background image

CMU 100 / 2.5.1.1 - 17
CMU 100 / 4.5.1.1 - 17
CMU 100 / 8.5.1.1 - 17

CMU 100 / x.5.1.1 - 17

 

Device:  

Document: 

Code:

Date:

CMU 100 / x.5.1.1 - 17

User manual CMUMU511

13.02.2021

CMU 100

RS485 to 2x RS232 

fallback switch

User Manual

Summary of Contents for CMU 100 / 2.5.1.1 - 17

Page 1: ...U 100 2 5 1 1 17 CMU 100 4 5 1 1 17 CMU 100 8 5 1 1 17 CMU 100 x 5 1 1 17 Device Document Code Date CMU 100 x 5 1 1 17 User manual CMUMU511 13 02 2021 CMU 100 RS485 to 2x RS232 fallback switch User Manual ...

Page 2: ...CAL APPLICATION 7 3 3 APPEARANCE 8 3 4 HARDWARE DESCRIPTION 8 3 4 1 MAIN BOARD 8 3 4 2 RS485 INTERFACE BOARD 9 3 4 3 RS232 INTERFACE BOARD 11 4 SCHEMATIC 13 5 INSTALLATION 14 5 1 INSTALLATION 14 6 COMMISSIONING MAINTENACE 15 6 1 COMMISSIONING 15 6 2 MAINTENANCE 15 7 TECHNICAL DATA 16 8 DIMENSIONS 18 9 ORDERING 19 Page Device Document Code Date 2 CMU 100 x 5 1 1 17 User manual CMUMU511 13 02 2021 ...

Page 3: ...386 51 643 411 051 643 411 Email grega flander ediseja21 com www ediseja21 com Copyright Copyright Ediseja 21 2019 All rights reserved Explanation of the symbols Read the instructions Device was tested with 2 5 kV or 500 V AC voltage to check the device insulation Device ground terminal Waste Electrical and Electronic Equipment WEEE Directive 2002 96 EC the affixed product label indicates that you...

Page 4: ... result in severe personal injury or property damage Only qualified personnel may work with described devices after being familiar with warnings and safety notices in this paper and other safety regulations Warning Device must operate completely assembled Device must be used as described No modifications of the device should be made Warning Do not open device while it is energized Hazardous voltag...

Page 5: ...ns Software s task is switching between communication ports and allows almost any combination between them 2 1 2 HARDWARE Hardware is based on main board with power supply and port switching logic On that board interface boards are attached CMU 100 can handle up to 8 different interface boards Currently available interface boards RS232 isolated RS485 Multimode Fiber Optic with ST and SMA connector...

Page 6: ...CMU 100 RS485 to 2x RS232 fallback switch Page Device Document Code Date 6 CMU 100 x 5 1 1 17 User manual CMUMU511 13 02 2021 Picture 1 CMU 100 system general diagram ...

Page 7: ...in If data comes to both master ports simultaneously master port 1 physical port 2 has priority Switch time delay is set with switches at the bottom of the device Possible timer settings are no delay 20 ms 40 ms 60 ms 80 ms 0 1 s 0 2 s 0 3 s 0 4 s 0 5 s 1s 1 2 s 1 5 s 2 s 2 5 s 5 s Wide power supply voltage allows connection to all common station batteries Additionaly it can be also connected to s...

Page 8: ...ctivity on transmit Tx line On the bottom side of device are switches and JTAG connector which is intended for downloading necessary software Do not connect anything to that connector Additional switches allows echo on each port Echo can be set on or off for each port Switches Switch 1 2 3 4 No delay OFF OFF OFF OFF 20 ms ON OFF OFF OFF 40 ms OFF ON OFF OFF 60 ms ON ON OFF OFF 80 ms OFF OFF ON OFF...

Page 9: ...re settings For proper functioning of that board some settings must be done RS485 bus termination and stabilisation baud rate RS485 bus termination and stabilisation TERMINATION At high transmission rates or long distance RS485 bus termination is necessary The termination on RS485 bus must be set on both ends of the RS485 bus STABILISATION Some device to work properly demands that RS485 must alway...

Page 10: ...face L 1 2 3 19200 4800 300 OFF OFF OFF 38400 9600 600 OFF OFF ON 57600 19200 1200 OFF ON OFF 115200 38400 2400 ON OFF OFF BAUD rate setting 19 2 kbit s is valid for all standard communication protocols that do not request special timings If special protocols small request respond time required are used please note it in order NOTE If there are problems with communication try using higher speed se...

Page 11: ...rt with DB9 female connector Supported Rx Tx and GND pins Connector pin table DB9 F 2 3 5 Description RX TX GND Direction IN OUT Device Document Code Date Page CMU 100 x 5 1 1 17 User manual CMUMU511 13 02 2021 11 Picture 6 Standard data rate vs cable lenght Picture 5 RS485 interface board appearance with switch settings ...

Page 12: ...switch Cable for connection to PC CMU 100 DB9 M pin Signal Direction PC Signal DB9 F pin 2 RX TX 3 3 TX RX 2 5 GND GND 5 Page Device Document Code Date 12 CMU 100 x 5 1 1 17 User manual CMUMU511 13 02 2021 Picture 7 DB9 Female connector ...

Page 13: ...CMU 100 RS485 to 2x RS232 fallback switch 4 SCHEMATIC Device Document Code Date Page CMU 100 x 5 1 1 17 User manual CMUMU511 13 02 2021 13 Picture 8 CMU 100 x 5 1 1 17 schematic ...

Page 14: ...ust be vibration free The admisible operating temperature must be observed Check the device for damage at unpacking If device is damaged it must not be installed but it should be send to the manufacturer for repair The device should not be opened The device should be mounted on a 35 mm rail acc to EN 50022 Attach ground wire before attaching power supply Device must be grounded during operation Si...

Page 15: ...ion must be taken into consideration Device must operate completely assembled Device must be used as described No modifications of the device should be made Attach ground wire before attaching power supply Device must be grounded during operation Check if the power supply voltage complies with device operation voltage Do not open device while it is energized Hazardous voltage is present inside the...

Page 16: ...MSTB Phoenix 2pin Power Supply Wire crossection 0 5 2 5 mm2 type single or stranded wire voltage rating 500 V colour see valid standard Ground wire crossection Cu 2 5 mm2 colour see valid standard Communication port RS485 interface type 5 M L Type RS485 Direction half duplex Speed Interface type 5 19 2 115 2 kbit s Interface type M 4 8 38 4 kbit s Interface type L 300 2400 bit s Distance up to 120...

Page 17: ... Lines out 1 Tx slowest interface defines device s maximum speed Other data Weight approx 0 35 kg Dimensions see picture H D W 105 mm 111 mm connectors 55 mm Temperature range 0 C to 55 C Humidity operating up to 95 noncondensing Enclosure Material Al IP 20 Mount type standard DIN 35 rail acc to DIN EN 50022 Class I Overvoltage category III Device Document Code Date Page CMU 100 x 5 1 1 17 User ma...

Page 18: ...CMU 100 RS485 to 2x RS232 fallback switch 8 DIMENSIONS Page Device Document Code Date 18 CMU 100 x 5 1 1 17 User manual CMUMU511 13 02 2021 Picture 10 CMU 100 x 5 1 1 17 dimensions ...

Page 19: ... optic for 1 mm plastic connector up to 40 kbit s 110 m P Multimode 820 nm fiber optic with ST connector up to 2 048 Mbit s 500 m 6 Multimode 820 nm fiber optic with SMA connector up to 2 048 Mbit s 500 m 7 Singlemode 1310 nm fiber optic with SC connector up to 2 048 Mbit s 20 km S Singlemode 1310 nm fiber optic with FC connector up to 2 048 Mbit s 20 km T Singlemode 1310 nm fiber optic with ST co...

Page 20: ...pply CMU 100 1 5 T 0 RS485 FO SM ST connector 20 km high voltage power supply CMU 100 1 5 U 0 RS485 FO VL Versatile link plastic fiber optic high voltage power supply CMU 100 1 1 P 0 RS485 ETH 10 100 Mbit s virtual com port high voltage power supply CMU 100 1 5 9 0 FO MM RS232 high voltage power supply CMU 100 1 6 1 0 FO MM FO SM SC connector 20 km up to 2 048 Mbit s high voltage power supply CMU ...

Page 21: ...r optic CMU 100 2 1 6 6 6 12 4 x FO MM RS232 to 4 x multimode fiber optic CMU 100 2 1 6 6 6 6 12 5 x FO MM RS232 to 5 x multimode fiber optic CMU 100 2 1 6 6 6 6 6 12 6 x FO MM RS232 to 6 x multimode fiber optic CMU 100 2 1 6 6 6 6 6 6 12 7 x FO MM RS232 to 7 x multimode fiber optic CMU 100 2 1 6 6 6 6 6 6 6 12 2 x FO VL RS232 to 2 x versatile link fiber optic CMU 100 2 1 P P 12 3 x FO VL RS232 to...

Page 22: ... 3 x multimode FO CMU 100 2 6 6 6 6 12 4 x FO MM Multimode fiber optic to 4 x multimode FO CMU 100 2 6 6 6 6 6 12 5 x FO MM Multimode fiber optic to 5 x multimode FO CMU 100 2 6 6 6 6 6 6 12 6 x FO MM Multimode fiber optic to 6 x multimode FO CMU 100 2 6 6 6 6 6 6 6 12 7 x FO MM Multimode fiber optic to 7 x multimode FO CMU 100 2 6 6 6 6 6 6 6 6 12 Master s Slaves Detail Type RS232 RS485 6 x FO MM...

Reviews: