IS--1379

IS--161/162LRJS

February 2015

Page 1 of 4

Installation & Operating Instructions

161LRJS (without test point) / 162LRJS (with test point)

Loadbreak Elbow Connectors with Jacket Seal

CONTENTS:

Elbow Connector Housing, Compression Lug, Probe, Probe Wrench, Lubricant (Do Not Substitute)

3--Sealing strips and Installation/Operating Instructions.

The 161LRJS (without test point) and 162LRJS (with test point) are designed to terminate UD cable having jacketed concentric neutral

wires and extruded insulation shielding. The elbow provides an operating interface for connecting to an Elastimold

R

15kV class (8.3kV

phase--to--ground and 14.4kV phase--to--phase) 200 ampere loadbreak bushing or accessory device with fault close rating of 10,000

amperes RMS symmetrical. Designed with a fold down extension on the cable entrance for sealing to the jacket of jacketed cable. When

other types of UD cable are to be terminated, an appropriate Elastimold

R

cable shield or grounding device must be used.

DANGER

All apparatus must be de--energized during installation

or removal of part(s) except for test point caps and

indicators that can be installed and operated

energized.
Do not touch or move energized products in the work

area.
These instructions do not attempt to provide for every

possible contingency.
Failure to follow these instructions will result in

damage to the product and serious or fatal injury.
This product should be installed only by competent

personnel trained in good safety practices involving

high voltage electrical equipment. These instructions

are not intended as a substitute for adequate training or

experience in such safety practices.
All apparatus must be installed and operated in

accordance with individual user, local, and national

work rules.

If this product is supplied with a protective shipping

cover(s), remove this shipping cover(s) and replace

with the appropriate HV insulated cap(s) or

connector(s) before submerging or energizing the

circuit.

Inspect parts for damage, rating and compatibility with

mating parts.

Excess distortion of the assembled product may result

in its failure.

After installation loadbreak products can be operated

energized per operating instructions. All deadbreak

connectors must be de--energized before operating.

Connectors must be operated with a full insulated

“hotstick” type tool. Consult the company’s safe work

practices for the required tool length.

FOR MORE INFORMATION ON PARTS, INSTALLATION RATINGS AND COMPATIBILITY, CALL THE NEAREST ELASTIMOLD

R

OFFICE.

Limited Warranty:

1. T&B warrants that its products will be free from defects in materials or workmanship for a period of two (2) years, except for tools which

are warranted separately (see warranty accompanying those products). Fisher Pierce

R

products and Elastimold

R

Reclosers are

warranted for three years; and Joslyn

t

VBT and VBU capacitor switches are warranted for four years or 40,000 operations whichever

occurs first. Upon prompt notification of a warranted defect, T&B will, at its option, repair or replace the defective product.

2. In no event shall T&B be liable for any consequential, indirect or special damages, nor will T&B be liable for transportation, labor, or other

charges arising out of the removal or reinstallation of its products. Liability for breach of warranty is limited to the cost of repair or

replacement of the warranted product only.

3. Misuse, misapplication or modification of T&B products immediately voids all warranties.
THE WARRANTIES AND REMEDIES CONTAINED HEREIN ARE EXCLUSIVE AND ARE IN LIEU OF ALL OTHER WARRANTIES AND

REMEDIES, INCLUDING BUT NOT LIMITED TO ANY IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A

PARTICULAR PURPOSE, WHICH ARE SPECIFICALLY DISCLAIMED.

IMPORTANT

1. Check contents of package to ensure they are complete

and undamaged.

2. Check all components to ensure proper fit with cable

and/or mating products.

3. Check threads by threading probe into compression lug.

If resistance is encountered prior to full assembly, check

for damage and replace damaged component.

4. Read entire installation instructions before starting.
5. Have all required tools at hand and maintain cleanliness

throughout the procedure.

Caution:

If test point cap is not installed, lubricate cap

and test point and install cap.

Compression Lug

Probe

Test Point

162LRJS Only

Operating

Eye

ASSEMBLED ELBOW

Integral

Cable Jacket

Seal

IS--1379

IS--161/162LRJS

February 2015

Printed in U.S.A.

8155 T&B Boulevard, Memphis, Tennessee 38125

(800) 888--0211 Fax: (800) 888--0690

Summary of Contents for 161LRJS

Page 1: ... operated energized per operating instructions All deadbreak connectors must be de energized before operating Connectors must be operated with a full insulated hotstick type tool Consult the company s safe work practices for the required tool length FOR MORE INFORMATION ON PARTS INSTALLATION RATINGS AND COMPATIBILITY CALL THE NEAREST ELASTIMOLDR OFFICE Limited Warranty 1 T B warrants that its prod...

Page 2: ...ires imbedded into the first mastic strip Use the third strip of mastic if needed to build up the outer diameter in the area of the first mastic location Cover all mastic with vinyl tape D Remove insulation shield and insulation from the cable end Cut squarely taking care not to nick conductor E Wire brush bare aluminum conductors and immediately install compression lug Rotate to spread inhibitor ...

Page 3: ...RAL CONNECTION A Pull the hood over the concentric neutral seal area on the cable by pulling the tabs and or rolling the seal down B Insert one end of a separate copper wire No 14 AWG 2 5mm or equivalent through the grounding eye on the elbow Twist tightly taking care not to damage the eye C Twist all neutral wires and connect to ground using appropriate connector Provide adequate slack in wires f...

Page 4: ...for energized operation 2 Firmly tighten the hotstick to the loadbreak connector pulling eye 3 Without exerting any pulling force slightly rotate clockwise the connector in order to break surface friction prior to disconnection 4 Withdraw the connector from the bushing with a fast firm straight motion being careful not to place the connector near a ground plane 5 Place connector on appropriate acc...