GP1, HP1 AND SP1  

DUCT AND PLENUM PROBE  

INTERNAL MOUNT INSTALLATION

 

OVERVIEW 

 

This document provides the instructions necessary 
to install Internal Mount Probes as shown in Figure 
1. Internally mounted probes are installed inside of 
the duct/plenum. Internal mounting is ideal for 
applications where access through the outside of 
the duct is limited or not possible and is also well 
suited for installation in air handling units and 
plenums. Installation consists of marking the duct 
for bracket installation and then securing the probe 
mounting 
brackets. For detailed probe information, refer to 
the Duct/Plenum Probe technical manual under 
separate cover. For detailed information on 
transmitter set up and operation of the complete 
airflow measurement station, refer to the 
associated transmitter technical manual under 
separate cover. Observe the following installation 
precautions: 

 

CAUTION 

Location of the probe(s) is critical for proper performance of the airflow station.  Probes 

must be installed in accordance with the engineer’s plans and EBTRON Minimum 

Placement Guidelines (Figures 4 and 5) for the specified location.  For additional probe 

placement detail, refer to the probe technical manual under separate cover.  

Ensure that adequate installation/service clearance exists at the installation site to 

permit installation of the probe into the duct/plenum, and that the cable length for the 

probes is sufficient to reach the planned transmitter installation.  Refer to the mechanical 

details of Figure 2.  

On applications where multiple probes are to be installed at a single measurement 

location, install probes in accordance with Figure 3 (Internal Mount Probe 

Spacing/Configuration).  In addition, when traverse data is desired (Gold Series GP1 

probes only), place the lowest numbered probe at the top of the duct for horizontal 

mounting.  For vertical mounting, place the lowest numbered probe on the left side of 

duct when viewed from the upstream side of the mounting location, with cables exiting on 

the higher side to prevent any potential moisture from accumulating on the heated 

sensors. 

Insulation that may interfere with mounting should be temporarily removed prior to 

installation and replaced afterwards. 

 

INTERNAL MOUNTING OVERVIEW 

Figure 2 provides Standard Internal Mount probe installation details. Probes are installed from inside of 
the duct or plenum using the included brackets. Internal insulation that may interfere with mounting 
should be temporarily removed to permit installation. Internal mount probes are manufactured shorter to 
permit 0.75 in (19 mm) adjustment and allow for installation clearance. Install each probe as follows 
using the convenient check boxes at each step. 

Figure 1. Internal Mount Probe

Document Number 930-0035