Three seconds after applying voltage to the
controller the actual temperature of the room
sensor is being displayed.

Calling up Parameters

Upon pressing the "Programming" key one of
the parameters numbers is displayed which are
listed on page 4 of this manual. Using the 

ñ

 or

ò

 key, you can select any other parameter.

Upon pressing "P" again, the value of the selec-
ted parameter is displayed.

Editing Parameters

A displayed value can be edited by use of the 

ñ

and 

ò

 keys. Pressing "P" again brings you back

to the parameter list and loads the edited value
into the controller.

Unlock Keys

To prevent un-authorized persons from editing
parameter values, there is a locking function
which allows only the setpoint to be changed at
any time. All other parameters must be unlok-
ked beforehand. This means that at parameter
P33 a certain value is to be set (---88---) :

- Press "P",
- Use "

ñ

" to select parameter P33

- Press "P" again
- Use "

ñ

" to set value to --88--

- Press "P" again to select parameter to edit.

If no key is hit for about one minute, the access
code is cancelled and the editing function is
locked automatically.

ELEKTRONISCHE REGELUNGEN GMBH

General

The TAR x31x series controller was designed
for controlling refrigeration and freezer devices
with all their necessary functions. There are
three standard relay outputs available and all
operation is made from the front.

Features

Following functions and features are included in
the standard type of this controller:

- Displaying actual and set temperatures

( optional °C / °F )

- Temperature control with different switching

modes.

- Internal defrost timer, different defrost modes
- Defrost termination by time and/or tempera-

ture

- Fan control by time or temperature
- Temperature warning (high/low, time-delay-

ed) with integrated buzzer

- Manual defrost
- Sensor correction

Operating and Programming

Operating the TAR is very easy since all para-
meters can be shown and edited by means of
only three keys.

D-68766 Hockenheim
Schwetzinger Str. 103

Telefon 0 62 05 / 2009-0
Telefax 0 62 05 / 2009-39

Technical Manual

  On TAR 2300 the keys are located differently.

Refrig/Freezer Contr.
TAR 1310 / 2310 / 4310

5310923- 06/02 E

valid for Software No.950627

P

TAR                      ELREHA

1            2            3

Relay position

increase 
values

decrease 
values

Programming

Display

Summary of Contents for TAR 1310

Page 1: ...ess code is cancelled and the editing function is locked automatically ELEKTRONISCHE REGELUNGEN GMBH General The TAR x31x series controller was designed for controlling refrigeration and freezer devices with all their necessary functions There are three standard relay outputs available and all operation is made from the front Features Following functions and features are included in the standard t...

Page 2: ...about 10 days on power failure Because the display has three digits only the time value comes in the following for mat Function Display All temperature values can be displayed in C or F Parameter P08 allows toggling these two display modes Temperature Control The controller compares the actual room tem perature with the setpoint P03 and according to the deviation energizes or de energizes re lay K...

Page 3: ... temperature Defrost Termination There are three ways for terminating a defrost cycle 1st thermal termination Whenever the evaporator sensor tem perature P02 is warmer than the tem perature limit set with parameter P11 defrosting is terminated 2nd termination by safety time The time set with parameter P17 is the maximum time a defrost cycle can last before it is terminated automatically 3rd manual...

Page 4: ...us P14 Defrost time 2 000 235 00 00 a m 11 50 p m Aus P15 Defrost time 3 000 235 00 00 a m 11 50 p m Aus P16 Defrost time 4 000 235 00 00 a m 11 50 p m Aus P17 Defrost safety Time 1 99 minutes 30 minutes P18 Cooling delay after defrost 0 99 minutes 0 minutes P19 Fan Stop Go Temperature total control range 0 C P20 Fan Mode 1 2 3 see text 1 P21 Fan delay after defrost 0 30 minutes 3 minutes P22 Alar...

Page 5: ...ay reads the temperature of the control room sensor After you have punched in the access code see chapter unlock keys you programm the configuration of the controller to suit your application switching mode parameter P07 display mode P08 defrost method P12 evaporator fan mode P20 and or the alarm mode P25 Thebasicsetupiscompletenow and you can edit the setpoints delay times etc If for any reason t...

Page 6: ...t K1 40 29 64 70 55 Dimensions and Wiring TAR 4310 ELREHA P E 8 Fühler gem 3 K1 Schließer 7 K3 Ventilator oder Warnen 4 K1 Öffner 5 K1 Wurzel 6 K2 Abtauen 1 Netz L 2 Netz N 10 Abtaufühler 9 Regelfühler PE mains phase mains neutral relay K1 N O relay K1 N C relay K1 common relay K2 N O relay K3 N O sensor common control sensor evaporetor sensor ...

Page 7: ...l entfernen Klappe öffnen und Schraube lösen 136 ELREHA 87 5 P TAR 2000 34 Bottom Case Mounting Holes 10 evaporator sensor F2 9 control sensor F1 8 sensor common 7 K3 fan or alarm relay N O 6 K2 defrost relay N O 5 K1 control relay N O 4 common K1 K2 K3 3 K1 control relay N C 2 mains phase 1 mains neutral ...

Page 8: ...lation with IEC 1000 4 3 is based on test results which are located on site at the manufacturer EG Statement of Conformity We state the following When operated in accordance with the technical manual the criteria have been met that are outlined in the guidelines of the council for alignment of statutory orders of the member states on electro magnetic consistency 89 336 EWG This declaration is vali...

Reviews: