Smart Switched PDU Installation 

 

Important Safety Instruction 

 

There  are  no  user-serviceable  parts  inside.  Do  not  attempt  to  open  any 
part  of  Power  Distribution  Unit  (PDU).  Doing  so  may  expose  you  to 
possible shock hazard and voids the product warranty. 

 

 

 

The PDU does not provide short-circuit protection. Therefore, Echola Systems does 
not recommend plugging the unit directly into any unprotected power source, such 
as  a  wall  outlet.  Always  connect  to  an  appropriately  rated  branch  circuit’s  outlet 
which provides short-circuit protection using standard Circuit Breakers or Fuses. 

 

 

Always  maintain  reliable  earthing  of  the  PDU.  Do  not  connect  the  PDU  to  an 
ungrounded  outlet  or  adapters  or  extension  cords  that  doesn’t  have  ground 
connection. 

 

 

The power requirement of each equipment connected to the PDU’s outlet should not 
exceed  individual  outlet’s  rated  maximum  capacity  (refer  to  specification  of 
appropriate model for ratings).  

 

 

The  aggregate  power  requirements  of  equipments  connected  to  all  outlets  at  any 
time should not exceed the maximum input capacity of PDU (refer to specification of 
appropriate model for ratings). 

 

 

Install the PDU where it may be easily disconnected for service. 

 

 

The  PDU  is  designed  for  indoor  use  only.  Avoid  exposing  to  extreme  ambient 
temperatures.

 

 

Summary of Contents for SPDU-108M

Page 1: ...ny unprotected power source such as a wall outlet Always connect to an appropriately rated branch circuit s outlet which provides short circuit protection using standard Circuit Breakers or Fuses Always maintain reliable earthing of the PDU Do not connect the PDU to an ungrounded outlet or adapters or extension cords that doesn t have ground connection The power requirement of each equipment conne...

Page 2: ... www echola com power Installing in a Rack The PDU can be installed in a standard 19 rack or enclosure It can be mounted horizontally at front of the rack or vertically at the back as shown below Rack Horizontal Installation Vertical Installation at the back of the Rack Outlet 1 Outlet 8 ...

Page 3: ...as Input Output receptacle type NEMA 5 20R Maximum Output current outlet 16A Aggregate current of all outlets can t exceed Max Input current Number of Outlets 8 Outlet Current Monitoring Accuracy 10 Interfaces Network Interface RJ45 10Base T Ethernet Front Panel display 2x16 Color character LCD with LED backlight Environmental Operating Environment 32 113 F Operating Relative Humidity 0 95 Operati...

Page 4: ...Output receptacle type NEMA 5 20R Maximum Output current outlet 16A Aggregate current of all outlets can t exceed Max Input current Number of Outlets 16 Outlet Current Monitoring Accuracy 10 Interfaces Network Interface RJ45 10Base T Ethernet Front Panel display 2x16 Color character LCD with LED backlight Environmental Operating Environment 32 113 F Operating Relative Humidity 0 95 Operating Eleva...

Page 5: ...receptacle type IEC 320 C13 7 IEC 320 C19 1 Maximum Output current outlet 16A Aggregate current of all outlets can t exceed Max Input current Number of Outlets 8 Outlet Current Monitoring Accuracy 10 Interfaces Network Interface RJ45 10Base T Ethernet Front Panel display 2x16 Color character LCD with LED backlight Environmental Operating Environment 32 113 F Operating Relative Humidity 0 95 Operat...

Page 6: ...receptacle type IEC 320 C13 14 IEC 320 C19 2 Maximum Output current outlet 16A Aggregate current of all outlets can t exceed Max Input current Number of Outlets 16 Outlet Current Monitoring Accuracy 10 Interfaces Network Interface RJ45 10Base T Ethernet Front Panel display 2x16 Color character LCD with LED backlight Environmental Operating Environment 32 113 F Operating Relative Humidity 0 95 Oper...

Page 7: ...net Protcol Properties of the ethernet interface Now launch the internet browser and type http echolasys in the address bar and press Enter key Now you will be prompted with a PDU s login dialog If this is first time then use default username and password After login you will see the main menu page of the PDU Now click on the Setup tab of the menu to bring the Network Config menu From here you can...

Page 8: ...fferent user who can access to main Control Monitor page but is not allowed to access Setup page This user is by default called guest but name can be changed using Setup User tab and default password is guest as well If the authentication fails Authentication Required message will be displayed The authentication can optionally be disabled for Control Monitor web page the home page on the main menu...

Page 9: ...U through user friendly web interface The web interface uses AJAX for providing near real time update on current consumption for each outlets total current Temperature and outlet statuses To access GUI from any smart phone mobile devices just use letter m after the ipaddress or the hostname like http 192 168 2 21 m For more details on web interface please refer to User s Manual at http www echola ...

Page 10: ... perl Command Syntax perl xmlget pl http ipaddress use LWP UserAgent use XML Simple IPADDR shift create objects xml new XML Simple ua LWP UserAgent new send request for api xml REQUEST IPADDR api xml req HTTP Request new GET REQUEST req header Cookie test quest res ua request req data xml XMLin res content print them print Outlet1 Power data pow1 print Outlet2 Power data pow2 print Outlet3 Power d...

Page 11: ...f java ver 5 or early 6 versions doesn t work well with the AJAX calls that we use for real time updates You can check whether you have latest java by clicking on following link http java com en download testjava jsp and do an update to avoid this intermittent problem Also check for any malware anti virus firewall software which might block the http connection to PDU We don t support router behind...