Three seconds after applying voltage to the
controller the actual temperature of the room
sensor is being displayed.
Calling up Parameters
Upon pressing the "Programming" key one of
the parameters numbers is displayed which are
listed on page 4 of this manual. Using the
ñ
or
ò
key, you can select any other parameter.
Upon pressing "P" again, the value of the selec-
ted parameter is displayed.
Editing Parameters
A displayed value can be edited by use of the
ñ
and
ò
keys. Pressing "P" again brings you back
to the parameter list and loads the edited value
into the controller.
Unlock Keys
To prevent un-authorized persons from editing
parameter values, there is a locking function
which allows only the setpoint to be changed at
any time. All other parameters must be unlok-
ked beforehand. This means that at parameter
P33 a certain value is to be set (---88---) :
- Press "P",
- Use "
ñ
" to select parameter P33
- Press "P" again
- Use "
ñ
" to set value to --88--
- Press "P" again to select parameter to edit.
If no key is hit for about one minute, the access
code is cancelled and the editing function is
locked automatically.
ELEKTRONISCHE REGELUNGEN GMBH
General
The TAR x31x series controller was designed
for controlling refrigeration and freezer devices
with all their necessary functions. There are
three standard relay outputs available and all
operation is made from the front.
Features
Following functions and features are included in
the standard type of this controller:
- Displaying actual and set temperatures
( optional °C / °F )
- Temperature control with different switching
modes.
- Internal defrost timer, different defrost modes
- Defrost termination by time and/or tempera-
ture
- Fan control by time or temperature
- Temperature warning (high/low, time-delay-
ed) with integrated buzzer
- Manual defrost
- Sensor correction
Operating and Programming
Operating the TAR is very easy since all para-
meters can be shown and edited by means of
only three keys.
D-68766 Hockenheim
Schwetzinger Str. 103
Telefon 0 62 05 / 2009-0
Telefax 0 62 05 / 2009-39
Technical Manual
On TAR 2300 the keys are located differently.
Refrig/Freezer Contr.
TAR 1310 / 2310 / 4310
5310923- 06/02 E
valid for Software No.950627
P
TAR ELREHA
1 2 3
Relay position
increase
values
decrease
values
Programming
Display