K100H 

DEHUMIDIFIER 

OWNER’S MANUAL

 

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

www.eipl.co.uk  

Summary of Contents for K100H

Page 1: ...Page 1 of 16 Drawing TPC450 Issue 1 Date 18 01 16 K100H DEHUMIDIFIER OWNER S MANUAL www eipl co uk...

Page 2: ...16 Drawing TPC450 Issue 1 Date 18 01 16 K100H PACKAGE CONTENTS Item Description Quantity 10185GH US Dehumidifier 1 off 3086144 Quick release hose coupling 1 off 3944110 PVC Tube 3 8 I D 7 8M TPC450 Ma...

Page 3: ...tive humidity than when the air entered the unit Continuous circulation of the room air through the dehumidifier unit gradually reduces the relative humidity in the room A digital Humidistat is includ...

Page 4: ...of refrigerants used in products manufactured by Ebac Industrial Products Ltd is as follows R134a 1300 R407c 1610 For type and weight of refrigerant contained in this unit please refer to the product...

Page 5: ...outlet grille of the dehumidifier unit must have clear space around them and not be obstructed in anyway WIRING Connect the power mains cable to a designated 30 Amp breaker As follows For Models witho...

Page 6: ...lative Humidity within the space being conditioned The required humidity level can be set as follows Press the S button once to access the set point Press the or button to change the display to the de...

Page 7: ...after carrying out the above procedures the unit does not appear to function properly refer to the Trouble Shooting section which follows or contact the Factory Service Center Discharge Pump The pump...

Page 8: ...LUBRICATING 3 To check the refrigerant charge run the unit for 20 minutes with humidistat set to maximum and briefly remove the cover The evaporator coil should be evenly frost coated across its surfa...

Page 9: ...the refrigerant compressor The charging stub should be crimped and rebrazed after servicing NEVER allow permanent service valves to be fitted to any part of the circuit Service valves may leak causing...

Page 10: ...3 Loss of refrigerant gas 1 Check all of the above 2 Contact the Factory Service Center 3 Contact the Factory Service Center Little or no defrost when required 1 Faulty Timer 2 Faulty bypass timer 1 C...

Page 11: ...cs 3014251 48 x2 3 COMPRESSOR R407c 3944915 1 4 CONDENSER COIL 3020727 1 5 EVAPORATOR COIL 3020732 1 6 DEFROST VALVE 3020833 1 7 FILTER DRYER 3020957 1 8 CONTACTOR 3930732 1 9 SOLENOID COIL 3030453 1...

Page 12: ...WRITTEN OR IMPLIED WARRANTY WITH RESPECT TO THE FOREGOING DESCRIBED MERCHANDISE For Your Records Model ____________________ S N ______________________ Date Received ______________ SAVE THIS SECTION FO...