background image

ER6CD

600 Watt Dimmer

Install Guide

This guide covers all models of the ER6CD lighting controller. The box contents 

includes the controller with lock nut and installation guide.

Overview

The ER6CD controller is a 600 Watt dimming controller. 
The  model  ER6CD-AU-120  is    phase  adaptive  and  the  model  ER6CD-AU-277 

provides re

verse phase dimming control. They both provide dimming control 

for  line  voltage  tungsten  lamps,  2-wire  fluorescent  ballasts  and  line  voltage 

LED  drivers.  The  ER6CD-AU-120  also  controls  120V  electronic  low-voltage 

transformer loads.  Neither of these controllers can accommodate magnetic, or 

step-down transformer loads.

These controllers have a single channel dimming output and uses wireless 

technology to monitor any rooms environment, eliminating much of the wiring 

normally  required  for  distributed  lighting  control.  This  translates  into  quick 

installations with less disruption to occupants, allowing facilities to accelerate 

retrofit schedules and start saving money sooner. 
The  controller  supports  several  methods  of  configuration  making  it  easy  for 

installers and  facility operators to manage these settings without extra tools 

reducing call-backs and installation expense. 

Summary of Contents for ER6CD

Page 1: ...trols 120V electronic low voltage transformer loads Neither of these controllers can accommodate magnetic or step down transformer loads These controllers have a single channel dimming output and uses...

Page 2: ...essed while the lights are on and the timer is counting down an additional period of time is added to the timer total Example if the timer setting is 1 hour and the user presses the switch ON twice th...

Page 3: ...t specification item details that a certain value of light must be measured on a desktop The dimming light fixture providing light to the desktop is controlled The light sensor is located over the des...

Page 4: ...ange confirmation feature to provide visual feedback of a linked sensors signal strength for optimal sensor placement To evaluate the radio signal strength the sensor must be also support the test and...

Page 5: ...isrupt transmissions Fire doors elevator shafts stairwells storage areas and any large metal objects can create radio shadows and disrupt wireless transmissions It is recommended that switches and sen...

Page 6: ...off the power to the lighting circuit 2 Remove the face plates and other hardware from the junction box gaining access to the high voltage wiring 3 The dimmer mounts to the exterior of the junction b...

Page 7: ...ton marked LEARN for a half second In link mode the LEARN LED will stay ON and the POWER LED will toggle every 2 second 2 Using the switch that will be linked to the controller press the wall switch O...

Page 8: ...mming mode the Status LED will flash amber and the CLR LRN LED will indicate the current mode with specific LED colors red is Reverse Phase dimming mode and green is Forward Phase dimming mode 2 To ch...

Page 9: ...taps 10 min 3 blinks 6 taps 15 min 4 blinks 7 taps 20 min 5 blinks 8 taps 25 min 6 blinks for demonstration purposes only 2 After the controller has completed responding to the change press the sensor...

Page 10: ...ge 2 Open Loop The lighting set point can be set to an absolute value useful in open loop sensor applications The absolute value selected becomes the maximum dimming set point 1 With the light on tap...

Page 11: ...he light is dimming down up twice Press ON for three seconds 2 Click the switch ON 5 times to clear the switch click ON 5 times again to clear ALL switches and sensors and reset the controller to defa...

Page 12: ...crease the timeout in 5 minute increments 4 To continue with configuration press ON for 3 seconds the light will resume dimming down up five times To exit Smart Click press OFF for 5 seconds Light Tim...

Page 13: ...es past day lighting set point The lights will turn ON upon the next motion detected by the occupancy sensor When set for daylight harvesting operation the set point is used with a photo sensor light...

Page 14: ...wn up nine times 2 Press ON for 3 seconds Default setting is 100 Adjust the maximum light level to the brightness level desired by clicking ON to increase and OFF to decrease in 2 increments 3 To cont...

Page 15: ...Minimum Dimming Output enabled Motion sensor Time out 15 minutes Switch Time out no time out Auto ON Time out enabled with no linked switch disabled with linked rocker switch Light ON Set point 60 of...

Page 16: ...rmful interference and ii this device must accept any interference received including interference that may cause undesired operation IC RSS 210 Contains IC 5713A STM300U echoflex Powered by ETC Echof...