Quick Start Guide

00825-0200-4410, Rev EA

May 2018

Emerson

 Wireless 1410 A/B and 1410D 

Gateway with 781 Field Link

00825-0200-4410_RevEA.fm  Page 1  Thursday, May 10, 2018  1:26 PM

Summary of Contents for 1410 A/B

Page 1: ...Quick Start Guide 00825 0200 4410 Rev EA May 2018 Emerson Wireless 1410 A B and 1410D Gateway with 781 Field Link ...

Page 2: ... all persons Explosion hazard Do not make or break any connections to the Gateway while circuits are live unless area is known to be non hazardous Explosions could result in death or serious injury Installation of this device in an explosive environment must be in accordance with the appropriate local national and international standards codes and practices Review the Product Certifications sectio...

Page 3: ...ns or major infrastructure 2 0 PC requirements 2 1 Operating system optional software only Microsoft Windows Server 2008 Standard Edition Service Pack 2 Windows Server 2008 R2 Standard Edition Service Pack 1 Windows 7 Professional Service Pack 1 Windows 7 Enterprise Service Pack 1 Windows 8 Enterprise Service Pack 1 Windows 10 Enterprise Service Pack 1 2 2 Applications Configuration of the Gateway...

Page 4: ...way Housing A DIN Rail clip B SMA to N type connection C Power light During normal operation the power indicator will be green D Ethernet port 2 When this port is activated the factory IP address is 192 168 2 10 See Table 1 on page 9 E Ethernet port 1 Use for standard communication to the webserver or other protocols enabled on the Gateway The factory IP address is 192 168 1 10 See Table 1 on page...

Page 5: ... this port is activated the factory IP address is 192 168 2 10 See Table 1 on page 9 D Ethernet port 1 When this port is activated the factory IP address is 192 168 1 10 See Table 1 on page 9 E Emerson 1410 Power and Serial connections Black terminal included in the box F Emerson Wireless 781 Field Link power and data connections Black terminal included in box A B C D E F E F ...

Page 6: ...thernet 1 Primary receptacle on the Gateway using an Ethernet cable Windows 7 1 Click the Internet Access icon on the bottom right of the screen Figure 3 Internet Access 2 Select the Network and Sharing Center 3 Select Local Area Connection Figure 4 Local Area Connection 4 Select Properties ...

Page 7: ...top is from another network record the current IP address and other settings so the PC laptop can be returned to the original network after the Gateway has been configured 6 Select the Use the following IP address button Figure 6 IP Address 7 In the IP address field enter 192 168 1 12 DeltaV Ready enter 10 5 255 12 8 In the Subnet mask field enter 255 255 255 0 ...

Page 8: ...rnet Protocol TCP IP Properties window and the Local Area Connection Properties window Windows 10 1 Select the network icon in the lower right corner 2 Select the Network settings link 3 Select Ethernet on the left hand side of the Network Settings dialog 1 2 ...

Page 9: ...ent network settings Disable proxies 1 Open web browser 2 Navigate Tools I nternet Options Connections LAN Settings may be a different process for other browsers 3 Under Proxy server uncheck the Use a proxy server box Table 1 TCP IP Network Settings Gateway PC laptop tablet Subnet Ethernet 1 192 168 1 10 192 168 1 12 255 255 255 0 Ethernet 2 192 168 2 10 192 168 2 12 255 255 255 0 ...

Page 10: ...e in password default 2 Navigate to System Settings Gateway Ethernet Communication to enter the Network Settings a Configure a static IP Address or set for DHCP and enter a Hostname b Restart application at System Settings Gateway Backup and Restore Restart Apps Note Resetting applications will temporarily disable communications with field devices 3 Disconnect the power and Ethernet cable from the...

Page 11: ...ht angle allowing the lower lip of the chassis to catch the bottom of the DIN rail 2 Apply pressure forward to snap the back of the unit securely onto the DIN rail Figure 7 Installing To remove the unit see Figure 8 1 Place a flat or rounded object such as a screw driver into the DIN clip and apply a slight pressure downwards on the object 2 Once the unit is released from the DIN rail pull backwar...

Page 12: ...and hazardous approval option of the Emerson 781 determines whether it needs to be installed with barriers NOTICE When mounting the unit in an electrical enclosure or other location comply with the appropriate local and national installation codes Verify that the installer associated hardware and installation equipment used have the proper certifications for the specific type of installation being...

Page 13: ...om the Emerson 1410D Figure 9 Emerson 1410D and 781 without Barriers Installation A Emerson Wireless1410DGateway B Attach shield pair cable Belden 3084A or equivalent C Tape back shield wire and foils D Short these terminals to enable 250 Ω terminating resistor E Emerson Wireless 781 Field Link Data A Data B Return 24 VDC Blu Wht Red Blk C E D B A Red Blk Blu Wht 10 5 30VDC Gray line means interna...

Page 14: ...t to the Emerson 1410D terminals or to a separate power supply Make sure power supply is rated to handle power drawn for the barrier Figure 10 and Figure 11 show the two variations of powering the signal barrier Figure 10 Emerson 1410D and 781 with Gateway Powered Barrier Installation A Emerson Wireless1410DGateway B Attach shield pair cable Belden 3084A C Tape back shield wire and foils D Short t...

Page 15: ...less1410DGateway B Attach shield pair cable Belden 3084A C Tape back shield wire and foils D Short these terminals for 250 Ω E Emerson Wireless 781 Field Link F I S segregation G Shield B Data Data Power Barrier Signal Barrier Red Blk Blu Wht 20 30 VDC 20 30 VDC Power Supply Data Data Safe Area A Red Blk Wht Blu Gray line means internal connection Blu Red Blk C Data A Data B Return 24 VDC E Wht D ...

Page 16: ...erson 781 side Emerson 1410D Grounding The Emerson 1410D DIN rail cabinet must be grounded as well A 6 AWG 4 11 mm European copper wire bonding connector with the shortest length possible no sharp bends and no coiling is recommended Figure 12 Emerson 1410D Grounding A 6 AWG copper wire B Protective ground C Reference ground when present D Earth May be polymer with grounding plate 2 1 A A B D ...

Page 17: ...ireless performance Ideally this will be 15 25 ft 4 6 7 6 m above the ground or 6 ft 2 m above obstructions or major infrastructure To install the remote antenna use one of the following procedures When installing remote mount antennas for the Gateway always use established safety procedures to avoid falling or contact with high power electrical lines Install remote antenna components for the Gate...

Page 18: ...ightning arrestor to a common earth point using individual high integrity low resistance means as shown in Figure 13 5 The DIN rail cabinet must be grounded as well A 6 AWG or 4 11 mm European copper wire bonding conductor with the shortest length possible no sharp bends and no coiling is recommended 6 All the outdoor connections should be made hand tight plus an 1 8th turn with a wrench and wrapp...

Page 19: ... 14 Applying Coaxial Sealant to Cable Connections Indoor outdoor cabinet and antenna Outdoor cabinet and antenna A To antenna B Coaxial RF C Drip loop D Lightning arrestor E Type N bulkhead connector F 5 8 in ring terminal G 6 AWG copper wire H Transient protection ground I Outdoor rated enclosure J Protective ground K Earth L Seal per Figure 13 Inside Outside 2 1 300 mm 11 8 in minimum bend radiu...

Page 20: ...LAN Local Area Network and not a WAN Wide Area Network 5 0 Software installation optional The 2 disk software pack contains the Security Setup Utility only required for secure host connections or OPC communications and AMS Wireless Configurator The Security Setup Utility is located on Disk 1 To install the software 1 Exit close all Windows programs including any running in the background such as v...

Page 21: ...n 8 Follow the prompts Note If the autorun function is disabled on the PC or installation does not begin automatically double click D SETUP EXE where D is the CD DVD drive on the PC and select OK For more information about the Security Setup Utility and AMS Wireless Configurator see the Emerson Wireless Gateway 1410 Reference Manual 6 0 Verify operations Operation is verified through the web inter...

Page 22: ... the same Network ID and Join Key information Once the field devices are powered they will appear on the wireless network and communications can be verified under the Explore tab using the web interface The time needed for the network to form will depend on the number of devices For more detailed installation instructions see the Emerson Wireless Gateway 1410 Reference Manual ...

Page 23: ...y interference received including interference that may cause undesired operation This device must be installed to ensure a minimum antenna separation distance of 20 cm from all persons 7 4 Ordinary Location Certification As standard the transmitter has been examined and tested to determine that the design meets the basic electrical mechanical and fire protection requirements by a nationally recog...

Page 24: ... be installed in an area of not more than Pollution Degree 2 as defined in IEC 60664 1 and in an enclosure that provides a degree of protection of at least IP54 and meets the relevant requirements of EN 60079 0 and EN 60079 15 2 External connections to the equipment must not be inserted or removed unless either the area in which the equipment is installed is known to be non hazardous or the circui...

Page 25: ...d 3 The equipment is not capable of withstanding the 500 V electrical strength test as defined in clause 6 5 1 of EN 60059 15 2010 This must be taken into account during installation 4 When fitted the surface resistivity of the remote antenna is greater than 1 GW To avoid electrostatic charge build up it must not be rubbed with a dry cloth or cleaned with solvents Note Currently not available for ...

Page 26: ...y Rosemount Inc 8200 Market Boulevard Chanhassen MN 55317 9685 USA to which this declaration relates is in conformity with the provisions of the European Union Directives including the latest amendments as shown in the attached schedule Assumption of conformity is based on the application of the harmonized standards and when applicable or required a European Union notified body certification as sh...

Page 27: ... EN 61326 1 2013 Radio Equipment Directive RED 2014 53 EU Harmonized Standards EN 300 328 V2 1 1 EN 301 489 17 V3 2 0 EN 60950 1 2006 A11 A12 A1 A2 EN 50371 2002 ATEX Directive 2014 34 EU Baseefa14ATEX0125X Type n Certificate Equipment Group II Category 3 G Ex nA IIC T4 Gc Harmonized Standards EN 60079 0 2012 A11 2013 EN 60079 15 2010 ...

Page 28: ...tified Body SGS Baseefa Limited Notified Body Number 1180 Rockhead Business Park Staden Lane Buxton Derbyshire SK17 9RZ United Kingdom ATEX Notified Body for Quality Assurance SGS Baseefa Limited Notified Body Number 1180 Rockhead Business Park Staden Lane Buxton Derbyshire SK17 9RZ United Kingdom ...

Page 29: ...bly X O O O O O ᵜ㺘Ṭ ᦞ SJ T11364Ⲵ㿴ᇊ㘼ࡦ This table is proposed in accordance with the provision of SJ T11364 O Ѫ䈕䜘ԦⲴᡰᴹ 䍘ᶀᯉѝ䈕ᴹᇣ 䍘Ⲵਜ਼䟿 վҾGB T 26572ᡰ㿴ᇊⲴ䲀䟿㾱 O Indicate that said hazardous substance in all of the homogeneous materials for this part is below the limit requirement of GB T 26572 X Ѫ 䈕䜘Ԧᡰ Ⲵᡰᴹ 䍘ᶀᯉ䟼ˈ㠣ቁᴹа 䍘ᶀᯉѝ䈕ᴹᇣ 䍘Ⲵਜ਼䟿儈ҾGB T 26572ᡰ㿴ᇊⲴ䲀䟿㾱 X Indicate that said hazardous substance contained in at lea...

Page 30: ...ent Emerson Terms and Conditions of Sale are available upon request The Emerson logo is a trademark and service mark of Emerson Electric Co Rosemount is a mark of one of the Emerson family of companies All other marks are the property of their respective owners 2018 Emerson All rights reserved Europe Regional Office Emerson Automation Solutions Neuhofstrasse 19a P O Box 1046 CH 6340 Baar Switzerla...