background image

Ei208W/Ei208DW Stand-alone carbon monoxide detector 

 

MZZ25008 

 Ei208W/Ei208DW stand-alone carbon monoxide detector 

 

The product serves for the detection of CO (carbon monoxide) gas and 

early warning to avoid the harmful effects of this gas on human health.  

The detector is certificated  for use in building interiors,  caravans and 

boats.

  

The detector indicates excessive carbon monoxide concentration both 

optically with a LED (Ei208DW also shows the concentration data on the 

display) and acoustically using a built-in siren. 

The detector is powered with an integrated lithium battery which supplies 

the detector for its whole service life. 

 

 

Fig. 1: 1 – warning LEDs; 2 – test button; 3 – information display (Ei208DW only) 

Origin of carbon monoxide and its effects on 

the human organism 

CO (carbon monoxide) is a very dangerous gas which is poisonous even 

in small concentrations. It is generated by imperfect combustion of fossil 

fuels (natural gas, petroleum, coal, wood). The gas is colourless, tasteless 

and odourless. Therefore, it cannot be detected by the human sense and 

there is a great danger of intoxication of the human organism with this gas. 

The main carbon monoxide sources: 

  incorrectly installed or poorly set fuel-burning appliances  (gas, coal, 

fuel oils and wood) 

  blocked, poorly maintained or damaged chimneys  

  combustion engines running in confined spaces 

  portable paraffin or gas heaters in confined or badly ventilated rooms   

Effects of carbon monoxide on the  human organism depending on the 

inhalation time and CO concentration in the air 

CO 

concentration 

(ppm)

 

Inhalation time and symptoms developed

 

35 

The maximum allowable concentration for continuous 

exposure in any 8 hour period according to OSHA

 

150 

Slight headache after 1.5 hours

 

200 

Slight headache, fatigue, dizziness, nausea after 2-3 

hours

 

400 

Strong frontal headache after 1-  2 hours. Life is 

threatened after 3 hours

 

800 

Dizziness, nausea and convulsions within 45 minutes. 

Unconsciousness within 2 hours. Death within 2-3 

hours.

 

1 600 

Headache,  dizziness  and nausea within 20  minutes. 

Death within 1 hour. 

3 200 

Headache,  dizziness  and nausea within 5-10  minutes. 

Death within 25-30 minutes. 

6 400 

Headache,  dizziness  and nausea within 1-2  minutes. 

Death within 10-15 minutes. 

12 800 

Death within 1-3 minutes. 

ppm -  parts per million 

 

The same concentration of CO may have a different effect on persons 

with varying body weight or who are weakened by an illness. 

Warning: 

The CO detector may not prevent the chronic effects of carbon 

monoxide exposure, and the apparatus will not fully safeguard individuals at 

special risk.

 

Detector range and location 

Ideally, the carbon monoxide detector should be installed in every room 

containing a possible source of carbon monoxide (boilers, fireplaces, local 

heaters, etc.). It is also recommended to install the carbon monoxide 

detector in the rooms where occupants spend considerable amounts  of 

time and bedrooms where they sleep. 

 

 

Rooms with possible 

sources of carbon 

monoxide and level 

ceilings. Installation 

above the upper 

edge of any window 

or door. At least 15 

cm from the ceiling. 

Installation on the 

ceiling at least 30 cm 

from the walls. 

 

Rooms with possible 

sources of carbon 

monoxide and sloped 

ceilings.  

 

 

Bedrooms and other 

rooms remote from 

possible sources of 

carbon monoxide.  

Installation at the 

approximate height of 

1 to 2m in the 

expected breathing 

zone of the 

occupants. 

1 – unsuitable location; 2 – recommended location 

   

 

Avoid installing the detector in the following locations: 

  in the immediate vicinity of heat sources (keep it at least 1 metre 

horizontally from any heat source) 

  in an enclosed space (e.g. in a cupboard) 

  above a bath, a washbasin or heat sources  

  next to a door, a window, an air vent or anywhere where it would be 

affected by draught 

  in places where free circulation of air is obstructed (e.g. behind curtains 

or furniture) 

  in places with high levels of dust, humidity or in places where it would 

be subjected to water or steam. 

  in places with high levels of paint, thinner or solvent fumes or close to 

air fresheners 

  in places where it could be easily damaged or accidentally knocked or 

turned off 

Warning:

 Do not use the detector as a portable device or on an intermittent 

basis. 

Interfering Substances 

  The apparatus should not be exposed to excessive amounts of fumes 

from petrol, diesel, solvents, greases, alcohols and organic cleaning 

fluids. 

  The apparatus may respond to brief exhaust gas emissions e.g. during 

initial start-up of an appliance or engine. 

  Hydrogen acts as an interferon and may give rise to alarms. 

Installing the detector 

When installing the detector, abide by the procedures recommended in the 

previous paragraphs. 

Warning:

  The Installation of this CO Alarm should not be used as a 

substitute  for proper installation, use and maintenance of fuel burning 

appliances including appropriate ventilation and exhaust systems. 

In addition the CO detector must be installed by a competent person 

 

Installation steps: 

 

1)  Open the detector by turning it anti-clockwise 

2)  Attach the base to the selected place using 

screws. 

3)  Insert the detector into the plastic base  and 

secure it by turning it clockwise 

4)  Once you have inserted and secured the 

detector, it is switched on automatically with a 

built-in switch located in the detector body 

5)  If the detector is OK, all three LEDs will flash 

briefly in sequence and all symbols  on the 

display (Ei208DW) will light up. 

 

Fig. 2 

Reviews: