background image

Before installation, these instructions must be carefully read and understood.

© 2019 Emerson. All Rights Reserved.

Emerson.com

CASH VALVES™

 TYPE LTC CRYOGENIC REVERSE ACTING TEMPERATURE REGULATOR

INSTALLATION, OPERATION, AND MAINTENANCE INSTRUCTIONS

DESCRIPTION

The Type LTC Temperature Control Valve 
is a double-port valve with a range of 
0 to -40°F (-17 to -40°C) for low temperature 
cut-off. As it is subject to ambient temperature 
under normal conditions, it will normally 
be in a wide-open position. A copper well is 
recommended for each installation, which 
allows the removal of the capillary bulb without 
depressurizing the system.

Note:

 Valve seat closure may take several seconds 

under normal operating conditions. In addition, 
Type LTC fails in the closed position. Type LTC is not 
intended to be bubble tight on closing. It is only meant 
to drastically reduce flow on sensing temperature 
based on set.

TECHNICAL DATA

Service:

 Liquid or gas

Sizes:

  ½", ¾", 1", 1¼", 1½" and 2"

Connections:

  Threaded union inlet and outlet

Operating temperature range:

 

0 to -40°F (-17 to -40°C)

Standard valve setting

: -20°F (-28°C)

Max. temperature limit:

 300°F (208°C)

Min. temperature limit:

 -320°F (-195°C)

Max. body pressure on all sides:

 

400 psi - see maximum pressure differentials 
table on page 3

CONSTRUCTION

Brass union ends; bronze body and trim; 
copper capillary armor and bellows; PTFE 
gasket and packing; stainless steel spring; 
copper bulb and capillary. 
Copper bulb is ½" NPT x 5.82" 
(15 mm x 147.83 mm). All parts are 
commercially cleaned for oxygen service. A 
copper well is available as an option and is 
recommended for each cryogenic application.

MAXIMUM OPERATING LIMITS

Operating temperature range is 
0 to -40°F (-17 to -40°C); standard setting is 
-20°F (-28°C). Maximum temperature limit is 
300°F (208°C); minimum temperature limit 
is -320°F (-195°C). Maximum body pressure 
on all sizes is 400 psi (27.5 bar); however, 
for proper operation, maximum pressure 
differentials as shown on page 3 must 
be observed.

VCIOM-14762-EN 22/01

WARNING

Failure to follow these instructions or to properly 
install and maintain this equipment could result in 
an explosion, fire and/or chemical contamination
causing property damage and personal injury 
or death.

Cash Valve regulators must be installed, operated 
and maintained in accordance with federal, 
state and local codes, rules and regulations 
and Emerson Process Management Regulator 
Technologies, Inc. instructions.

If the regulator vents gas or a leak develops in 
the system, service to the unit may be required. 
Failure to correct trouble could result in a
hazardous condition. 

Installation, operation and maintenance 
procedures performed by unqualified personnel 
may result in improper adjustment and unsafe 
operation. Either condition may result in 
equipment damage or personal injury. Only 
a qualified person shall install or service the 
Type LTC Temperature Regulator.

CALIFORNIA PROPOSITION 65 WARNING  

This product can expose you to chemicals 
including lead, which is known to the State of 
California to cause cancer, birth defects or other 
reproductive harm. For more information, go to 
www.P65Warnings.ca.gov.

INTRODUCTION

Scope of the Manual

This manual provides instructions for the 
installation, adjustment and maintenance for 
the Type LTC Temperature Regulator. 

Summary of Contents for CASH VALVES

Page 1: ...is available as an option and is recommended for each cryogenic application MAXIMUM OPERATING LIMITS Operating temperature range is 0 to 40 F 17 to 40 C standard setting is 20 F 28 C Maximum temperature limit is 300 F 208 C minimum temperature limit is 320 F 195 C Maximum body pressure on all sizes is 400 psi 27 5 bar however for proper operation maximum pressure differentials as shown on page 3 m...

Page 2: ...with those in the yoke 6 Using three 10 32 x 1 screws inserted in alternate holes in the bellows flange tighten the screws evenly to draw the bellows housing 7 down until it contacts the yoke 9 Install the shorter standard screws 8 in the remaining holes then replace the 10 32 x 1 slave screws with the standard screws Note An alternative method of install ing the new bellows housing to the yoke wo...

Page 3: ... fully close valve DIMENSIONS Size Dimension A B C D E in mm in mm in mm in mm in mm in mm Note Also available Separable well contact factory for more information Thermal system repair kit contact factory for more information C A E B D NPTF 5 82 6 ft approx Dia HOW TO ORDER To order repair parts refer to the cut away view of the Type LTC Regulator to identify the part required When ordering please...

Page 4: ...rvices described herein or their use or applicability All sales are governed by our terms and conditions which are available upon request We reserve the right to modify or improve the designs or specifications of such products at any time without notice Emerson Electric Co does not assume responsibility for the selection use or maintenance of any product Responsibility for proper selection use and...

Reviews: