Appleton • 1.800.621.1506 • www.appletonelec.com
650525-001 Rev. B 10/16 • Page 1 of 1
650525-001 INSTRUCTION SHEET
Installation Instructions for Appleton™ Areamaster™ GEN 2 LED Luminaire -
Yoke Mount
FOR PROPER AND SAFE INSTALLATION OF THIS PRODUCT, PLEASE READ THE FOLLOWING INSTRUCTIONS.
Product Safety
Signal Words Defined
DANGER
indicates a hazardous situation which, if not avoided, will result in death or serious injury.
WARNING
indicates a hazardous
situation which, if not avoided, could result in death or serious injury.
CAUTION
indicates a hazardous situation which, if not avoided,
could result in minor or moderate injury.
NOTICE
is used to address practices not related to physical injury.
Safety Instructions
WARNING:
• Do not open or remove luminaire with the circuit energized.
• Do not remove or replace fuse when luminaire is energized.
• Do not use this luminaire on ungrounded systems. Failure to ground this luminaire can result in an electric shock, which may be fatal.
• Do not use on ungrounded 480 Volt circuits.
CAUTION:
• Do not look directly at the LEDs when energized.
NOTICE:
• Do not touch the LEDs; touching could leave oily deposits, causing hot spots and potential premature failure.
• This product must be installed in accordance with the applicable installation code by a person familiar with the construction and
operation of the product and the hazards involved.
• This luminaire is designed for and should be installed in accordance with the National Electrical Code
®
/Canadian Electrical Code
and all applicable local codes.
Marine & Hazardous Locations
CAUTION/ATTENTION:
• To reduce the risk of ignition of hazardous atmospheres, disconnect the luminaire from the supply circuit before opening. Keep
tightly closed when in operation.
Pour réduire le risque d’inflammation/explosion en atmosphères explosibles, isoler le luminaire du circuit d’alimentation avant
ouverture. Veillez à ce que le luminaire soit correctement fermé avant la mise sous tension.
• Make sure to tighten unused close-up plug to 400 in.-lb. after applying TLNC4 grease. TLNC4 grease shall be applied in 3 lines,
spaced approximately 120 degrees apart, perpendicular to the threads.
• Where flexible cord is used, it should be approved for extra hard, wet location usage and shall have a separate ground conductor.
Agency Ratings: (NEC/CEC)
• Class
I
, Division 2, Groups A, B, C, & D
• Class
II
, Division 1, Groups E, F, & G
• Class
II
, Division 2, Groups F & G
• Class
III
• Simultaneous Exposure
• Class
I
, Zone 2, Group
II
C
• Zone 20, Group
III
C
• Zone 21, Group
III
C
• Zone 22, Group
III
B
• Wet Locations
• Marine Outside Type (Salt Water) (For installation in USA only)
• Type 3R, 4, & 4X
• IP66 & IP67