 Basic safety rules

The safety hazards associated with the device must be assessed again
following installation in the final product.
Note the following when working on the device:

;

Do not perform any modifications, additions or conversions on the
device without the approval of ebm-papst.

1.4 Voltage

1

1.4 Voltage

;

Check the device's electrical equipment at regular intervals; see
Chapter 6.2 Safety inspection.

;

Replace loose connections and defective cables immediately.

DANGER
Electrically charged device

Risk of electric shock
→ When working on an electrically charged device, stand on a

rubber mat.

WARNING
Live terminals and connections even with device
switched off

Electric shock

2

1.5 Safety and protective features

2

1.6 Electromagnetic radiation

2

1.7 Mechanical movement

2

1.8 Emissions

2

1.9 Hot surface

2

1.10 Transport

2

1.11 Storage

3

2. INTENDED USE

4

3. TECHNICAL DATA

4

3.1 Product drawing

5

3.2 Nominal data

5

3.3 Data according to Commission Regulation (EU) 327/2011

5

3.4 Technical description

6

3.5 Mounting data

6

3.6 Transport and storage conditions

6

4. CONNECTION AND STARTUP

6

4.1 Mechanical connection

7

4.2 Electrical connection

8

4.3 Connection in terminal box

9

4.4 Factory settings

10

4.5 Connection diagram

11

4.6 Checking connections

11

4.7 Switching on the device

11

4.8 Switching off the device

11

5. INTEGRATED PROTECTIVE FEATURES

11

6. MAINTENANCE, MALFUNCTIONS, POSSIBLE
CAUSES AND REMEDIES

12

6.1 Cleaning

12

6.2 Safety inspection

12

6.3 Disposal

Item no. 51217-5-9970 · ENU · Change 89187 · Approved 2017-02-21 · Page 1 / 13

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com

Summary of Contents for W3GZ50-FB02-01

Page 1: ... suitably qualified trained and authorized technical staff Only authorized specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules The safety hazards associated with the device must be assessed again following installation in the final product Note the following when working on the de...

Page 2: ...o a standstill DANGER Ejected parts Missing protective devices may cause balancing weights or broken fan blades to be ejected and cause injuries Take appropriate safety measures WARNING Rotating device Long hair and dangling items of clothing jewelry and the like can become entangled and be pulled into the device Injuries can result Do not wear any loose fitting or dangling clothing or jewelry whi...

Page 3: ...rming all maintenance work Conveying air at an ambient air pressure between 800 mbar and 1050 mbar Using the device within the permitted ambient temperature range see Chapter 3 6 Transport and storage conditions and Chapter 3 2 Nominal data Operating the device with all protective devices Following the operating instructions Improper use In particular operating the device in the following ways is ...

Page 4: ...ameter min 4 mm max 10 mm tightening torque 4 0 6 Nm 3 Cable diameter min 9 mm max 16 mm tightening torque 6 0 9 Nm 4 Tightening torque 3 5 0 5 Nm 5 Mounting holes for AxiTop Item no 51217 5 9970 ENU Change 89187 Approved 2017 02 21 Page 4 13 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de ebmpapst com www ebmpapst com ...

Page 5: ... using a motor impeller combination in a standardized measurement setup 3 4 Technical description Weight 128 kg Fan size 1250 mm Rotor surface Painted black Electronics housing material Die cast aluminum painted black Blade material Die cast aluminum Fan housing material Sheet steel galvanized and coated with black plastic RAL 9005 Guard grille material Steel coated with black plastic RAL 9005 Num...

Page 6: ...ing that can be used for transport Ensure after installation that the impeller moves easily and that its blades are not deformed or bent and do not scrape anywhere CAUTION Cutting and crushing hazard when removing device from packaging Blades can bend Carefully remove the device from its packaging by the fan housing Strictly avoid shocks Wear safety shoes and cut resistant safety gloves CAUTION De...

Page 7: ...ast AWG 26 0 13 mm Protective earth contact resistance according to EN 61800 5 1 Compliance with the resistance specifications according to EN 61800 5 1 for the protective earth connection circuit must be verified in the end application Depending on the installation situation it may be necessary to connect an additional protective earth conductor by way of the extra protective earth terminal provi...

Page 8: ...are fed in Route the wire s not included in scope of delivery into the terminal box First connect the PE protective earth Connect the wires to the corresponding terminals Use a screwdriver to do so When connecting ensure that no wire ends fan out Fig 2 Connecting wires to terminals Seal the terminal box 4 3 3 Cable routing Water must be prevented from reaching the cable gland along the cable NOTE ...

Page 9: ...ade for the device by ebm papst Mode parameter set 1 PWM control Mode parameter set 2 PWM control Fan device address 01 Max PWM 100 Min PWM 8 Save set value to EEPROM Yes Set value requirement Analog linear Direction of action parameter set 1 Positive heating Direction of action parameter set 2 Positive heating Item no 51217 5 9970 ENU Change 89187 Approved 2017 02 21 Page 9 13 ebm papst Mulfingen...

Page 10: ...ronics enable pin open or applied voltage 5 50 VDC disable bridge to GND or applied voltage 1 VDC reset function triggers software reset after a level change to 1 VDC SELV KL 3 8 Din2 Digital input 2 Switching parameter sets 1 2 according to EEPROM setting the valid or used parameter set can be selected via bus or via digital input DIN2 Parameter set 1 pin open or applied voltage 5 50 VDC Paramete...

Page 11: ...a power supply Switching off the device for maintenance Switch off the device via the control input Do not switch the motor e g in cyclic operation on and off via power supply Disconnect the device from the power supply When disconnecting be sure to disconnect the ground connection last 5 INTEGRATED PROTECTIVE FEATURES The integrated protective functions cause the motor to switch off automatically...

Page 12: ...test The integrated EMC filter has Y capacitors The tripping current is exceeded when AC testing voltage is applied Test the device with DC voltage when you perform the legally required high voltage test The voltage to be used corresponds to the peak value of the AC voltage required by the standard What to check How to check How often What action Contact protection cover for intactness or damage V...

Page 13: ...etallic materials are generally considered to be fully recyclable Separate the components for recycling into the following categories Steel and iron Aluminum Non ferrous metal e g motor windings Plastics particularly with brominated flame retardants in accordance with marking Insulating materials Cables and wires Electronic scrap e g circuit boards Only ferrite magnets and not rare earth magnets a...