background image

DIN RAIL TRAILING EDGE DIMMER – DMR.732 & DMR.733 

User Manual.                                                                                                                            

(Ver.03)

 

 

 

ELECTRON S.A.

 

 

7 klm National Road Athens - Lamia, 68 Antiohias Str, 

PROFESSIONAL LIGHTING SYSTEMS

 

 

N. Philadelphia, 143 41 Athens, Greece 

info@electron.gr, www.electron.gr 

 

Tel. +30 210 2584240, Fax. +30 210 2584245 

 

DMR.732  &  DMR.733  it  is  a  single  channel  trailing  edge 
dimmer. The dimmer’s output is capable of supplying up 
to 350VA of load max. DMR.732 & DMR.733 can be used 
for  different  type  of  loads  such  LED,  Incandescent  and 
Halogen  230VAC  dimmable  lamps.  DMR.732  offers  high 
flexibility  in  terms  of  communication  and  can  be 
controlled  through  1/10V,  and  Push  button  while 
DMR.733  supports  Bluetooth  protocol  and  Push  button. 
Furthermore, 

DMR.732 

supports 

“aller 

retour” 

configuration  between  1/10V  and  Push  button.  Both 
dimmers offer overtemperature protection and have been 
designed  for  interior  use  only.  Finally,  DMR.732  & 
DMR.733  can  be  power  supplied  directly  with  230VAC 
and with their polymer case they can be easily fastened 
to DIN (EN 60715) RAIL. 

 

 

 

 

General notes and precautions. 

 

Please make sure that during the installation, DMR.732 
& DMR.733 should not be supplied with 230VAC. 

 

Designed only for indoor use.

 

 

Do not try to fix any damage or malfunction, by opening 
the  DMR.732  or  DMR.733.  There  is  a  risk  for  an 
electrical  shock  hazard  and  the  materials  and  parts 
used  in  the  DMR.732  &  DMR.733  cannot  be  replaced. 
This  must  be  done  by  an  experienced  and  specialized 
technician of your supplier. 

 

When  DMR.733  is  installed  inside  metallic 
distribution boards, its range might be reduced. 

 

Disconnect the power supply for any service. 

 

Caution:  Make  sure  that  the  total  current  of  the  loads 
that  are  going  to  be  connected  to  the  dimmer  is  not 
higher  than  the  output  current  capacity  of  the  dimmer. 
The  current  of  the  load  can  be  higher  if  their  power 
factor  is  smaller  than one. Please  refer  to  the  technical 
specifications  of  the  loads  to  learn  more  about  the 
current they consume. 

 

Compatible loads. 

 

Dimmer  DMR.732  &  DMR.733  are  operating  with  Trailing 
edge mode and therefore the loads should also operate with 
the  same  way  of  regulation.  If  your  loads  don’t indicate  the 
dimming  mode,  contact  your supplier  to  inform  you  on  this. 
The types of loads you can connect are the following: 

 

 

Dimmable  Lamps  and  luminaires  with  LED 
and operating voltage at 230VAC.

 

 

Dimmable Fluorescent lamps CFL (Compact 
Fluorescent  Lamps),  with  operating  voltage 
at 230VAC.

1

 

 

Dimmable  Electronic  transformers  for  low 
voltage lamps. 

 

 

Incandescent  and  Halogen  lamps  at 
230VAC.

 

1.

For CFL lamps start up, you may need to adjust the output 

to full for 2-3 seconds.

 

Connecting power sypply and load. 

 

DMR.732 &  DMR.733 must be  switched off at the mains 
before connecting / replacing any type of lamp or load in 
general. 

 

It is important that the total amount of the load does not 
exceed the dimmer’s rated output power. 

 

Only  230VAC  dimmable  loads  should  be  connected  to 
the dimmer’s output. 

 

 

 

The  dimmers  have  to  be  always  supplied  through  a 
Miniature Circuit Breaker (MCB) as the figure indicates. 

 

Use always MCBs with the appropriate current capacity 
according to the load. 

 

Avoid to use MCBs with current capacity over 10A. 

 

Connecting  &  controlling  the  output  with 
1/10V (DMR.732). 

 

The 1/10V input can be adjusted by connecting at the screw 

terminals (marked with a variable resistor 

) either a 100K 

log  potentiometer  or  a  sink  current  1/10V  controller.  Note 
that  the  sink  current  1/10V  controller  has  polarity  thus,  the 
positive  end  from  this  device  must  be  connected  to  the 
dimmer’s  positive  1/10V  input  (marked  with  “+”)  and  the 
negative end to the dimmer’s negative 1/10V input (marked 
with “-”). By turning the controller “clock wise”  the dimmer’s 
output level can be adjusted from 0% to 100%.  

 

Caution:  Connecting  the  controller  in  the  opposite  way 
may damage the controller or the dimmer or even both. 

Summary of Contents for DMR.732

Page 1: ...power factor is smaller than one Please refer to the technical specifications of the loads to learn more about the current they consume Compatible loads Dimmer DMR 732 DMR 733 are operating with Trailing edge mode and therefore the loads should also operate with the same way of regulation If your loads don t indicate the dimming mode contact your supplier to inform you on this The types of loads y...

Page 2: ...level and with the same direction down Dimmer s operating mode DMR 732 DMR 732 is operating in LAST mode LAST takes precedence or aller retour The dimmer is detecting the input that changed last and modifies the control level of the output accordingly For example we suppose that the Push button input has 70 level and is currently controlling the output If the level of 1 10V input changes by more t...

Page 3: ...vior of the lamps at low dimming areas The regulator is located at the center of the device and it is marked as MIN ADJUST Furthermore when you connect to the output different types of lamps and you notice that by rising the control signal of the dimmer from 0 each type of lamp starts to light up at different percentage of the control signal Then you can set the minimum output percentage with the ...

Page 4: ...n Screw terminals Output current 1 52A rms Output voltage 230VAC Output power 350 VA Dimmable Yes Phase cut Power consumption Max load 100 352 W Power supply 230VΑC 50Hz 15 Class Class II Ambient temperature 20 C 50 C Dimensions LxWxH 90mm x 36mm x 58mm Conductor size Power Supply Dimmer output 1mm 2 5mm stranded Input output controls 0 5mm 1mm stranded Standards in compliance LVD Directive EMC Di...