IS--1379
IS--161/162LRJS
February 2015
Page 1 of 4
Installation & Operating Instructions
161LRJS (without test point) / 162LRJS (with test point)
Loadbreak Elbow Connectors with Jacket Seal
CONTENTS:
Elbow Connector Housing, Compression Lug, Probe, Probe Wrench, Lubricant (Do Not Substitute)
3--Sealing strips and Installation/Operating Instructions.
The 161LRJS (without test point) and 162LRJS (with test point) are designed to terminate UD cable having jacketed concentric neutral
wires and extruded insulation shielding. The elbow provides an operating interface for connecting to an Elastimold
R
15kV class (8.3kV
phase--to--ground and 14.4kV phase--to--phase) 200 ampere loadbreak bushing or accessory device with fault close rating of 10,000
amperes RMS symmetrical. Designed with a fold down extension on the cable entrance for sealing to the jacket of jacketed cable. When
other types of UD cable are to be terminated, an appropriate Elastimold
R
cable shield or grounding device must be used.
DANGER
All apparatus must be de--energized during installation
or removal of part(s) except for test point caps and
indicators that can be installed and operated
energized.
Do not touch or move energized products in the work
area.
These instructions do not attempt to provide for every
possible contingency.
Failure to follow these instructions will result in
damage to the product and serious or fatal injury.
This product should be installed only by competent
personnel trained in good safety practices involving
high voltage electrical equipment. These instructions
are not intended as a substitute for adequate training or
experience in such safety practices.
All apparatus must be installed and operated in
accordance with individual user, local, and national
work rules.
If this product is supplied with a protective shipping
cover(s), remove this shipping cover(s) and replace
with the appropriate HV insulated cap(s) or
connector(s) before submerging or energizing the
circuit.
Inspect parts for damage, rating and compatibility with
mating parts.
Excess distortion of the assembled product may result
in its failure.
After installation loadbreak products can be operated
energized per operating instructions. All deadbreak
connectors must be de--energized before operating.
Connectors must be operated with a full insulated
“hotstick” type tool. Consult the company’s safe work
practices for the required tool length.
FOR MORE INFORMATION ON PARTS, INSTALLATION RATINGS AND COMPATIBILITY, CALL THE NEAREST ELASTIMOLD
R
OFFICE.
Limited Warranty:
1. T&B warrants that its products will be free from defects in materials or workmanship for a period of two (2) years, except for tools which
are warranted separately (see warranty accompanying those products). Fisher Pierce
R
products and Elastimold
R
Reclosers are
warranted for three years; and Joslyn
t
VBT and VBU capacitor switches are warranted for four years or 40,000 operations whichever
occurs first. Upon prompt notification of a warranted defect, T&B will, at its option, repair or replace the defective product.
2. In no event shall T&B be liable for any consequential, indirect or special damages, nor will T&B be liable for transportation, labor, or other
charges arising out of the removal or reinstallation of its products. Liability for breach of warranty is limited to the cost of repair or
replacement of the warranted product only.
3. Misuse, misapplication or modification of T&B products immediately voids all warranties.
THE WARRANTIES AND REMEDIES CONTAINED HEREIN ARE EXCLUSIVE AND ARE IN LIEU OF ALL OTHER WARRANTIES AND
REMEDIES, INCLUDING BUT NOT LIMITED TO ANY IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A
PARTICULAR PURPOSE, WHICH ARE SPECIFICALLY DISCLAIMED.
IMPORTANT
1. Check contents of package to ensure they are complete
and undamaged.
2. Check all components to ensure proper fit with cable
and/or mating products.
3. Check threads by threading probe into compression lug.
If resistance is encountered prior to full assembly, check
for damage and replace damaged component.
4. Read entire installation instructions before starting.
5. Have all required tools at hand and maintain cleanliness
throughout the procedure.
Caution:
If test point cap is not installed, lubricate cap
and test point and install cap.
Compression Lug
Probe
Test Point
162LRJS Only
Operating
Eye
ASSEMBLED ELBOW
Integral
Cable Jacket
Seal
IS--1379
IS--161/162LRJS
February 2015
Printed in U.S.A.
8155 T&B Boulevard, Memphis, Tennessee 38125
(800) 888--0211 Fax: (800) 888--0690